INFIRISK 3D buildings · 1(a) Residential: block of flats

High-rise block of flats

A block of flats of 5 to 18 storeys, its top storey 13.5 to 52.5 m above ground, with shops on the ground floor, designed to Approved Document B Volume 1. Step through every floor, from the basement to the roof, and change the height to see which fire safety measures each height brings.

This building is illustrative. It is drawn to show how the guidance fits together, and it is not a fire strategy or a design for any real building. For your own building, speak to a competent fire engineer or fire risk assessor.

Every part of the building

The roof

Plant room with standby generator

  • Compartmentation
Show in the 3D model

This plant room houses a standby generator: a fixed engine that runs on fuel.

  • That makes it a place of special fire hazard, so it is enclosed in fire-resisting construction to keep a fire in here away from the rest of the building.
  • In this model the generator backs up the power to the firefighting lift, the smoke extract fans and the vents that open with them, the sprinkler pumps in the basement and the fan that keeps smoke out of the basement lobby.
  • The extract fans’ control panel is in here too, beside the generator: the mains and the generator’s supply meet there through an automatic changeover, out of the corridors and the shaft, where BS 9991 says such panels should not be.

Where it goes is this model’s choice.

REI 30Places of special fire hazard are enclosed with at least REI 30. These walls are not compartment walls.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.2Fire resisting construction enclosing places of special fire hazard should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.
  • GuidanceADB Vol 1, Appendix APlaces of special fire hazard include oil-filled transformer rooms, switch gear rooms, boiler rooms, storage spaces for fuel or other highly flammable substances, and rooms housing a fixed internal combustion engine.
  • GuidanceADB Vol 1, Diagram D6The height of the top storey excludes roof-top plant areas, so plant on the roof does not make the building taller for the height rules.
  • StandardBS 9991, clauses 35 and 36 (opens in a new tab)Places of special fire hazard, and rooms that house engineering services.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this room is both a place of special fire hazard and a plant room.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Boiler house

  • Compartmentation
Show in the 3D model

The communal boilers that heat the flats sit in their own room on the roof.

  • A boiler room is a place of special fire hazard, so it is enclosed in fire-resisting construction with a fire door, and its flue rises clear of the roof.

This model puts the boiler room on the roof to show how it is protected; in other buildings boiler rooms, tank rooms and pump rooms are often in a basement, on the ground floor or elsewhere, and the same protection applies wherever they are.

REI 30Places of special fire hazard are enclosed with at least REI 30. These walls are not compartment walls.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.2Fire resisting construction enclosing places of special fire hazard should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.
  • GuidanceADB Vol 1, Appendix APlaces of special fire hazard include oil-filled transformer rooms, switch gear rooms, boiler rooms, storage spaces for fuel or other highly flammable substances, and rooms housing a fixed internal combustion engine.
  • GuidanceADB Vol 1, Diagram D6The height of the top storey excludes roof-top plant areas, so plant on the roof does not make the building taller for the height rules.
  • StandardBS 9991, clauses 35 and 36 (opens in a new tab)Places of special fire hazard, and rooms that house engineering services.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this room is both a place of special fire hazard and a plant room.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Lift motor room

The machinery that drives the firefighting lift sits in this room above the lift well.

  • ADB counts the machinery space as part of the firefighting lift installation, with the lift car, the well, the controls and the communications.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.11A firefighting lift installation includes the lift car, lift well, lift machinery space, lift control system and lift communications system.
  • StandardBS EN 81-72 (opens in a new tab)Firefighting lifts, including their machinery spaces.Why it applies here: ADB para 15.11 asks for firefighting lift installations to conform to BS EN 81-72, and the machinery space is part of the installation. ADB names the 2015 edition; this page uses the current edition, BS EN 81-72:2020.
  • StandardBS 9991, clause 41.2 (opens in a new tab)Lift machine rooms and machinery spaces.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the lift’s machine room.

INFIRISK guides

No INFIRISK guide on this yet.

Only in this building at: Over 18 m, Over 30 m, Over 50 m.

Show in the 3D model

Smoke shaft head

The tops of the two smoke shafts.

  • At this height each carries smoke extract fans instead of an open vent: the shaft is closed at roof level by a low upstand, and the fans on it throw the smoke straight up, clear of the roof and of the stair head or lift motor room beside it.
  • Below 30 m this model shows open, louvred heads, which ADB para 3.55 would accept at any height.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.55(b)The shaft should be open at roof level, at least 0.5 m above any structures within 2 m of it horizontally, and extend at least 2.5 m above the ceiling of the highest storey it serves. The vent at its head should have at least 1 m2 free area.Why it applies here: ADB would accept an open head at any height; from 30 m this model follows BS 9991 and closes the shaft at the roof under its extract fans instead.
  • StandardBS 9991, clauses 20.2.4 and 20.2.2.3 (opens in a new tab)Where a storey is 30 m or more above ground, the stairs and lobbies are protected by a mechanical system: a pressure differential system, or a mechanical smoke ventilation system in the protected corridor with an automatic vent, at least 0.7 m² in aerodynamic free area, as high as practicable at the top of the stair.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this block has a storey 30 m or more above ground, so its corridor smoke shafts are mechanical.
Show in the 3D model

Smoke extract fans

Two fans at the head of a mechanical smoke shaft: one on duty, and one on standby that starts on its own if the first fails.

  • When smoke is detected in a corridor they draw it up the shaft and throw it out above the roof.
  • They run on the mains with a second supply behind it, and they are built to keep running in hot smoke.

In this model two pairs stand on the heads of the two smoke shafts, one beside the head of Stair B and one beside the lift motor room, at Over 30 m and Over 50 m only: below 30 m the shafts are natural.

  • Their stacks throw the smoke out 3.4 m above the roof, higher than the stair head and the lift motor room beside them.
  • Their control panel is in the roof plant room, beside the standby generator that is their second supply, and the replacement air comes in through the vent at the head of the stair.

These placings are this model’s own; a real design takes them from its computer model of the smoke flow.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • StandardBS EN 12101, Part 3 (opens in a new tab)Powered smoke and heat control ventilators: smoke extract fans.Why it applies here: BS 9991 asks for smoke extract fans to BS EN 12101-3, able to handle gas at 300 °C for at least 60 minutes.
  • StandardBS EN 12101, Part 10 (opens in a new tab)Power supplies for smoke and heat control systems.Why it applies here: The vents open on electric actuators, and BS 9991 asks for a secondary supply to BS EN 12101-10 wherever a smoke control mechanism is powered by electricity.
  • StandardBS 9991, Annex F, F.2.1, F.3.2.1 and F.5.3 (opens in a new tab)The fans of a mechanical smoke ventilation system: a duty fan and a standby fan that starts on its own if the duty fan fails, on a secondary power supply as well as the mains, to BS EN 12101-3 and able to handle gas at 300 °C for at least 60 minutes. Control panels are kept out of common areas and smoke shafts.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and these are the extract fans of this block’s mechanical smoke shafts.

Only in this building at: Over 30 m, Over 50 m.

Show in the 3D model

Vents at the head of the stairs

Each stair has a vent to the outside at its top.

  • In this model, when smoke is found in one half of a corridor, the vent at the head of the stair that half of the corridor leads to opens together with that half’s vent, letting out smoke that gets into the stair when doors are opened.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.56A vent to the outside with a minimum free area of 1 m2 should be provided from the top storey of the stair.
  • GuidanceADB Vol 1, para 3.55(b)(iv)With a natural smoke shaft, the vents on the storey where the fire is, at the top of the smoke shaft and to the stair open at the same time.
  • GuidanceADB Vol 1, para 15.8The stair and lobby of the firefighting shaft should have a means of venting smoke and heat.
  • StandardBS 9999, clause 27.1 (opens in a new tab)Smoke control for firefighting shafts, as referred to by ADB para 15.8.Why it applies here: Stair A is a firefighting stair, and ADB para 15.8 points to this clause for how it is vented.
  • StandardBS 9991, clause 20.1 (opens in a new tab)The smoke control provisions for residential buildings.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the stair vents are part of this block’s smoke control.
  • StandardBS 9991, clauses 20.1 and 20.2.2.1, and Table 3 (opens in a new tab)Where vents discharge into a smoke shaft, detection in the common corridor or lobby opens together the vents on the fire floor, the top of the shaft and the vent on the stairway, and the vents on every other storey stay shut. Only the vent from the lobby or corridor where smoke was found opens, and no other lobby vent opens with it. A vent at the top of a stair works on detection in a lobby or corridor next to that stair. Table 3 lists one vent at the head of the stair.Why it applies here: This model reads each half of the corridor, either side of the cross-corridor door, as a corridor of its own, with its own detector, vent and shaft: that reading is the model’s own. Clause 20.2.2.1 is written under the heading for 11 m to under 18 m; above that this model applies it by analogy.
Show in the 3D model

Dry riser head and roof outlet

The top of the dry riser.

  • An air release valve lets air out as water fills the main, and lets it back in when the main drains.
  • A landing valve at roof level is for testing the main, and is provided where it is practicable.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • StandardBS 9990, clause 4.1.3.4 (opens in a new tab)An air release valve is fitted at the top of a dry rising main. It lets air out when the main is charged and helps it drain afterwards.Why it applies here: This block has a dry rising main, and BS 9990, the standard ADB para 14.5 names for fire mains, asks for the valve at its top.
  • StandardBS 9990, clause 4.1.5 (opens in a new tab)On a dry main, a landing valve is provided at roof level for testing, where practicable.Why it applies here: The dry riser has to be tested, and this clause provides an outlet at roof level for that where it is practicable.
  • Ongoing dutyFire Safety Order 2005, Article 38Facilities and equipment provided for firefighters, such as the fire main, are kept maintained in efficient working order and good repair.
  • StandardBS 9991, clause 47.1 and Figure 47 (opens in a new tab)Fire mains, and where their outlets sit in a firefighting shaft.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the fire main this part belongs to.

INFIRISK guides

No INFIRISK guide on this yet.

Only in this building at: Over 11 m, Over 18 m, Over 30 m.

Show in the 3D model

A typical floor

Firefighting stair (Stair A)

  • Means of escape
  • Firefighting
Show in the 3D model

This firefighting stair sits inside the firefighting shaft with the firefighting lobby and lift.

  • Its walls and doors resist fire, so it stays usable while a fire burns on this floor.
  • Residents use it to escape.
  • Firefighters use it to reach the fire floor, and the fire main outlet is on its landing.

On each floor Stair A’s door opens into the stair, the way people escape.

  • It stands in a recess 1 m deep, cut out of the firefighting lobby, so as it swings it narrows neither the lobby nor the landing, as the guidance asks for a door that opens towards a stair.
  • The landing beyond the recess is 1.7 m deep, and the half landing is deeper still: each is at least as deep as the flights are wide, as Approved Document K asks.

REI 120 / REI 60Shaft enclosure: 120 minutes from the flats side, 60 minutes from inside the shaft. REI 60 between the stair, lift shaft and lobby. Stair door E 30 Sa.

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.2A building with a storey more than 18 m above fire and rescue service vehicle access level should have one or more firefighting shafts, each containing a firefighting lift.
  • GuidanceADB Vol 1, para 15.9 and Table B1 item 12Firefighting shaft REI 120 from the side remote from the shaft, REI 60 from the shaft side, and REI 60 between the stair, lift shaft and lobby.
  • GuidanceADB Vol 1, para 15.8The stair and lobby of the firefighting shaft should have a means of venting smoke and heat (clause 27.1 of BS 9999).
  • StandardBS 5266-1 (opens in a new tab)Emergency lighting to the stair.Why it applies here: The stair is an escape route, and ADB Volume 1 para 3.48 asks for escape lighting to conform to BS 5266-1, so the stair stays lit if the mains power fails. ADB names the 2016 edition; this page uses the current edition, BS 5266-1:2025.
  • GuidanceADB Vol 1, paras 3.97 to 3.99The door of any doorway or exit should be hung to open in the direction of escape whenever reasonably practicable. It should always be hung to open in the direction of escape if more than 60 people might be expected to use it during a fire. All doors on escape routes should be hung to meet both of the following conditions. a. Open by a minimum of 90 degrees. b. Open with a swing that complies with both of the following. i. Is clear of any change of floor level, other than a threshold or single step on the line of the doorway. ii. Does not reduce the effective width of any escape route across a landing. Any door opening towards a corridor or a stair should be recessed to prevent its swing encroaching on the effective width.Why it applies here: Stair A’s door opens into the stair, the way people escape. Its 0.97 m leaf turns inside a 1.0 m recess cut out of the lobby and stops short of the landing, which keeps its full 1.7 m depth.
  • GuidanceADB Vol 1, para 3.63If it is also a firefighting stair or a common stair in a building with a storey 18 m or more in height, a stair should be at least 1100 mm wide: the clear width between the walls or balustrades. Handrails and strings intruding into that width by up to 100 mm on each side may be ignored.Why it applies here: Each flight is 1.65 m from the stair’s wall to its well, about 1.6 m clear between the wall lining and the balustrade: well over 1,100 mm.
  • GuidanceApproved Document K, para 1.20At the top and bottom of every flight, provide landings the width and length at least as great as the smallest width of the flight.Why it applies here: Stair A’s flights are 1.65 m wide. Its floor landing is 1.7 m deep and its half landing 1.92 m.
  • StandardBS 9991, clause 46.3 (opens in a new tab)How firefighting shafts are built: the stair, the lobby and the firefighting lift.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the firefighting shaft this part belongs to.
Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 120 / REI 60
Over 30 mREI 120 / REI 60
Over 50 mREI 120 / REI 60
Show in the 3D model

Firefighting lobby

A fire-resisting space between the corridor and the firefighting stair and lift.

  • Two sets of doors keep smoke out of the stair.
  • It gives crews a protected place to gather before they go onto the fire floor.

From 30 m this model does not show the smoke control BS 9999:2017 asks for in the firefighting lobby.

  • BS 9999 accepts an outside-wall lobby vent only where the top floor is under 30 m.
  • Above that the lobby needs an automatic vent into a smoke shaft of at least 3 m², a pressure differential system, or a mechanical system shown to do as well.
  • The corridor smoke shafts outside the lobby door do not vent the lobby.

REI 120 / REI 60Wall to the corridor is the shaft enclosure (120 from the flats side, 60 from the shaft side). REI 60 to the stair and lift shaft. Door from the corridor E 60 Sa, as Diagram 15.1 shows for a firefighting shaft.

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.8Firefighting stairs and lifts are approached from a firefighting lobby, or a protected corridor or lobby. Firefighting lift landing doors no more than 7.5 m from the door to the firefighting stair. Only services for the shaft itself should pass through it.
  • GuidanceADB Vol 1, Table B1 item 12bREI 60 between the firefighting stair, firefighting lift shaft and firefighting lobby.
  • GuidanceADB Vol 1, Diagram 15.1The firefighting shaft is REI 120 from the accommodation side and REI 60 from inside the shaft, with E 60 Sa fire doors in that enclosure. Between the stair, lift shaft and lobby it is REI 60 from both sides, with E 30 Sa fire doors. Table C1 gives E 30 Sa as the general minimum for a door into a protected stair in flats; for the enclosure of a firefighting shaft this diagram shows E 60 Sa.
  • StandardBS 9999, clause 27.1 (opens in a new tab)Venting of smoke and heat from the firefighting stair and lobby, as referred to by ADB para 15.8.Why it applies here: ADB para 15.8 points to this clause for venting the stair and the lobby of a firefighting shaft. The stair has its vent at its head and the lobby a vent in its outside wall. From 30 m this model does not show the smoke control BS 9999:2017 asks for in the firefighting lobby. BS 9999 accepts an outside-wall lobby vent only where the top floor is under 30 m; above that the lobby needs an automatic vent into a smoke shaft of at least 3 m², a pressure differential system, or a mechanical system shown to do as well. The corridor smoke shafts outside the lobby door do not vent the lobby.
  • GuidanceADB Vol 1, para 15.8 and Diagram 15.1 note 2Both the stair and lobby of the firefighting shaft should be provided with a means of venting smoke and heat (see clause 27.1 of BS 9999). Diagram 15.1 note 2: smoke control should be provided in accordance with BS 9999 or, where the firefighting shaft only serves flats, the provisions for smoke control given in paragraph 3.53 may be followed instead.Why it applies here: For a shaft that serves only flats ADB lets smoke control follow para 3.53 (natural venting to paras 3.54 to 3.57: a vent directly in front of each storey exit). The door from the corridor into this lobby is one, so that vent is the corridor’s west shaft just outside it. This model reads the shaft as serving plant too from 18 m (see the assumptions), so it also follows BS 9999.
  • StandardBS 9999, clauses 27.1.3 to 27.1.4 and Table 21 (opens in a new tab)A naturally vented firefighting shaft has openable vents in both the lobby and the stair. A lobby vent on an external wall needs at least 1.5 m² of free area (1.0 m² aerodynamic), may be opened by hand or automatically, and is accepted only where the top floor is under 30 m. A vent from the lobby into a common smoke shaft of at least 3 m², opened automatically, is accepted at any height; so are a pressure differential system and a mechanical system shown to do as well.Why it applies here: ADB para 15.8 points to BS 9999 for venting the firefighting lobby, and this model reads the shaft as serving plant from 18 m, so it follows BS 9999. The lobby’s outside-wall vent is the kind BS 9999 accepts where the top floor is under 30 m; from 30 m BS 9999 asks for more, which this model does not show.
  • StandardBS 9991, clause 46.3 (opens in a new tab)How firefighting shafts are built: the stair, the lobby and the firefighting lift.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the firefighting shaft this part belongs to.

INFIRISK guides

No INFIRISK guide on this yet.

Only in this building at: Over 18 m, Over 30 m, Over 50 m.

Show in the 3D model

Firefighting lift

In normal use the firefighting lift is an ordinary passenger lift.

  • In a fire, the fire service takes control of it with a switch at access level.
  • It has a protected power supply so crews can carry kit up quickly.

The resident waiting for the lift uses a wheelchair.

  • Since 6 April 2026 the responsible person for a block of flats at least 18 m high has had to try to identify residents who may need help to get out in a fire because of an impairment or condition, and offer each one a person-centred fire risk assessment.

REI 60Lift shaft walls inside the firefighting shaft.

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.2Each firefighting shaft contains a firefighting lift.
  • GuidanceADB Vol 1, para 15.11The installation covers the car, well, machinery space, control system and communications system. Lift shaft built to Section 6 of BS 9999. Installations to BS EN 81-72 and BS EN 81-20.
  • StandardBS EN 81-72 (opens in a new tab)Firefighting lifts, and the construction of passenger lifts.Why it applies here: ADB para 15.11 asks for firefighting lift installations to conform to BS EN 81-72, so this lift is built and controlled to it. ADB names the 2015 edition; this page uses the current edition, BS EN 81-72:2020.
  • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 3 to 6In a building with two or more homes that is at least 18 m high, or has at least seven storeys, or is more than 11 m high with a simultaneous evacuation strategy, the responsible person must use reasonable endeavours to identify residents whose ability to evacuate without help is compromised by a cognitive or physical impairment or condition, and offer each of them a person-centred fire risk assessment. In force from 6 April 2026.
  • StandardBS 9991, clause 46.3 (opens in a new tab)How firefighting shafts are built: the stair, the lobby and the firefighting lift.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the firefighting shaft this part belongs to.

INFIRISK guides

No INFIRISK guide on this yet.

Only in this building at: Over 18 m, Over 30 m, Over 50 m.

Show in the 3D model

Dry riser outlet

A dry riser is an empty pipe that runs up the building inside the firefighting stair.

  • Firefighters pump water into the inlet at street level and take it off at the outlet on the floor they need, instead of running hose up the stairs.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.10All firefighting shafts should have fire mains with outlet connections and valves at every storey.
  • GuidanceADB Vol 1, para 14.4The outlets from fire mains should be located within the protected stairway enclosure.
  • GuidanceADB Vol 1, para 14.6A storey more than 50 m above fire service vehicle access level needs wet fire mains. Below that, wet or dry are both suitable. This block is 34.5 m, so dry is acceptable.
  • GuidanceADB Vol 1, para 13.5Pumping appliance access to within 18 m of each inlet, and the inlet visible from where the appliance parks.
  • StandardBS 9990 (opens in a new tab)Design and construction of fire mains, inlets and landing valves.Why it applies here: The tower has a firefighting shaft, so it needs a fire main, and BS 9990 sets how the main, its inlet and its outlets are designed and tested.
  • StandardBS 9990, clause 4.1.5 (opens in a new tab)A landing valve on every floor, including the ground floor. In blocks of flats it sits on the full landing inside the stair enclosure, with its lowest point about 750 mm above the floor.Why it applies here: This is the valve firefighters connect their hose to on each floor, and the clause sets where it goes and how high.
  • StandardBS 9991, clause 47.1 and Figure 47 (opens in a new tab)Fire mains, and where their outlets sit in a firefighting shaft.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the fire main this part belongs to.

INFIRISK guides

No INFIRISK guide on this yet.

Only in this building at: Over 11 m, Over 18 m, Over 30 m.

Show in the 3D model

Second staircase (Stair B)

  • Means of escape
Show in the 3D model

A second, separate escape stair at the other end of the corridor.

  • If smoke fills one end, residents and firefighters still have a way down.
  • The outside wall of a protected stair like this does not normally need to be fire resisting, except in the cases the guidance sets out.
  • At ground level the stair has no door into the shops: flats need their own escape routes, kept separate from other uses, so the stair leads straight outside through its own exit.

On each floor of flats Stair B’s door opens into the stair, the way people escape.

  • It stands in a recess 1 m deep, so as it swings it narrows neither the corridor nor the landing, as the guidance asks for a door that opens towards a stair.
  • The landing beyond the recess, and the half landing, are each at least as deep as the flights are wide, as Approved Document K asks.
In existing buildings

Many existing blocks have a single stair. The second stair applies to new buildings with a top storey of 18 m or more.

REI 120Protected shaft enclosure, from Table B2 for this height. Stair door E 30 Sa.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.30Flats should be served by more than one common stair if either of the following applies. a. The flat is on a storey that does not meet the criteria for a single escape route or a small single stair building (see paragraphs 3.27 and 3.32). b. The building has a top storey of 18m or more in height (see Diagram D6 in Appendix D).Why it applies here: Here both apply: the corridor is too long for escape in one direction only, and the top storey is over 18 m.
  • GuidanceADB Vol 1, 2026 amendment booklet, introductionThe edition before the 2026 amendments continues to apply where a building notice or an initial notice has been given to, or a building control approval application with full plans made to, the relevant authority before 30 September 2026, and the building work has started and is sufficiently progressed before that day, or is started and is sufficiently progressed within the period of 18 months beginning on that day.Why it applies here: This model is a new building designed to the edition with the 2026 amendments, so 3.30 b. applies to it.
  • GuidanceADB Vol 1, Table 3.1Maximum travel distance from a flat entrance door to a storey exit or stair lobby: 7.5 m where escape is in one direction only, 30 m where it is possible in more than one direction.
  • GuidanceADB Vol 1, Table B1 item 8c and Table B2Protected shaft enclosure to the fire resistance in Table B2: 120 minutes for a sprinklered block of flats with a top storey over 30 m.
  • GuidanceADB Vol 1, Table C1 item 2bDoors into a protected stair in a block of flats: E 30 Sa.
  • GuidanceADB Vol 1, para 7.29The external wall of a protected shaft does not normally need fire resistance; paragraph 3.66 and paragraphs 15.8 to 15.11 say where it does.
  • GuidanceADB Vol 1, para 3.5In mixed use buildings, separate means of escape should be provided from the parts used as flats.
  • GuidanceADB Vol 1, paras 3.97 to 3.99The door of any doorway or exit should be hung to open in the direction of escape whenever reasonably practicable. It should always be hung to open in the direction of escape if more than 60 people might be expected to use it during a fire. All doors on escape routes should be hung to meet both of the following conditions. a. Open by a minimum of 90 degrees. b. Open with a swing that complies with both of the following. i. Is clear of any change of floor level, other than a threshold or single step on the line of the doorway. ii. Does not reduce the effective width of any escape route across a landing. Any door opening towards a corridor or a stair should be recessed to prevent its swing encroaching on the effective width.Why it applies here: Stair B’s door opens into the stair, the way people escape. Its 0.97 m leaf turns inside a 1.0 m recess and stops short of the landing, which keeps its full 1.67 m depth; the corridor keeps its full 1.5 m.
  • GuidanceApproved Document K, para 1.20At the top and bottom of every flight, provide landings the width and length at least as great as the smallest width of the flight.Why it applies here: Stair B’s flights are 1.65 m wide. Its floor landing is 1.67 m deep beyond the door’s recess, and its half landing 1.65 m.
  • StandardBS 9991, clause 11.1 (opens in a new tab)Basement stairs in a building with more than one stair: at least one stair from the upper storeys ends at ground level, and any other stair that carries on down is separated from each basement level by a protected lobby.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and Stair B is the stair that ends at ground level, so Stair A may carry on down to the basement.
  • StandardBS 9991, clause 12 (opens in a new tab)Stairs within mixed-use residential developments.Why it applies here: The tower has shops on the ground floor, so its stairs are in a mixed-use building and must stay separate from the shops.
  • StandardBS 9991, clause 15.1 (opens in a new tab)Discharge and final exits from common stairs.Why it applies here: Stair B ends at a final exit straight to the street, which is how a common stair should discharge.
Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 90
Over 30 mREI 120
Over 50 mREI 120
Show in the 3D model

Common corridor

  • Means of escape
  • Smoke control
Show in the 3D model

The common corridor is the route from every flat door to the stairs.

  • It is kept clear, lit and ventilated so it stays usable in a fire.
  • Its length is limited so nobody has far to go through smoke.
  • There is no fire alarm here: the smoke detectors in the corridor only open the smoke vents, and each flat has its own alarms.

There are no manual call points in the corridors or stairs.

  • Each flat has its own alarms and is a fire-resisting compartment, so a communal fire alarm is not normally needed, and the code of practice for alarms in homes advises against one in a purpose-built block because it can put residents at risk.
  • The corridor smoke detectors only open the smoke vents.
  • Where the top storey is over 18 m, an evacuation alert system lets the fire service sound an alert in the flats if they decide residents should leave.

A pair of fire doors divides the corridor, about 9 m from its west end and 5.75 m from its east end.

  • Approved Document B asks for a self-closing E 30 Sa fire doorset across any common corridor that joins two storey exits, placed so that smoke on one side cannot reach both stairs.
  • Here the door into the lobby in front of Stair A is on the west side and Stair B’s door on the east, with three flats on each side.
  • BS 9991 would put such a door at about the halfway point of a corridor over 15 m; this one is 14.75 m, and the door also means the two stairs do not share one lobby, which BS 9991 would otherwise ask to be pressurised.
  • The leaves swing both ways, so whichever stair people head for they push the door the way they are going, and each has a vision panel, as the guidance asks for doors that divide corridors or swing both ways.
  • In this model they close on floor springs and are not held open.

E 30 SaCross-corridor fire doorset with a self-closing device and fire-resisting screen (ADB para 3.39).

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, Table 3.1Maximum travel distance from a flat entrance door to a storey exit or stair lobby: 7.5 m where escape is in one direction only, 30 m where it is possible in more than one direction.
  • GuidanceADB Vol 1, para 3.54The corridor or lobby in front of each storey exit should have a smoke vent, as high as practicable, with its top edge at least as high as the top of the door to the stair.
  • GuidanceADB Vol 1, para 1.10Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed.
  • GuidanceADB Vol 1, para 15.17In blocks of flats with a top storey over 18 m above ground level, an evacuation alert system should be provided in accordance with BS 8629.
  • GuidanceADB Vol 1, para 3.39 and Diagram 3.8Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Doors should be positioned such that smoke does not affect access to more than one stair.
  • GuidanceADB Vol 1, para 3.100Doors should contain vision panels where doors on escape routes divide corridors, and where doors are hung to swing both ways.
  • GuidanceADB Vol 1, paras 3.97 to 3.99The door of any doorway or exit should be hung to open in the direction of escape whenever reasonably practicable. It should always be hung to open in the direction of escape if more than 60 people might be expected to use it during a fire. All doors on escape routes should be hung to meet both of the following conditions. a. Open by a minimum of 90 degrees. b. Open with a swing that complies with both of the following. i. Is clear of any change of floor level, other than a threshold or single step on the line of the doorway. ii. Does not reduce the effective width of any escape route across a landing. Any door opening towards a corridor or a stair should be recessed to prevent its swing encroaching on the effective width.Why it applies here: Escape along this corridor runs both ways, to either stair, so its cross-corridor doors swing both ways: whichever way people go, the leaf opens the way they escape.
  • StandardBS 9991, clause 7.2.1 (opens in a new tab)A corridor of more than 15 m joining a flat’s entrance to two exits should be divided at about its halfway point by a self-closing E 30 Sa (FD 30S) fire door. A corridor of 15 m or less that would form a common lobby to both stairs instead needs the stairs, the lobby and the lifts to be pressurised.Why it applies here: This corridor is 14.75 m between its end walls, so BS 9991 would not ask for the door on length; ADB para 3.39 does, for any common corridor joining two storey exits. The door divides the corridor about 9 m and 5.75 m from its ends, not at its halfway point, so that smoke on one side does not reach both stairs (ADB para 3.39, Diagram 3.8). With the door in place the two stairs do not share one lobby, which BS 9991 would otherwise ask to be pressurised.
  • StandardBS 9991, clause 7.2 and Figure 7 (opens in a new tab)Escape routes from flats along a common corridor or lobby, with layouts for buildings served by more than one stair.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and every flat on this floor escapes along this corridor to one of two stairs.
  • StandardBS 9991, clause 13.2 and Table 1 (opens in a new tab)Ventilation of protected lobbies and protected corridors.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this corridor is ventilated through the smoke shaft.
  • StandardBS 5839-6, Introduction (opens in a new tab)Communal fire alarm systems should not normally be installed in purpose-built blocks of flats: they are normally undesirable and can even put residents at risk.Why it applies here: This is a purpose-built block of flats, so its corridors have no general fire alarm; each flat has its own.
Show in the 3D model

Smoke shafts and vents

Two vertical smoke shafts draw smoke out of the corridor, one in each half of it, each beside the door to a stair.

  • At the east end it is Stair B’s door.
  • At the west end it is the door into the firefighting lobby, the way to Stair A.
  • Approved Document B asks for a smoke vent in the corridor directly in front of each of these doors.
  • At this height each shaft is a mechanical system.
  • Each half of the corridor has its own detector: when one finds smoke, the vent in that half opens and extract fans at the head of its shaft draw the smoke out, so it leaves the corridor before it reaches the stairs.
  • In this model the vent at the head of the stair that half of the corridor leads to opens with them and lets in replacement air; how much air, and by which way, is for the designer’s smoke flow model.
  • The other half’s vent stays shut, and so does every vent on the other floors.
  • Treating each half of the divided corridor as a corridor of its own, with its own vent, is this model’s reading of BS 9991 clause 20.2.2.1, which is written for buildings with a storey 11 m to under 18 m above ground; above that this model applies it by analogy.
  • The firefighting lobby also has a vent in its outside wall, which firefighters open by hand.
  • The louvres are 2.0 m wide and 1.45 m high, 2.9 m² on their face.
  • This model takes their free area as 55 per cent of that, 1.6 m², over the 1.5 m² the guidance asks for; a real louvre’s free area comes from its maker’s tests.
  • See the assumptions for what BS 9999 asks of the lobby at this height.
  • The detectors that open them sound no alarm: they are a Category L5 system to BS 5839-1, linked to the vents as BS 7273-6 sets out, and they run the smoke control and nothing else.
  • ADB Volume 1 para 3.55 would accept natural smoke shafts at any height, and below 30 m this model has them.
  • Here it follows BS 9991, which asks for a mechanical system where a storey is 30 m or more above ground: wind and the pressures set up by the height of the building upset a natural shaft more than a fan-driven one, and fans keep drawing whatever the weather.
  • BS 9991 also asks for a duty and a standby fan, a second power supply, and a computer model of the smoke flow to show the design keeps the stair clear.

REI 120 · class A1Protected shaft enclosure built from class A1 material. Each vent from the corridor into the shaft is a smoke control damper, or under ADB a smoke-rated (Sa) fire doorset, with the same fire resistance as the shaft wall: 120 minutes at this height.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.55(b)Smoke shaft at least 1.5 m² in cross-section (0.85 m minimum in any direction), closed at the base, open at roof level at least 0.5 m above structures within 2 m, extending at least 2.5 m above the highest ceiling served. Vents into the shaft and at its head at least 1 m² free area. Shaft of class A1 material.Why it applies here: ADB would accept natural shafts of this size at any height. From 30 m this model follows BS 9991 and fits extract fans at their heads, keeping each shaft at least this size.
  • GuidanceADB Vol 1, para 3.55(b)(iii) and Table C1 item 2eAll vents should either be a smoke leakage (Sa) rated fire doorset (see Appendix C, Table C1, item 2.e for minimum fire resistance) or fitted with a smoke control damper achieving the same period of fire resistance and designed to operate as described below. Table C1 item 2e: same as for the wall in which it is fitted.
  • StandardBS EN 12101, Part 8 (opens in a new tab)Smoke control dampers: the vents that open from the corridor into the shaft.Why it applies here: BS 9991 asks for the vents into a smoke shaft to be smoke control dampers to this part, as fire resisting as the shaft wall; ADB para 3.55(b)(iii) would also accept a smoke-rated fire doorset.
  • StandardBS EN 12101, Part 10 (opens in a new tab)Power supplies for smoke and heat control systems.Why it applies here: The vents open on electric actuators, and BS 9991 asks for a secondary supply to BS EN 12101-10 wherever a smoke control mechanism is powered by electricity.
  • GuidanceADB Vol 1, para 3.54 and Appendix A (storey exit)Except in buildings that comply with Diagram 3.9, the corridor or lobby directly in front of each storey exit should have a smoke vent. The location of the vent should be as high as practicable, and positioned so the top edge is at least as high as the top of the door to the stair. Appendix A: a storey exit is a final exit, or a doorway that gives direct access into a protected stairway, evacuation lift lobby within an evacuation shaft, firefighting lobby or external escape route.Why it applies here: The doors into the firefighting lobby and into Stair B are this floor’s storey exits; each has a corridor vent directly in front of it.
  • GuidanceADB Vol 1, para 3.55(a)Smoke vents should be located on an external wall with minimum free area of 1.5 m2.Why it applies here: The firefighting lobby’s vent is in an outside wall. The louvres are 2.0 m wide and 1.45 m high, 2.9 m² on their face. This model takes their free area as 55 per cent of that, 1.6 m², over the 1.5 m² the guidance asks for; a real louvre’s free area comes from its maker’s tests.
  • GuidanceADB Vol 1, para 3.57In buildings with more than one stair, smoke vents may be activated manually. The control system should open the vent at the head of the stair before, or at the same time as, the vent on the storey where the fire is located. Smoke detection is not required for ventilation purposes in this instance.Why it applies here: The block has two stairs, so the lobby’s vent is opened by hand and the vent at the head of the stair opens before it or with it.
  • StandardBS 9991, clauses 20.2.4 and 20.2.2.3 (opens in a new tab)Where a storey is 30 m or more above ground, the stairs and lobbies are protected by a mechanical system: a pressure differential system, or a mechanical smoke ventilation system in the protected corridor with an automatic vent, at least 0.7 m² in aerodynamic free area, as high as practicable at the top of the stair.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this block has a storey 30 m or more above ground, so its corridor smoke shafts are mechanical.
  • StandardBS 9991, clauses 20.1 and 20.2.2.1, and Table 3 (opens in a new tab)Where vents discharge into a smoke shaft, detection in the common corridor or lobby opens together the vents on the fire floor, the top of the shaft and the vent on the stairway, and the vents on every other storey stay shut. Only the vent from the lobby or corridor where smoke was found opens, and no other lobby vent opens with it. A vent at the top of a stair works on detection in a lobby or corridor next to that stair. Table 3 lists one vent at the head of the stair.Why it applies here: This model reads each half of the corridor, either side of the cross-corridor door, as a corridor of its own, with its own detector, vent and shaft: that reading is the model’s own. Clause 20.2.2.1 is written under the heading for 11 m to under 18 m; above that this model applies it by analogy.
  • StandardBS 9991, Annex F, F.3.2.1 (opens in a new tab)A mechanical smoke ventilation system has a duty fan and a standby fan that starts on its own if the duty fan fails, a secondary power supply to the fans and every actuator and control, and replacement air allowed for in its design. It is designed to keep smoke out of the stair, shown by a calculation or a computer model of the smoke flow.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and these are the fans, power and air of this block’s mechanical smoke shafts.
  • StandardBS 9991, clause 16.1 (opens in a new tab)Where detection outside the flats is needed to start smoke control, it is at least a Category L5 system to BS 5839-1. Detection in other common areas, such as lounges, depends on their extent and use, the fire risk and how the building is managed.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the corridor detectors here start the smoke control, and nothing else.
  • StandardBS 9991, clause 20.1 (opens in a new tab)Unless the building is to be evacuated all at once, the smoke detectors in the common areas have no sounders: they are there to run the smoke control, not to raise an alarm.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and residents here stay put unless they are told to leave, so the corridor detectors sound nothing.
  • StandardBS 5839-6, Introduction (opens in a new tab)Detectors in blocks of flats that operate smoke control are outside BS 5839-6 (BS 7273-6 covers them). They are not there to warn residents or to sound an alarm.Why it applies here: The detectors in this corridor open the smoke vents, so they are a smoke control link, not a fire alarm for the residents.
  • StandardBS 7273-6 (opens in a new tab)How a fire detection and fire alarm system operates other fire safety equipment, smoke control among it.Why it applies here: The corridor detectors open the smoke control, and BS 5839-6 sends that link between detector and smoke control to BS 7273-6.
Fire resistance by height of the top storey
Over 11 mREI 60 · class A1
Over 18 mREI 90 · class A1
Over 30 mREI 120 · class A1
Over 50 mREI 120 · class A1
Show in the 3D model

Flat entrance doors

  • Compartmentation
  • Means of escape
Show in the 3D model

Each flat door is a fire door that shuts itself.

  • It keeps a fire inside the flat and keeps smoke out of the corridor everyone else uses.
  • A door that does not close fully does neither.
In existing buildings

Older flat doors are often not fire doors, or have lost their closers and seals.

E 30 SaFire doorset with smoke leakage rating and a self-closing device (FD 30 S under BS 476-22).

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, Table C1 item 2aDoor in a compartment wall separating a flat from a space in common use: E 30 Sa (FD 30 S).
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4), (6), (7) and (8)In a building with two or more flats and a top storey above 11 m, the responsible person must use best endeavours to check flat entrance doors at least every 12 months, and must check fire doors in the communal areas at least every 3 months. The checks include making sure the self-closing devices work.
  • StandardBS 9991, clause 30.1 and Table 15 (opens in a new tab)Fire doors, and the fire resistance each one needs.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and each flat entrance door is a fire door.
Show in the 3D model

Compartment walls

  • Compartmentation
Show in the 3D model

Every flat is its own fire compartment.

  • The walls between flats, and between each flat and the corridor, resist fire for a set time.
  • So a fire stays where it started long enough for the fire service to deal with it.

REI 60Walls separating a flat from any other part of the building: REI 60 or the Table B2 period, whichever is less.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1Any wall separating a flat from another part of the building is a compartment wall, and any floor (unless within a flat) is a compartment floor.
  • GuidanceADB Vol 1, Table B1 item 6aCompartment wall separating a flat from any other part of the building: REI 60, or the Table B2 period if that is less.
  • StandardBS 9991, clause 23.1 (opens in a new tab)Compartmentation in houses, flats and maisonettes.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and each flat is its own compartment.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Compartment floor

  • Compartmentation
Show in the 3D model

Every floor between flats is a compartment floor.

  • It stops fire spreading up or down the building, and it carries the floor above while it does.
  • The floor over the shops separates two different uses, so it is a compartment floor too.

REI 120Top storey is more than 30 m above ground in a sprinklered block of flats, so Table B2 gives 120 minutes. The floor over the shops is the greater of REI 60 and Table B2: also 120.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1(a)Any floor, unless it is within a flat, should be a compartment floor.
  • GuidanceADB Vol 1, Table B1 item 3c and Table B2Compartment floors: REI from Table B2. Block of flats with sprinklers, top floor more than 30 m: 120 minutes.
  • GuidanceADB Vol 1, Table B1 item 3aFloor between a shop and a flat above: REI 60 or Table B2, whichever is greater.
  • GuidanceADB Vol 1, para 7.13Where a compartment floor meets an external wall with no fire resistance, the wall should be restrained at floor level.
  • StandardBS 9991, clause 22.1 and Table 5 (opens in a new tab)Minimum fire resistance for elements of structure.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the floor is an element of structure whose fire resistance follows the height of the building.

INFIRISK guides

No INFIRISK guide on this yet.

Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 90
Over 30 mREI 120
Over 50 mREI 120
Show in the 3D model

Service riser and fire stopping

  • Compartmentation
Show in the 3D model

Pipes and cables run up the building through this service riser.

  • Every hole they make in a compartment floor or wall has to be sealed with a tested fire-stopping product.
  • Otherwise fire and smoke can travel from floor to floor.

Depends on designEither enclosed as a protected shaft (REI 120 walls, door half that period but at least 30) or fire-stopped at every floor. Shown here fire-stopped at the floor.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.22Any stair or other shaft passing directly from one compartment to another should be enclosed in a protected shaft.
  • GuidanceADB Vol 1, paras 9.2 to 9.4Pipes passing through a fire-separating element, unless in a protected shaft, need a proprietary tested seal or one of the other permitted methods.
  • GuidanceADB Vol 1, paras 9.24 to 9.27Fire-stopping materials and proprietary tested systems.
  • StandardBS 9991, clause 27.2 (opens in a new tab)Service shafts.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the riser is a service shaft through every floor.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Floor and flat signs

  • Means of escape
  • Firefighting
Show in the 3D model

Floor and flat signs tell firefighters which floor they are on and which flats it serves.

  • They are on every stair landing and in the lobby the firefighting lift opens into.
  • They have to be readable in low light or by torch.
In existing buildings

Many existing blocks were built without these signs and have had them added since.

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.13Blocks of flats with a top storey more than 11 m above ground: floor identification signs and flat indicator signs.
  • GuidanceADB Vol 1, para 15.14On every landing of a protected stairway and every lobby a firefighting lift opens into. Sans serif text at least 50 mm high, floor numeral at least 75 mm, mounted 1.7 m to 2 m above the floor.
  • GuidanceADB Vol 1, paras 15.15 and 15.16Worded “Floor X”, with a flat indicator sign immediately below worded “Flats X–Y”, with arrows when flats lie in more than one direction.
  • StandardBS 9991, clause 48.2 (opens in a new tab)Wayfinding signs for the fire and rescue service.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and these are the fire service wayfinding signs.
Show in the 3D model

Sprinklers in the flats, Category 4

Sprinkler heads in each flat open individually when they get hot, controlling a fire in the room where it starts.

  • Only the heads near the fire go off.
  • In this model the water comes up a sprinkler main in the service riser; a valve set with a flow switch on each floor feeds the flats, and the pipe is fire-stopped where it passes through the flat's compartment wall and through the screen over the cross-corridor doors.
  • The shops on the ground floor are sprinklered too, because the system runs throughout the building: the note to the guidance leaves out only fire-sterile common areas such as the stairs and corridors.
  • Shop sprinklers are normally designed to BS EN 12845 rather than BS 9251.
In existing buildings

Many existing blocks have no sprinklers.

  • Current guidance (ADB para 7.4) says new blocks with a top storey more than 11 m above ground should have them throughout.

Guidance is not law, but following it tends to show that the building regulations are met.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: Throughout the building takes in the flats and the shops alike: the note excepts only fire-sterile common areas.
  • StandardBS 9251 (opens in a new tab)Sprinkler systems for residential occupancies.Why it applies here: ADB Appendix E says sprinkler systems in residential buildings are designed and installed to BS 9251, so the system in each flat follows it.
  • GuidanceADB Vol 1, Appendix E, para E3Where sprinklers are needed they go throughout the building or separated part. Systems in residential buildings follow BS 9251. Systems in non-residential buildings, or in residential buildings outside the scope of BS 9251, follow BS EN 12845, with the extra measures for reliability in its Annex F.
  • StandardBS 9251, clause 4.1, Note 3 (opens in a new tab)Where a building mixes flats with shops or other non-residential uses, the flats are normally protected under BS 9251 and the non-residential parts under BS EN 12845.Why it applies here: This block has shops under the flats, which is the mixed use case the note covers.
  • StandardBS 9991, clause 17 and Table 2 (opens in a new tab)Sprinkler systems. For a block of flats over 18 m: a BS 9251 Category 4 system, or a BS EN 12845 system to Ordinary Hazard 1 as the alternative.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and its Table 2 sets which category of sprinkler system a block of this height needs.
  • GuidanceADB Vol 1, paras 9.1 and 9.2Every joint, imperfect fit and opening for services through a fire-separating element should be sealed with fire-stopping. Pipes passing through one, unless in a protected shaft, should meet one of the alternatives the guidance sets out: a proprietary tested seal, a pipe of restricted diameter fire-stopped round it, or sleeving.Why it applies here: The screen over the cross-corridor doors encloses a protected escape route, so it is a fire-separating element (Appendix A), and the branch to flat 6.02 passes through it.
Show in the 3D model

Smoke alarms in the flats

  • Detection and alarm
Show in the 3D model

Each flat has its own mains-powered alarms with a backup supply.

  • Smoke alarms in the hall and the main living room, and a heat alarm in the kitchen.
  • They warn the people in that flat only, in time to get out and call the fire service.
  • There is no alarm that sounds across the block: with good compartmentation a fire in one flat does not threaten the others.

The evacuation alert system is something else again, a tool only the fire service uses.

In existing buildings

Older flats may have battery-only alarms, or none.

  • In England the landlord of a rented home must make sure a smoke alarm is fitted on each storey that has a room used as living accommodation, and check that it works on the day each new tenancy begins.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 1.1All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3, in accordance with BS 5839-6.
  • GuidanceADB Vol 1, para 1.2Smoke alarms should be mains operated and conform to BS EN 14604.
  • GuidanceADB Vol 1, para 1.10Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed.
  • LawSmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)The immediate landlord of a home in England let on a tenancy the regulations cover must ensure that, while it is occupied under that tenancy, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker; that each alarm is checked and in proper working order on the day a new tenancy begins; and that, when a tenant reports an alarm, it is checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.
  • StandardBS 5839-6, clause 9.2 a) and Table 1 (opens in a new tab)Where the occupants are not known, as in a new flat, Table 1 applies: Grade D1, Category LD2 for a rented flat, which this model uses; an owner-occupied flat may be Grade D2, Category LD2. Category LD2 adds detectors in the kitchen (heat only) and the principal habitable room (heat or smoke; this model uses smoke).Why it applies here: ADB para 1.1 and BS 9991 clause 16.1 both send the alarms in every flat to BS 5839-6, and these flats are new, so its Table 1 sets their grade and category.
  • StandardBS 9991, clause 16.1 (opens in a new tab)Every flat has a fire detection and alarm system to BS 5839-6, to warn the people in it of a fire in their own flat in time to get out and call the fire service. It is a different system from the evacuation alert system in clause 48.3.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and these alarms are the fire detection and alarm system in each flat.
Show in the 3D model

Evacuation alert sounders

  • Detection and alarm
Show in the 3D model

A sounder in every flat, separate from the smoke alarms.

  • Smoke does not set it off.
  • The fire service sounds it floor by floor if they decide residents should leave.
  • To clear the whole building they turn on every floor’s switch, because there is deliberately no single switch for the whole building.
  • It lets firefighters change the plan from staying put to getting out.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.17In blocks of flats with a top storey over 18 m above ground level, an evacuation alert system should be provided in accordance with BS 8629.
  • StandardBS 8629 (opens in a new tab)Design, installation, commissioning and maintenance of evacuation alert systems for the fire and rescue service in buildings containing flats.Why it applies here: ADB para 15.17 asks for an evacuation alert system in this block because its top storey is over 18 m, and names BS 8629 as the standard it follows. ADB names the 2019 edition; this page uses the current edition, BS 8629:2019+A1:2023.
  • StandardBS 9991, clause 48.3 (opens in a new tab)Evacuation alert systems for use by the fire and rescue service.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the evacuation alert system this part belongs to.

Only in this building at: Over 18 m, Over 30 m, Over 50 m.

Show in the 3D model

Emergency lighting

  • Means of escape
Show in the 3D model

Emergency escape lighting stays on when the mains power fails.

  • The lights are in the corridor, lobby and stairs.
  • They light the way out, and the doors, stairs and changes of direction on it.
  • Each fitting has its own battery or a protected supply, and it is tested regularly.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.45Except for two storey blocks of flats, all escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route.
  • GuidanceADB Vol 1, para 3.47Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
  • StandardBS 5266-1 (opens in a new tab)Emergency lighting of premises: where it goes, how much light it gives, how long it lasts and how it is tested.Why it applies here: ADB Volume 1 para 3.48 asks for escape lighting to conform to BS 5266-1, so the fittings on this escape route follow it. ADB names the 2016 edition; this page uses the current edition, BS 5266-1:2025.
  • Ongoing dutyFire Safety Order 2005, Article 17The responsible person keeps the fire safety equipment in the common parts, such as emergency lighting, maintained in efficient working order and good repair.
  • StandardBS 9991, clause 40.2 (opens in a new tab)Lighting of common escape routes in buildings containing flats or maisonettes.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the corridor and stairs are this block’s common escape routes.
Show in the 3D model

External wall build-up

The corner is cut open to show the wall in layers: a light steel frame inner wall, a sheathing board, insulation, a ventilated cavity and a brick outer leaf.

  • In a block this tall regulation 7(2) applies: every material that becomes part of the wall must be class A2-s1, d0 or A1, apart from the few items regulation 7(3) exempts, such as cavity trays used between two leaves of masonry, membranes, seals and fixings, and window frames and glass.
  • This wall is a light steel frame with a brick outer leaf, so that cavity tray exemption is not one it relies on.
  • So the wall is not built of materials that would carry fire up the outside of the building from floor to floor.
  • Along the top of the walls all round the floor, the same layers show in section, with the cavity closed by its cavity barrier where the wall meets the floor above.
In existing buildings

Many existing blocks were built with combustible cladding or insulation, and a large programme of remediation is under way in England.

  • LawBuilding Regulations 2010, Schedule 1, B4External fire spread.
  • LawBuilding Regulations 2010, Regulation 7(2)In a building with a storey at least 18 m above ground level that contains flats, every material that becomes part of an external wall or specified attachment must achieve class A2-s1, d0 or class A1, apart from the exemptions in regulation 7(3).
  • GuidanceADB Vol 1, para 10.14Regulation 7(2) applies to any building with a storey at least 18 m above ground level, measured as in Diagram D6, which contains one or more dwellings.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 5In a high-rise residential building the responsible person keeps a record of the design and materials of the external walls, the level of risk they give rise to, and any steps taken to reduce it.
  • StandardBS 9991, clause 24.1 and Table 9 (opens in a new tab)Resisting fire spread over external walls.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the block’s external wall.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Cavity barriers

  • External wall
  • Compartmentation
Show in the 3D model

A cavity is a hidden route for fire and smoke.

  • Cavity barriers close it at every compartment floor and wall, and around windows and doors, so a fire cannot run unseen inside the wall from one flat to the next.
  • This wall has a framed inner leaf, so it needs them: a masonry cavity wall built to ADB Diagram 8.2 would not.

E 30 / I 15Cavity barriers give at least 30 minutes integrity and 15 minutes insulation, each side tested separately.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 8.3Cavity barriers should be provided at the edges of cavities, including around openings, and at the junction between an external cavity wall and every compartment floor and compartment wall. This does not apply where a wall meets the conditions of Diagram 8.2.
  • GuidanceADB Vol 1, para 8.8Cavity barriers, tested from each side separately, should provide at least 30 minutes integrity (E 30) and 15 minutes insulation (I 15).
  • StandardBS 9991, clauses 25.1 and 25.2 (opens in a new tab)Where cavity barriers are needed, and how they are built and fixed.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the wall’s cavity is closed by these barriers.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Soil stack and fire collar

  • Compartmentation
Show in the 3D model

The soil stack carries waste from the kitchens and bathrooms of the flats above each other, so it passes through every compartment floor.

  • Where it does, the gap is fire-stopped, and a plastic stack wears a fire collar that swells shut in a fire.
  • The stack is boxed in with a casing, shown cut down here.

E 30 casingThe casing around the stack achieves at least E 30, and the opening where the stack passes through the floor is kept small and fire-stopped (ADB Diagram 9.1).

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 9.2Pipes passing through a fire-separating element, unless in a protected shaft, should meet one of alternatives A, B or C.
  • GuidanceADB Vol 1, para 9.3Alternative A: a proprietary, tested sealing system that will maintain the fire resistance of the wall, floor or cavity barrier.
  • GuidanceADB Vol 1, Table 9.1 and Diagram 9.1A uPVC stack pipe through a compartment floor between flats may be up to 160 mm across when enclosed as in Diagram 9.1, with fire-stopping around it. The casing should not have fire resistance less than E 30.
  • GuidanceADB Vol 1, para 9.5Alternative C: a pipe up to 160 mm across in lead, aluminium, fibre-cement or uPVC may pass through inside a sleeve of high melting point metal.
  • StandardBS 9991, clause 27.5, Table 13 and Figure 44 (opens in a new tab)Protecting openings for pipes: the largest pipes allowed through a compartment wall or floor, and the enclosure for drainage pipes.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the stack passes through every compartment floor inside an enclosure.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Wet riser outlet

Above 50 m the fire main is kept full of water.

  • Pumps and tanks in the building supply it, so firefighters have water at the outlet at once, without waiting for an engine to fill a pipe this tall.
  • The outlet is in the firefighting stair on every floor.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 14.6Buildings with a storey more than 50 m above fire service vehicle access level should be provided with wet fire mains.
  • GuidanceADB Vol 1, para 14.1Wet fire mains are kept full of water and supplied by pumps from tanks in the building. There should be a facility to replenish a wet system from a pumping appliance in an emergency.
  • GuidanceADB Vol 1, para 14.4The outlets from fire mains should be located within the protected stairway enclosure.
  • StandardBS 9990, clause 4.1.4.1 (opens in a new tab)Wet mains are designed so that the pressure at an outlet does not exceed 20 bar.Why it applies here: The main in this block is a wet main, and BS 9990 is the standard ADB para 14.5 names for designing fire mains.
  • StandardBS 9990, clause 4.1.5 (opens in a new tab)A landing valve on every floor, including the ground floor. In blocks of flats it sits on the full landing inside the stair enclosure, with its lowest point about 750 mm above the floor.Why it applies here: This is the valve firefighters connect their hose to on each floor, and the clause sets where it goes and how high.
  • StandardBS 9991, clause 47.1 and Figure 47 (opens in a new tab)Fire mains, and where their outlets sit in a firefighting shaft.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the fire main this part belongs to.

INFIRISK guides

No INFIRISK guide on this yet.

Only in this building at: Over 50 m.

Show in the 3D model

The site and the ground floor

Entrance lobby and final exits

  • Means of escape
Show in the 3D model

The way out at the bottom of the building.

  • Stair A and Stair B each lead straight to open air, and the main entrance is a final exit too.
  • Final exits are kept clear, open easily from inside without a key, and lead away from the building.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.84Every protected stairway should lead to a final exit, either directly or via a protected exit passageway.
  • GuidanceADB Vol 1, para 3.93Doors on escape routes should be readily openable, to avoid undue delay to people escaping.
  • StandardBS 9991, clause 15.1 (opens in a new tab)Where common stairs and evacuation lifts discharge, and final exits.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and both stairs and the main entrance lead to final exits here.
Show in the 3D model

Shops on the ground floor

  • Compartmentation
  • Means of escape
Show in the 3D model

The two shops are a different use from the flats, so they are separate fire compartments.

  • Each shop has its own door to the street, so nobody in a shop needs the residents’ stairs, and a fire in a shop is kept out of the flats’ way out.
  • The shops are sprinklered too, as their own part shows.
  • Volume 1 of Approved Document B is written for the flats, so for the shops, their fire alarm included, Volume 2 is consulted as well.

The Bookshop has a second exit at the back as well as its front door.

  • In this model it was needed at design stage: an empty shop unit’s fittings are not known then, so this model reads Approved Document B Volume 2 as measuring straight lines to the exits and allowing two-thirds of the usual distance, and the far corner was too far from one door.
  • Fitted out as it is now, the walk to the front door would be short enough on its own, but the next tenant may lay it out differently.
  • The Travel panel works both through.

REI 120Compartment walls and floor between the shops and the flats. The floor takes the greater of REI 60 and the Table B2 period (Table B1 item 3a). The walls separate different uses, for which Table B1 item 6b gives REI 60, or the Table B2 period if that is less. This model builds them to the floor’s 120 minutes, more than item 6b asks.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.3Parts of a building occupied mainly for different purposes should be separated from one another by compartment walls and/or compartment floors.
  • GuidanceADB Vol 1, Table B1 item 3aFloor between a shop and a flat above: REI 60 or Table B2, whichever is greater.
  • GuidanceADB Vol 1, Table B1 item 6bCompartment walls separating occupancies: REI 60, or the Table B2 period if that is less.
  • GuidanceADB Vol 1, para 0.18For the design of a mixed use building, Approved Document B Volume 2 should be consulted as well as this volume.
  • Ongoing dutyFire Safety Order 2005, Articles 3(a), 6 and 9(1), (3) and (6)The Order applies to the shops, which are not domestic premises (article 6). Each shop’s responsible person, its employer as it is a workplace (article 3(a)), must make a suitable and sufficient assessment of the fire risks, review it regularly to keep it up to date, and record it (article 9(1), (3) and (6)).
  • GuidanceADB Vol 2, Table 2.1 note 1If the internal layout of partitions, fittings and so on is not known, direct distances should be assessed instead of travel distances, the direct distance being taken as two-thirds of the actual travel distance.
  • StandardBS 9991, clause 16.2 (opens in a new tab)Fire detection and fire alarm systems in mixed-use residential buildings.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the shops make this a mixed-use building.
  • StandardBS 9999, clause 31.4 (opens in a new tab)Construction of compartment walls and compartment floors.Why it applies here: The shops are not homes, so BS 9999 covers them. The wall and floor between the shops and the flats also protect the flats, and where one use relies on the other BS 9991 clause 4.4 asks for the more onerous of BS 9991 and BS 9999.
Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 90
Over 30 mREI 120
Over 50 mREI 120
Show in the 3D model

Fire alarm in the shops

  • Detection and alarm
Show in the 3D model

Each shop has its own fire alarm.

  • A manual call point by each way out and a sounder, so staff can warn everyone in the shop at once.
  • An automatic smoke detector in any store room.
  • The shops are not homes, so Approved Document B Volume 2 is consulted for them as well as Volume 1.
  • It asks for an electrically operated fire alarm system in all but some small premises, where a shouted warning can be enough.
  • It also asks for automatic detection where a fire could start unseen in a part that is not visited regularly, such as a store room, and put the means of escape at risk.

Here the shops’ alarm is separate from the flats above, which have alarms in each flat and no fire alarm across the block.

  • From 18 m the fire service can sound an evacuation alert in the flats instead.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 0.18For the design of a mixed use building, Approved Document B Volume 2 should be consulted as well as Volume 1.
  • GuidanceADB Vol 2, para 1.2In some small buildings or premises, a simple way of raising the alarm, such as a shouted warning, can be enough.
  • GuidanceADB Vol 2, para 1.3Apart from some small buildings or premises, an electrically operated fire alarm system should be fitted.
  • GuidanceADB Vol 2, para 1.5Premises that are not residential should have automatic fire detection and alarm where a fire could start unseen in an unoccupied part, such as a store or a part not visited regularly, and put at risk the way out from the parts people are in.
  • GuidanceADB Vol 2, para 1.8An electrically operated fire detection and alarm system, where one is fitted, should comply with BS 5839-1.
  • StandardBS 5839-1 (opens in a new tab)The code of practice for designing, installing, commissioning and maintaining fire detection and fire alarm systems in buildings other than homes.Why it applies here: ADB Volume 2 para 1.8 asks for an electrically operated fire alarm system in a building that is not a home to comply with BS 5839-1. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • Ongoing dutyFire Safety Order 2005, Article 13(1)(a)Where it is needed to keep people safe, the responsible person must make sure the premises have, as far as is appropriate, fire-fighting equipment and fire detectors and alarms.
  • GuidanceADB Vol 1, para 1.10Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed.
  • GuidanceADB Vol 1, para 15.17In blocks of flats with a top storey over 18 m above ground level, an evacuation alert system should be provided in accordance with BS 8629.
Show in the 3D model

Escape lighting and exit signs in the shops

  • Means of escape
Show in the 3D model

If the power fails, emergency lights light the way out of each shop.

  • Approved Document B Volume 2 asks for escape lighting in any open-plan area of a shop larger than 60 m².
  • It asks for it on every escape route the public use as well, unless the shop has no more than three storeys, no sales floor larger than 280 m² and is not a restaurant or bar.
  • An exit sign with the running figure marks every way out that customers do not normally use: the guidance asks for one on every exit other than those in ordinary use, such as a main entrance.

Both shops here are larger than 60 m², and the exit sign is over the door at the back of each shop.

  • The cafe sells food and drink for customers to have there, so it is treated as a restaurant: the small shop exception does not apply, and every escape route its customers use is lit as well.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 2, Table 5.1In shop and commercial premises, the areas that need escape lighting include open-plan areas larger than 60 m², and every escape route the public use, outside ones included, unless the shop has no more than three storeys, no sales floor larger than 280 m² and is not a restaurant or bar.
  • GuidanceADB Vol 2, para 5.25Every escape route should have adequate artificial lighting, and the routes Table 5.1 lists should have escape lighting that works if the mains supply fails.
  • GuidanceADB Vol 2, para 5.28Every doorway or exit that leads to a means of escape should be clearly marked with an exit sign to BS ISO 3864-1 and BS 5499-4, except exits in ordinary use, such as a main entrance.
  • StandardBS 5266-1 (opens in a new tab)The code of practice for the emergency escape lighting of premises.Why it applies here: ADB Volume 2 para 5.27 asks for escape lighting to conform to BS 5266-1. ADB names the 2016 edition; this page uses the current edition, BS 5266-1:2025.
  • Ongoing dutyFire Safety Order 2005, Article 14(2)(g) and (h)Where necessary, emergency routes and exits must be indicated by signs, and those that need lighting must have emergency lighting bright enough if the normal lighting fails.
Show in the 3D model

Fire extinguishers in the shops

Each shop has a water extinguisher by its main door and a carbon dioxide one by its till, where the electrical equipment is.

  • They stand where staff can reach them easily, off the way out, each marked with a sign.
  • The Fire Safety Order applies to the shops because they are not homes: the responsible person provides fire-fighting equipment where it is needed, and names and trains the staff who would use it.

The cafe also has a water extinguisher near its back door.

  • GuidanceHome Office small premises guide, Section 5, Fire protection measures: Fire extinguishersA water-based fire extinguisher should be provided to deal with fires in combustible materials. A carbon dioxide extinguisher should also be provided to deal with fires involving electrical equipment.Why it applies here: Each shop is a ground floor unit under 280 m² (about 91 m² and 127 m²), run by one tenant who controls it, with its own doors to the street, and no point in it is more than 25 m from an exit to the open air: among the limits the guide sets for itself. The guide also expects clear sight across the floor, no hazardous processes or large amounts of flammable liquids, cooking kept away from the exits (relevant to the cafe), and nobody sleeping on the premises. It shares no escape route with the flats, so this model reads the shops as not part of a larger complex such as a shopping centre, which the guide leaves out. A shop outside those limits would follow the fuller Home Office guidance instead.
  • Ongoing dutyFire Safety Order 2005, Article 13(1)Where necessary, the premises must have appropriate fire-fighting equipment, and any equipment that is not automatic must be easy to reach, simple to use and indicated by signs.
  • Ongoing dutyFire Safety Order 2005, Article 13(3)(b)Where necessary, the responsible person must nominate competent people to carry out the fire-fighting measures, enough of them, with the training and equipment the size and hazards of the premises call for.
  • StandardBS 5306 (opens in a new tab)BS 5306-8, the code of practice for choosing and placing portable fire extinguishers.Why it applies here: The responsible person chooses and places the extinguishers, and BS 5306-8 is the code of practice for doing that.
Show in the 3D model

Sprinklers in the shops

The shops are sprinklered too.

  • The guidance asks for sprinklers throughout a block of flats with a top storey over 11 m, and its note excepts only fire-sterile common areas such as the stairs and corridors.
  • As the non-residential part of a sprinklered building, the shops normally have sprinklers designed to BS EN 12845, the standard for non-residential systems, rather than to BS 9251, the standard for homes.
  • In this model their pipes and heads run under the ceiling of each shop.
  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: Throughout the building takes in the flats and the shops alike: the note excepts only fire-sterile common areas.
  • GuidanceADB Vol 1, Appendix E, para E3Where sprinklers are needed they go throughout the building or separated part. Systems in residential buildings follow BS 9251. Systems in non-residential buildings, or in residential buildings outside the scope of BS 9251, follow BS EN 12845, with the extra measures for reliability in its Annex F.
  • StandardBS 9251, clause 4.1, Note 3 (opens in a new tab)Where a building mixes flats with shops or other non-residential uses, the flats are normally protected under BS 9251 and the non-residential parts under BS EN 12845.Why it applies here: This block has shops under the flats, which is the mixed use case the note covers.
  • StandardBS EN 12845 (opens in a new tab)Automatic sprinkler systems for buildings other than homes: design, installation and maintenance.Why it applies here: ADB Appendix E para E3 sends sprinkler systems in buildings, or parts of buildings, that are not residential to BS EN 12845. ADB names the 2015 edition; this page uses the current edition, BS EN 12845:2015+A2:2026.
  • StandardBS 9991, clause 17 (opens in a new tab)Sprinkler systems: a building with a floor more than 11 m above ground is sprinklered to BS 9251 or BS EN 12845, as its Table 2 sets out. Where sprinklers are fitted they should cover the whole building, including common areas assumed to be fire sterile, which goes further than the note to ADB Volume 1 para 7.4.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the shops are part of the sprinklered building it covers.
Show in the 3D model

Refuse store

  • Compartmentation
Show in the 3D model

The refuse store holds the bins, a common place for fires to start.

  • It is walled off from the rest of the building with fire-resisting construction.
  • It opens straight to the open air, away from the exits.
  • Here it is a single-storey store built against the back wall of the tower, at its west end, beside Stair A but not inside it.
  • What separates it from the rest of the building is the one wall it shares with the tower, the outside wall of Stair A.
  • Because it encloses a refuse store it is a compartment wall, which takes the period the guidance sets for the building’s height, and where Stair A is a firefighting stair it is also the shaft’s wall, built to resist fire for 120 minutes from outside the shaft.
  • Each side takes the higher of the two, never less than the 60 minutes that is the least the guidance asks of a refuse store.
  • Its roof and its three outside walls separate it from the open air, not from the rest of the building, so they are external walls, not compartment walls, and the guidance for external walls applies to them.
  • They resist fire for 60 minutes as well, because BS 5906, the code of practice for waste storage that the guidance names for refuse stores, recommends an hour for the walls and roof of a waste store.
  • Its only door opens straight to the open air, on its west side.
  • The guidance gives no distance for keeping that door away from exits and flat windows, so this model sets its own: no final exit or path from one within 5 m, and no flat window on any storey above within 2 m to the side.
  • Along the tower’s own ground floor walls every stretch is either a stair, the firefighting lift and its lobby, or has flat windows close above it, which is why the store stands outside them.
  • BS 5906 shapes the store itself too. The door is a steel fire door that resists fire for 30 minutes, in a metal frame, locked with a lock the collection crews can use and openable from inside without a key.
  • The floor is a 120 mm concrete slab, level with the pavement, so there is no step to lift a bin over, and the bins stand at least 150 mm from the walls and from each other.
  • Its doorway is raised to match, leaving 2.08 m clear above the threshold, more than the 2 m of headroom BS 5906 asks for in the store.
  • Two louvred vents, one low and one high in the south wall, more than 5 m from the nearest flat window, let out smells and the dense flammable gases that aerosols and gas canisters can give off.
  • Burning rubbish gives off very toxic smoke, and up to half of fires in waste are started on purpose. So the store is kept locked and emptied often, and the sign by its door asks for no smoking.
  • It has sprinklers too, as part of the system that runs through the whole building, with its heads laid out to clause 5.6 of the residential sprinkler standard, the clause for areas like this that are not homes. As the store opens to the outside, its pipes are lagged and heated against frost.
  • Where the store used to be is now the block’s cycle store, which has a part of its own.

REI 120Walls enclosing a refuse storage chamber are compartment walls. Where the top storey is more than 5 m above ground they need at least REI 60. Here the store’s wall to the building is both a stretch of Stair A’s firefighting shaft wall and a compartment wall, so each side meets the higher of the two. Table B2 gives 120 minutes for a top storey more than 30 m, as much as the shaft’s period from outside it and more than its 60 from inside, so the wall is REI 120 from both sides. Its outside walls and roof are REI 60, the hour BS 5906 recommends for a waste store’s walls and roof. Its door is a steel doorset, E 30.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1(c)Any wall enclosing a refuse storage chamber should be a compartment wall.
  • GuidanceADB Vol 1, para 3.60Rooms for storing refuse should be separated from other parts of the building by fire resisting construction (minimum REI 30 where the top storey is up to 5 m above ground, otherwise REI 60), and should not be in a protected stairway, evacuation shaft or protected lobby.
  • GuidanceADB Vol 1, para 3.61The approach to a refuse store should be directly from the open air, or through a protected lobby with at least 0.2 m2 of permanent ventilation.
  • GuidanceADB Vol 1, para 3.62Access openings to refuse storage chambers should not be next to escape routes or final exits, or near the windows of flats.
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: The store is part of the building, so the sprinkler system takes it in as well.
  • StandardBS 9251, Tables 3 and 4; clause 5.6 (opens in a new tab)A bin store within or below the flats is among the areas that Category 2, 3 and 4 systems protect, with BS EN 12259-1 quick response heads and the design figures of Table 4. Those figures assume the store, whether a building or a compartment, is separated from the rest of the building by at least an hour of fire resistance, and draw attention to protecting it from frost. Any other non-residential area is to be protected either to clause 5.6 or to BS EN 12845. Clause 5.6 asks for a wet pipe system with heads no more than 4 m by 3 m apart, each covering no more than 12 m², no more than half the design spacing from a wall, and with the deflector no more than 150 mm below the ceiling.Why it applies here: This refuse store is built on to a block of flats sprinklered throughout. The table’s figures are written for a bin store that is a building or a compartment of its own, and any other non-residential area may be protected to clause 5.6 or to BS EN 12845, so clause 5.6 is open to it either way, and its heads are laid out by that clause.
  • GuidanceADB Vol 1, Table B1 items 7 and 12, and Table B2Compartment walls take the Table B2 period, from each side separately: for a block of flats with sprinklers, 60 minutes with a top storey up to 18 m, 90 minutes up to 30 m and 120 minutes above 30 m. A firefighting shaft is REI 120 from the side away from the shaft and REI 60 from the shaft side.Why it applies here: The store’s wall to the building encloses a refuse storage chamber, so it is a compartment wall (para 7.1(c)). Where Stair A is a firefighting stair it is also the shaft’s wall, so it meets both, the higher period from each side.
  • GuidanceADB Vol 1, para 3.59Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
  • StandardBS 5906, clauses 4.9 and 8.1 to 8.5 (opens in a new tab)A waste store is sited at vehicle access level, preferably away from the main entrance, so that containers go straight outside without passing through the building, with at least 2 m of headroom and 150 mm clear between containers and round them. Its walls and roof are non-combustible and resist fire for an hour; its door is steel or resists fire for 30 minutes, in a metal, hardwood or metal-clad frame, lockable with a lock the collection service can use, openable from inside, and self-closing unless it opens straight to the open air. Its floor is at least 100 mm thick, hard and impervious, with no step at the entrance. Permanent vents of at least 0.2 m² in all, as near the ceiling and the floor as possible and away from the windows of homes, let out odours and dense flammable gases. It is ideally outside the building or cut off from it, so nobody can get in through it. Burning waste gives very toxic smoke, up to half of waste fires are started deliberately, and one 1100 litre wheeled bin of loose paper can burn at about 930 kW, so stores are built to hold a fire, and kept locked and signed.Why it applies here: ADB Vol 1 para 3.59 says refuse stores are sited and built to BS 5906, and this is the block’s refuse store.
  • StandardBS 9991, clause 43 (opens in a new tab)Refuse storage and disposal. Refuse stores are sited and built to BS 5906 in class A1 materials and separated from the rest of the building, with their access kept away from escape routes, final exits and the windows of homes, and not inside or reached straight from a common stair. Clause 43 c) asks for a room that stores refuse to be reached only through a protected lobby with at least 0.2 m² of permanent ventilation, or a mechanical equivalent.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the block’s refuse store. Here the two differ: ADB Vol 1 para 3.61(a) lets the approach to a refuse store be directly from the open air, and this model follows ADB, so the store’s only door opens straight outside with no lobby. Clause 43 c) gives no open-air alternative, so a design to BS 9991 would put a ventilated protected lobby in front of that door.
  • StandardBS 9991, clause 43 b) and Table 5 (opens in a new tab)Waste storage chambers are separated from the rest of the building as Table 5 sets out: a refuse store and its lobby approach resist fire for 60 minutes, each side separately, with 30 minutes between the store and its lobby.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the block’s refuse store. Its wall to the building resists fire for at least 60 minutes from each side, and its outside walls and roof for 60 minutes too, as BS 5906, which clause 43 a) names, recommends.
Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 120 / REI 90
Over 30 mREI 120
Over 50 mREI 120
Show in the 3D model

Cycle store

  • Compartmentation
Show in the 3D model

The cycle store is a room of its own for bicycles, and above all e-bikes and e-scooters with their lithium-ion batteries.

  • It is walled off from the rest of the building with fire-resisting construction and sprinklered.
  • So a fire there is held in the room and its smoke kept out of the ways out.
  • Here it is the room behind the entrance lobby, where the refuse store used to be, with stands for 24 bikes.
  • E-bikes and e-scooters carry lithium-ion batteries. A damaged or faulty one can overheat and burn fiercely, giving off thick toxic smoke, and can flare up again after it seems out, so this model treats the store as a fire risk in its own right.
  • Approved Document B has no paragraph for cycle stores. BS 9991, the residential code of practice, asks for a store like this to be separated from the rest of the building and, where it opens off a route to a final exit, to be entered through a ventilated protected lobby.
  • This one has no door into the building at all. Its only door opens straight to the open air at the back, so a battery fire cannot fill the entrance lobby, which is the way in for firefighters as well as residents, and firefighters can reach it from outside.
  • The smoke outlets from the basement below are kept at least 2 m from that door, as from every final exit.
  • Its wall to the lobby resists fire for 60 minutes, on the safe side of the nearest row in the part of BS 9991 Table 5 this model read, a store for mobility scooters, which may drop to 30 minutes where there are sprinklers. Its other sides are Stair A’s enclosure, the firefighting lobby’s wall for the last 0.45 m of its north-west corner, the wall to the Bookshop and the floor of the flats above, each already rated at least as high.
  • Its door is a self-closing fire door that resists fire for 30 minutes, opens outwards and is kept locked.
  • It has two permanent vents, one low beside the door and one high over it, about 0.4 m² in all. A failing battery gives off flammable gas, and in a sealed store that gas can build up and ignite when someone opens the door; the vents let it out. But the store’s only outside wall has flat windows above it, and vents there also let smoke out up the face, so they sit in the one gap between those windows and away from the basement’s smoke outlets, and the sprinklers and the fire door are what hold a fire in the room.
  • There are no sockets in the store, and the sign by the door says no charging.
  • It has four sprinkler heads, laid out to clause 5.6 of the residential sprinkler standard for residents’ stores, fed from the pipe that crosses its ceiling on the way to the refuse store.

Sprinklers can hold a fire around a battery and keep it from spreading to the bikes beside it, but may not stop a battery that is already burning on its own.

REI 60Wall to the entrance lobby REI 60, on the safe side of the nearest row in the part of BS 9991 Table 5 this model read (mobility scooter storage, 30 with residential sprinklers). Its other sides are Stair A’s enclosure, the firefighting lobby’s wall for the last 0.45 m of its north-west corner, the compartment wall to the Bookshop and the compartment floor of the flats above, each rated for itself and at least as high. Door to the open air E 30, self-closing.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: The cycle store is part of the building and is not a fire-sterile common area, so the sprinkler system takes it in.
  • StandardBS 9251, Tables 3 and 4 (residents’ stores); clause 5.6 (opens in a new tab)Residents’ storage sheds and tenant stores are among the areas that Category 2, 3 and 4 systems protect with BS EN 12259-1 quick response heads, laid out by clause 5.6 with an area of operation of four heads, and the table draws attention to protecting them from frost. Any other non-residential area is to be protected either to clause 5.6 or to BS EN 12845. Clause 5.6 asks for a wet pipe system with a design density of at least 5 mm/min, heads no more than 4 m by 3 m apart, each covering no more than 12 m², no more than half the design spacing from a wall, and with the deflector no more than 150 mm below the ceiling; where such an area’s fire compartment is over 100 m², BS EN 12845 applies in full.Why it applies here: A cycle store keeps residents’ belongings, so this model reads it as a residents’ store. If it were not one, any other non-residential area is sent to the same clause, so its heads are laid out by clause 5.6 either way. At about 39 m² it is far under 100 m².
  • StandardBS 9991, clauses 15.1 and 34, Tables 1 and 16 (opens in a new tab)Ancillary areas such as stores are separated from the rest of the building, other ancillary areas included, and in a building with more than one stair from each stair by a protected lobby or corridor. One that opens off the route from a stair to its final exit is entered through a protected lobby ventilated as Table 1 sets out, and Table 1 names bicycle stores, with or without charging points, among the areas it covers. Table 16 keeps travel within a bicycle store to 9 m where there is one way out.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the block’s cycle store. It has no door into the building at all, so no lobby is needed: its only door opens to the open air, and the farthest point is 7.3 m from it in a straight line, about 8.2 m walked by the aisle.
  • StandardBS 9991, clause 75 and Table 5 (opens in a new tab)Charging points for electric wheelchairs and mobility scooters are kept out of common corridors and protected stairs, and in a sprinklered building the sprinklers are extended to the charging areas. Table 5 separates storage for them from the rest of the building by 60 minutes, each side separately, or 30 minutes with a residential sprinkler system.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and its Table 1 names bicycle stores, with and without charging points, but the part of Table 5 this model read has no row of their own, so it takes the nearest, storage for mobility scooters. The store’s wall to the entrance lobby resists fire for 60 minutes, the safe side of that row, and the store has no charging points.
Show in the 3D model

Evacuation alert control panel

  • Detection and alarm
Show in the 3D model

The control panel for the evacuation alert system sits near the entrance, where firefighters arrive.

  • From here the incident commander can sound the alert on one floor or on several, one switch for each floor, if they decide residents should leave.
  • There is deliberately no single switch for the whole building: to clear it, they turn on every floor’s switch.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.17In blocks of flats with a top storey over 18 m above ground level, an evacuation alert system should be provided in accordance with BS 8629.
  • StandardBS 8629 (opens in a new tab)Design, installation, commissioning and maintenance of evacuation alert systems for the fire and rescue service in buildings containing flats.Why it applies here: ADB para 15.17 asks for an evacuation alert system in this block because its top storey is over 18 m, and names BS 8629 as the standard it follows. ADB names the 2019 edition; this page uses the current edition, BS 8629:2019+A1:2023.
  • StandardBS 9991, clause 48.3 (opens in a new tab)Evacuation alert systems for use by the fire and rescue service.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the evacuation alert system this part belongs to.

Only in this building at: Over 18 m, Over 30 m, Over 50 m.

Show in the 3D model

Secure information box

The secure information box is a locked box by the entrance that firefighters can open.

  • It holds what they need at the start of an incident: the responsible person’s contact details, a plan of every floor and a single-page plan of the building.
  • It is checked at least once a year.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.19Blocks of flats with a top storey more than 11 m above ground level should be provided with a secure information box.
  • GuidanceADB Vol 1, para 15.20The box should be sized for all the necessary information, easy for firefighters to find and identify, secure against unauthorised access but readily accessible to firefighters, and protected from the weather.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 4In a high-rise residential building the responsible person installs a secure information box in or on the building, readily accessible to the fire and rescue service, keeps their contact details in it, and inspects it at least once a year.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 6Floor plans showing the lifts and key fire-fighting equipment, and a single-page building plan, are kept in the box and updated when the building changes.
  • StandardBS 9991, clause 48.1 (opens in a new tab)Secure information boxes.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the block’s secure information box.
Show in the 3D model

Dry riser inlet

This is where the fire engine connects to the dry riser.

  • It is on the face of the building, in a locked red box, within 18 m of where the engine parks and in sight of it.
  • Water pumped in here fills the main all the way to the top.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 13.5For buildings fitted with dry fire mains, a pumping appliance should be able to get within 18 m of each fire main inlet. Inlets should be on the face of the building, visible from where the appliance parks, and meet Section 8 of BS 9990.
  • StandardBS 9990, clause 4.1.3.2 and Section 8 (opens in a new tab)Clause 4.1.3.2 sets the inlet itself: a two-way breeching inlet in an inlet box, its lower edge 400 mm to 600 mm above the ground. Section 8 covers signage: identifying the equipment and giving information about the system.Why it applies here: ADB para 13.5(b) asks the inlet to meet Section 8 of BS 9990, which is about signing and identifying it; clause 4.1.3.2 is where the standard sets out the inlet.
  • Ongoing dutyFire Safety Order 2005, Article 38Facilities and equipment provided for firefighters, such as the fire main and its inlet, are kept maintained in efficient working order and good repair.
  • StandardBS 9991, clause 47.1 (opens in a new tab)Fire mains, including their inlets.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the inlet is where the fire main is fed.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Fire service hardstanding

A strong, level area beside the building where a fire engine parks to pump water into the dry riser.

  • It is marked and kept clear. A car parked here could stop the engine getting close enough, and every minute spent finding another place is a minute without water on the fire floor.
  • The fire engine shows how it should work: parked on the hardstanding, in sight of the inlet and close enough to connect a hose to the fire main.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 13.3Access routes and hardstandings should comply with the guidance in Table 13.1.
  • GuidanceADB Vol 1, Table 13.1For a pump appliance: at least 3.7 m between kerbs, gateways at least 3.1 m wide, clearance height at least 3.7 m, and a carrying capacity of at least 12.5 tonnes.
  • GuidanceADB Vol 1, para 13.4Dead-end access routes longer than 20 m need turning facilities, so fire engines do not have to reverse more than 20 m. This one is about 16 m long.
  • GuidanceADB Vol 1, para 13.5Pumping appliance access to within 18 m of each inlet, and the inlet visible from where the appliance parks.
  • StandardBS 9991, clause 46.1 (opens in a new tab)Access for fire appliances.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the hardstanding is where the fire appliance parks.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

The basement

Stair A down to the basement

  • Means of escape
  • Firefighting
Show in the 3D model

Stair A carries on down to the basement, and Stair B stops at the ground floor.

  • Where several stairs serve the floors above, only one has to end at the ground floor; the others may carry on down to a basement through a protected lobby.
  • In a block of this height with only one stair, that stair should not go down: the basement would need a stair of its own.
  • Stair B goes straight out to the street, with no door into the shops or the basement, so smoke from a fire down here has no way into it.
  • Stair A is the firefighting stair. ADB does not ask for a firefighting shaft to serve a basement this small and shallow.
  • This model reads ADB as asking a shaft to serve every storey the stair passes through, with a fire main outlet at each, so once Stair A carries on down, firefighters have the same protected stair and water here as on every other floor.
  • Whether a stair may instead pass down without its shaft serving the basement is for the designer to check.
  • No point in any room down here is more than 9 m from its door, or more than 18 m from the stair, the limits ADB Volume 2 sets for plant rooms with only one way out.
  • Like every escape stair in a basement, its flights and landings are class A2-s3, d2 or better.
  • At the ground floor the way out is at the foot of the flight from above, and the flight down to the basement turns back the other way, so nobody coming down from the flats is led on past the exit.

Stair A going down also changes the basis of its shaft’s smoke control.

  • ADB lets a firefighting shaft that serves only flats use the provisions for flats, and otherwise asks for smoke control to BS 9999.
  • ADB does not say whether plant serving the flats counts against “only serves flats”, so this model takes the cautious reading.

What that would change in practice is for the designer to check against BS 9999; the floors above still show the flats’ corridor smoke shaft.

REI 120 / REI 60Stair A’s firefighting shaft enclosure carries on below ground with the stair: 120 minutes from the basement side, 60 from inside the shaft. Stair door E 30 Sa.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.74Except in the small single stair buildings described in para 3.32, an escape stair that is part of the only escape route from an upper storey should not continue down to serve a basement storey; the basement should have a separate escape stair.
  • GuidanceADB Vol 1, para 3.75Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
  • GuidanceADB Vol 1, para 3.85(b)The flights and landings of an escape stair within a basement storey should be built of materials achieving class A2-s3, d2 or better.
  • GuidanceADB Vol 1, Table C1 item 2bDoors into a protected stair in a block of flats: E 30 Sa.
  • GuidanceADB Vol 1, para 0.18For the design of a mixed use building, Approved Document B Volume 2 should be consulted as well as Volume 1.
  • GuidanceADB Vol 2, Table 2.1Plant rooms, where escape is in one direction only: at most 9 m of travel within the room, and 18 m overall along an escape route not in the open air. Places of special fire hazard: at most 9 m within the room, and outside it the limits for the rest of the building or part.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.2Firefighting shafts are not required to serve a basement that is not large or deep enough to need one (see para 15.3 and Diagram 15.2).
  • GuidanceADB Vol 1, para 15.4Firefighting shafts should serve all storeys through which they pass.
  • GuidanceADB Vol 1, para 15.10All firefighting shafts should have fire mains with outlet connections and valves at every storey.
  • GuidanceADB Vol 1, para 15.9 and Table B1 item 12Firefighting shaft REI 120 from the side remote from the shaft, REI 60 from the shaft side, and REI 60 between the stair, lift shaft and lobby.
  • GuidanceADB Vol 1, Diagram 15.1 note 2Smoke control should be provided in accordance with BS 9999 or, where the firefighting shaft only serves flats, the provisions for smoke control given in paragraph 3.53 may be followed instead.
  • StandardBS 9990, clause 4.1.5 (opens in a new tab)A landing valve on every floor, including the ground floor. In blocks of flats it sits on the full landing inside the stair enclosure, with its lowest point about 750 mm above the floor.Why it applies here: This is the valve firefighters connect their hose to on each floor, and the clause sets where it goes and how high.
  • StandardBS 9991, clause 11.1 (opens in a new tab)Basement stairs in a building with more than one stair: at least one stair from the upper storeys ends at ground level, and any other stair that carries on down is separated from each basement level by a protected lobby.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and Stair B ends at ground level and Stair A carries on down to the basement through a protected lobby.
  • StandardBS 9991, clause 46.3 (opens in a new tab)How firefighting shafts are built: the stair, the lobby and the firefighting lift.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the firefighting shaft this part belongs to.
  • StandardBS 9991, clause 47.1 and Figure 47 (opens in a new tab)Fire mains, and where their outlets sit in a firefighting shaft.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the fire main this part belongs to.

INFIRISK guides

No INFIRISK guide on this yet.

Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 120 / REI 60
Over 30 mREI 120 / REI 60
Over 50 mREI 120 / REI 60
Show in the 3D model

Firefighting lobby in the basement

  • Means of escape
  • Firefighting
  • Smoke control
Show in the 3D model

Between Stair A and the basement is a lobby with a fire door at each end, so smoke from a fire down here has two doors to get through before it reaches the stair.

  • ADB would accept a protected lobby here, but Stair A brings its firefighting shaft down to this storey, so this model builds a firefighting lobby, like the ones above it.
  • BS 9999:2017 (Table 21, items 7 and 8) and BS 9991:2024 (clause 20.3.2.1) ask a firefighting lobby at basement level to have a vent: a 1 m² vent to open air, opened by hand, or one into a shaft.
  • This lobby has none: it has no outside wall, and the fan that pressurises it stands in its place.
  • A design to those documents would add the vent, or show that the fan does as well.
  • The stair also serves a place of special fire hazard, the switch room, so the lobby needs either a permanent vent of at least 0.4 m² or a mechanical system that keeps smoke out.
  • The lobby has no outside wall for a vent, so a fan in its own chamber next to it, against the west wall, blows in fresh air drawn through a grating in the ground well away from the fire service hardstanding, south-west of the building.
  • A fire engine pumping at a fire can stand on the hardstanding for hours, and the fan must not draw its exhaust into the lobby, so a duct about 17 m long runs under the ground to the grating, which also keeps it off the pavement where bins are wheeled out.
  • The fan is sized for that long duct.
  • The chamber is reached from the corridor, not from the lobby: a room for plant should not open off a protected lobby that is the only way out of its storey.
  • It is not part of the lobby either, but its own fire-resisting enclosure with its own fire door, built to the lobby’s standard and sprinklered like the plant rooms.
  • Its air passes into the lobby through a short fire-resisting sleeve in the shared wall, with no damper, because a damper would shut off the air the lobby needs.
  • The fan is meant to keep the lobby at a higher pressure than the basement. That works only if the air it pushes in can get away: past the lobby door into the corridor, then through the plant, sprinkler and water rooms to their smoke outlets, with those doors opened.
  • This model assumes that path is enough; the switch room is never part of it, because its door stays shut and its outlet serves it alone. The fan runs on the supply the standby generator backs up.
  • The lift stops at the ground floor. ADB would let a lift serve the basement through a lobby like this one, but a firefighting lift is only needed below ground where a basement is more than 10 m deep, and keeping the lift out keeps basement smoke out of the lift well that serves every floor.

REI 120 / REI 60The lobby is built as part of the firefighting shaft (ADB Diagram 15.1): 120 minutes from the basement side and 60 from inside the shaft, an E 60 Sa door from the corridor and an E 30 Sa door to the stair. The fan chamber beside it is not part of the shaft. It is its own fire-resisting enclosure, built to the lobby’s period: REI 120 walls and an E 60 Sa door from the corridor. Its air reaches the lobby through a short fire-resisting sleeve in the shared wall, with no damper.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.75Where multiple escape stairs serve the upper storeys, only one needs to end at ground level. Other stairs may connect with the basement storeys if there is a protected lobby or a protected corridor between the stairs and accommodation at each basement level.
  • GuidanceADB Vol 1, para 3.77Where a common stair is not part of the only escape route from a flat, it may also serve ancillary accommodation from which it is separated by a protected lobby or protected corridor (minimum REI 30).
  • GuidanceADB Vol 1, para 3.78Where a stair serves an enclosed car park or place of special fire hazard, the lobby or corridor should have a minimum 0.4 m² of permanent ventilation or be protected from the ingress of smoke by a mechanical smoke control system.
  • GuidanceADB Vol 1, para 3.41Ancillary accommodation should not be located in, or entered from, a protected lobby or protected corridor forming the only common escape route on that storey.
  • GuidanceADB Vol 1, Table C1 item 5aDoor forming part of the enclosure of a protected lobby approach to a stairway: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, Table C1 note 2Doors marked Sa (or S) must also limit smoke leakage, unless pressurisation techniques that comply with BS EN 12101-6 are used.
  • GuidanceADB Vol 1, para 3.105In basements and enclosed car parks, the lift should be within the enclosure of a protected stairway or evacuation shaft. Otherwise, the lift should be approached only via a protected lobby or protected corridor (minimum REI 30).
  • GuidanceADB Vol 1, para 3.107A lift shaft serving storeys above ground level should not serve a basement where there is only one escape stair and smoke from a basement fire would affect escape from the upper storeys, or where the lift shaft is within the enclosure of an escape stair that ends at ground level.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 15.2Firefighting shafts are not required to serve a basement that is not large or deep enough to need one (see para 15.3 and Diagram 15.2).
  • GuidanceADB Vol 1, para 15.8Firefighting stairs and lifts are approached from a firefighting lobby, or from a protected corridor or protected lobby that meets the guidance on means of escape (Section 3) and compartmentation (Section 7). Both the stair and the lobby of a firefighting shaft should have a means of venting smoke and heat (clause 27.1 of BS 9999), and only services for the shaft, such as its ventilation and lighting, should pass through or be contained in it.
  • GuidanceADB Vol 1, Diagram 15.1Firefighting shaft: REI 120 from the accommodation side and REI 60 from inside the shaft, with E 60 Sa fire doors; REI 60 from both sides, with E 30 Sa fire doors, between the stair, the lift shaft and the lobby.
  • GuidanceADB Vol 1, para 15.3A basement needs firefighting shafts where it is more than 10 m below fire and rescue service vehicle access level (with firefighting lifts), or where there are two or more basement storeys each with a minimum area of 900 m² (lifts not needed).
  • StandardBS 9999, clause 27.1 (opens in a new tab)Venting of smoke and heat from the firefighting stair and lobby, as referred to by ADB para 15.8.Why it applies here: ADB para 15.8 points to this clause for keeping a firefighting shaft’s stair and lobby clear of smoke.
  • StandardBS 9999, Table 21 items 7 and 8 (opens in a new tab)A firefighting lobby at basement level, where the basement is less than 10 m below ground, has a vent: a manual vent of at least 1.0 m² direct to open air, or an automatic vent of at least 1.0 m² into a common smoke shaft. BS 9991:2024 clause 20.3.2.1 asks the same of such a lobby: a 1 m² manual vent or a 0.7 m² automatic vent to open air or to a shaft serving that level only, or an extension of the shaft from above ground, if its total height is no more than 30 m.Why it applies here: Stair A’s firefighting shaft goes down to the basement, so this model follows BS 9999 for it. The basement’s firefighting lobby has no vent: it has no outside wall, and the fan that pressurises it stands in its place. This model does not claim the fan meets these items.
  • StandardBS EN 12101, Part 13 (opens in a new tab)Design, installation and testing of pressure differential systems: systems that keep a space at a higher pressure than the spaces round it, so smoke stays out.Why it applies here: The fan keeps this lobby at a higher pressure than the basement. ADB Table C1 note 2 still names BS EN 12101-6, which is now the specification for the kit only; the design, installation and testing of the system are in Part 13.
  • StandardBS 9991, clause 46.3 (opens in a new tab)How firefighting shafts are built: the stair, the lobby and the firefighting lift.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this clause covers the firefighting shaft this part belongs to.
  • StandardBS 9991, clause 13.2 and Table 1 (opens in a new tab)Ventilation of protected lobbies and protected corridors.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this is the protected lobby between Stair A and the basement.
Fire resistance by height of the top storey
Over 11 mREI 30
Over 18 mREI 120 / REI 60
Over 30 mREI 120 / REI 60
Over 50 mREI 120 / REI 60
Show in the 3D model

Basement smoke outlets

  • Smoke control
  • Firefighting
Show in the 3D model

A basement has no windows, so heat and smoke from a fire down here would otherwise pour up the stair that firefighters need to come down.

  • Each room except the fan chamber has its own outlet, high in the outside wall, into a shaft that rises to a steel grating in the pavement, and firefighters can also use the outlets to let cooler air in.
  • ADB lets a basement storey do without outlets direct to the open air where it is both no more than 200 m² and no more than 3 m below the ground beside it, and says a basement storey containing rooms with doors or windows needs none, which this model reads as doors or windows to the open air. This one is about 196 m², but its floor is 3.5 m down and its rooms have no windows or doors to the open air, so it needs them.
  • Together they must give a clear area of at least a fortieth of the floor area, about 4.9 m², measured where each way out is narrowest; these give about 4.91 m², just over, taking each grating’s free area as half its size, an assumption the product chosen must meet.
  • The switch room, a place of special fire hazard, has an outlet of its own. The short corridor has no outside wall, so it is vented through the plant room, the sprinkler room and the water tank room by opening their doors, never through the switch room.
  • The lobby fan’s small chamber has no outlet of its own because one is impracticable there. Its only outside wall faces Stair A’s way out to the street and holds the fan’s own air intake, so an outlet there would put smoke beside the exit. Where an outlet is not practicable, ADB lets a space be vented indirectly by opening connecting doors, so the chamber is vented the same way as the corridor, by opening its door. ADB’s example is a deep plan with little outside wall, and the chamber is on the outside wall, so treating it this way is this model’s own reasoning, for the designer to check.
  • The gratings are near each end of the front and back pavements. Final exits should avoid basement smoke outlets and no outlet may block a way out, so this model keeps every grating at least 2 m from every final exit, the cycle store’s door at the back included, and clear of the paths from them, and at least 1 m from the refuse store door, where bins are wheeled out. Inside, nothing stands within 1 m in front of an outlet.
  • The basement is sprinklered, so ADB would also accept a mechanical smoke extract system instead. This model keeps natural outlets, which need no fans, power or controls.
In existing buildings

In older buildings basement smoke outlets are often covered over, blocked by bins or planters, or lost under new paving. They only work if they are kept clear.

REI 120 · class A1Each outlet shaft is class A1 construction with the fire resistance of the floor over the basement (ADB para 16.13 and Diagram 16.1): 120 minutes at this height.

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 16.1Heat and smoke from basement fires vented via stairs can inhibit access for firefighters. Smoke outlets let heat and smoke escape to the open air, and firefighters can use them to let cooler air into the basement.
  • GuidanceADB Vol 1, paras 16.2 and 16.3Each basement space should have one or more smoke outlets. Where that is not practicable (for example, a deep plan whose external wall is restricted by adjoining buildings), the perimeter spaces may be vented and the other spaces vented indirectly by opening connecting doors, but not a place of special fire hazard. Every basement storey needs outlets direct to the open air unless it is both no more than 200 m² and no more than 3 m below the adjacent ground. A basement storey or compartment containing rooms with doors or windows does not need smoke outlets.
  • GuidanceADB Vol 1, paras 16.5 and 16.6Smoke outlets should be at high level, evenly distributed around the perimeter, and together give a clear cross-sectional area of at least 1/40 of the floor area of the storey they serve.
  • GuidanceADB Vol 1, Appendix D, para D5 and Diagram D3The free area of a smoke ventilator is its declared aerodynamic free area, or the total unobstructed cross-sectional area measured where it is smallest, at right angles to the air flow. The floor area of a storey is measured to the inner surface of its enclosing walls, internal walls included.
  • GuidanceADB Vol 1, para 16.7Separate outlets should be provided from places of special fire hazard.
  • GuidanceADB Vol 1, paras 16.8 to 16.10An outlet that is not readily accessible is kept unobstructed, covered only by a class A1 grille or louvre. One in a readily accessible place may instead have a cover that can be broken out or opened, with its position marked. Outlets should not be placed where they prevent the use of escape routes from the building.
  • GuidanceADB Vol 1, paras 16.11 and 16.12Where basement storeys are sprinklered in accordance with Appendix E, a mechanical smoke extraction system may be provided instead of natural venting. It should give at least 10 air changes an hour, handle gas temperatures of 300°C for at least an hour, and start automatically when the sprinklers operate or from automatic fire detection to BS 5839-1 (minimum L3).
  • GuidanceADB Vol 1, para 16.13 and Diagram 16.1Outlet ducts or shafts, including any bulkheads over them, should be enclosed in class A1 construction with fire resistance at least equal to that of the element through which they pass; Diagram 16.1 shows the same rating as the floor of the ground storey.
  • GuidanceADB Vol 1, para 3.112Final exits should avoid outlets of basement smoke vents and openings to transformer chambers, refuse chambers, boiler rooms and similar risks.
  • Ongoing dutyFire Safety Order 2005, Article 38Where necessary to safeguard firefighters, the responsible person keeps the premises and the facilities, equipment and devices provided for their use or protection under a suitable system of maintenance, in efficient working order and good repair.

INFIRISK guides

No INFIRISK guide on this yet.

Fire resistance by height of the top storey
Over 11 mREI 60 · class A1
Over 18 mREI 90 · class A1
Over 30 mREI 120 · class A1
Over 50 mREI 120 · class A1
Show in the 3D model

Electrical intake and switch room

  • Compartmentation
Show in the 3D model

The building’s electricity supply comes in here, with the meters and the main switchboard that feeds the flats, the lifts and the fire safety systems.

  • ADB names a switch gear room as a place of special fire hazard, so this room is enclosed in fire-resisting construction with a fire door, keeping a fire in here away from the rest of the basement, and it has a smoke outlet of its own.
  • It has sprinklers like every room down here: the sprinkler standard lists electrical rooms among the areas it protects, and notes that sprinkler protection near electrical equipment is generally safe.
  • A building that needs its own oil-filled transformer would have another place of special fire hazard, usually a substation with its own door to the outside.

This model puts the intake in the basement. Other buildings put it on the ground floor, often with a door straight to the outside, or elsewhere, and the same protection applies wherever it is.

REI 30Places of special fire hazard are enclosed with at least REI 30. These walls are not compartment walls. Door E 30.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.2Fire resisting construction enclosing places of special fire hazard should achieve minimum REI 30. These walls and floors are not compartment walls and compartment floors.
  • GuidanceADB Vol 1, Appendix APlaces of special fire hazard include oil-filled transformer rooms, switch gear rooms, boiler rooms, storage spaces for fuel or other highly flammable substances, and rooms housing a fixed internal combustion engine.
  • GuidanceADB Vol 1, Table C1 item 10aDoor forming part of the enclosure to a place of special fire hazard: E 30 (FD 30).
  • GuidanceADB Vol 1, para 16.7Separate outlets should be provided from places of special fire hazard.
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: Throughout the building takes in this basement’s plant rooms: the note excepts only fire-sterile common areas, here the corridor, the lobby and the stair.
  • StandardBS 9251, clause 5.4 and Table 3 (opens in a new tab)Sprinkler protection is provided in all parts of the premises, with a short list of exceptions such as small bathrooms, enclosed stairs and shafts of the stated construction, and plant rooms with no direct access from inside the building. Table 3 names electrical rooms and plant rooms among the areas protected in Category 2, 3 and 4 systems.Why it applies here: A room reached from inside the building meets none of the clause 5.4 exceptions, so it is sprinklered like every other room down here; Table 3 gives its design figures.
  • StandardBS 9991, clauses 35 and 36 (opens in a new tab)Places of special fire hazard, and rooms that house engineering services.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this room is both a place of special fire hazard and a plant room.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Sprinkler tank and pump room

The water for the building’s sprinklers is stored here and pumped to them: up the service riser to a valve set on every floor for the flats, and to the heads in every room down here, this one and the lobby fan’s chamber included.

  • Only the fire-sterile corridor, lobby and stair have none.
  • The pumps start on their own when a sprinkler head opens.
  • The main leaves the basement through a fire-resisting riser enclosure, boxed in where it crosses the shop above, and carries on up the building’s service riser.
  • Above 18 m BS 9991 asks for a Category 4 system, and for that the sprinkler standard asks for a more reliable water supply.
  • Here it is a tank split into two halves feeding two pumps that work independently, so either pump can draw from either half and one can be shut down for servicing while the other keeps the system live.
  • The pumps have a back-up power supply that switches over on its own: the standby generator on the roof, through fire-resisting cables.
  • The sprinkler standard puts the pumps either where sprinklers protect them, as here, or in a fire compartment holding only sprinkler plant, and somewhere flooding is unlikely to reach them.
  • A basement can flood from a burst pipe, the tanks themselves or the ground, so the pumps stand on a raised plinth and the floor drains to a sump.
  • They run on electricity, so this is not a place of special fire hazard; a diesel pump engine would make it one.

This model puts the tank and pumps in the basement. Other buildings put them on the ground floor or elsewhere, and the same protection applies wherever they are.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: Throughout the building takes in this basement’s plant rooms: the note excepts only fire-sterile common areas, here the corridor, the lobby and the stair.
  • GuidanceADB Vol 1, Appendix E, para E3Where sprinklers are needed they go throughout the building or separated part. Systems in residential buildings follow BS 9251. Systems in non-residential buildings, or in residential buildings outside the scope of BS 9251, follow BS EN 12845, with the extra measures for reliability in its Annex F.
  • GuidanceADB Vol 1, Appendix APlaces of special fire hazard include oil-filled transformer rooms, switch gear rooms, boiler rooms, storage spaces for fuel or other highly flammable substances, and rooms housing a fixed internal combustion engine.
  • StandardBS 9251, clause 5.4 and Table 3 (opens in a new tab)Sprinkler protection is provided in all parts of the premises, with a short list of exceptions such as small bathrooms, enclosed stairs and shafts of the stated construction, and plant rooms with no direct access from inside the building. Table 3 names electrical rooms and plant rooms among the areas protected in Category 2, 3 and 4 systems.Why it applies here: A room reached from inside the building meets none of the exceptions, so it is sprinklered.
  • StandardBS 9251, clause 5.12.1 a) and g) (opens in a new tab)In a Category 2, 3 or 4 system the pump set is either in an area protected by the sprinkler system, or in a fire compartment holding only the sprinkler system’s plant and electrical equipment, with fire resistance at least as long as the system must run; and it is sited where flooding is unlikely to affect it.Why it applies here: These are the system’s pumps: a sprinklered pump room meets the first of the two options, and a basement is a place that can flood.
  • StandardBS 9251, clauses 5.12.5.1 and 5.12.5.3 (opens in a new tab)A Category 4 system has an enhanced water supply. One way is two or more half-capacity tanks (a split tank will do) feeding two or more pumps that work independently, each able to draw from each tank, with any pump or tank able to be isolated for maintenance, and a back-up power supply that changes over automatically: an emergency generator, uninterruptible power supplies, a second grid supply from a separate substation, or a diesel pump in place of back-up power.Why it applies here: A Category 4 system needs an enhanced water supply, and this clause sets out the arrangement drawn here.
  • StandardBS 9991, clause 17 and Table 2 (opens in a new tab)Sprinkler systems. For a block of flats over 18 m: a BS 9251 Category 4 system, or a BS EN 12845 system to Ordinary Hazard 1 as the alternative.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and its Table 2 sets which category of sprinkler system a block of this height needs.
Show in the 3D model

Water tank and booster pump room

  • Compartmentation
Show in the 3D model

Drinking water for the flats is stored here in two tanks, so one can be emptied and cleaned while the other stays in use, and a booster set pumps it up the building, because mains pressure alone will not reach the upper floors.

  • It is not a place of special fire hazard, so ADB asks for no fire-resisting walls round it, but it is inside the basement’s own fire compartment, it has sprinklers, and it has its own smoke outlet to the street.
  • Some buildings share one water supply between the flats and the sprinklers, arranged so the sprinklers always get what they need; this model keeps them apart.
  • The rising main leaves through the same fire-resisting riser enclosure as the sprinkler main, boxed in where it crosses the shop above.

This model puts the tanks and pumps in the basement. Other buildings put them on the roof, on the ground floor or elsewhere, and the same protection applies wherever they are.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1(a)Any floor, unless it is within a flat, should be a compartment floor.
  • GuidanceADB Vol 1, Appendix APlaces of special fire hazard include oil-filled transformer rooms, switch gear rooms, boiler rooms, storage spaces for fuel or other highly flammable substances, and rooms housing a fixed internal combustion engine.
  • GuidanceADB Vol 1, paras 16.2 and 16.3Each basement space should have one or more smoke outlets. Where that is not practicable (for example, a deep plan whose external wall is restricted by adjoining buildings), the perimeter spaces may be vented and the other spaces vented indirectly by opening connecting doors, but not a place of special fire hazard. Every basement storey needs outlets direct to the open air unless it is both no more than 200 m² and no more than 3 m below the adjacent ground. A basement storey or compartment containing rooms with doors or windows does not need smoke outlets.
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: Throughout the building takes in this basement’s plant rooms: the note excepts only fire-sterile common areas, here the corridor, the lobby and the stair.
  • StandardBS 9251, clause 5.4 and Table 3 (opens in a new tab)Sprinkler protection is provided in all parts of the premises, with a short list of exceptions such as small bathrooms, enclosed stairs and shafts of the stated construction, and plant rooms with no direct access from inside the building. Table 3 names electrical rooms and plant rooms among the areas protected in Category 2, 3 and 4 systems.Why it applies here: A room reached from inside the building meets none of the exceptions, so it is sprinklered.
  • StandardBS 9991, clauses 35 and 36 (opens in a new tab)Places of special fire hazard, and rooms that house engineering services.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this room houses engineering services.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

General plant room

  • Compartmentation
Show in the 3D model

Pumps, controls and water treatment for the communal heating are here; the boilers themselves are on the roof.

  • None of that makes it a place of special fire hazard, which ADB keeps for rooms such as switch gear rooms, oil-filled transformer rooms, boiler rooms, stores of fuel or other highly flammable substances, and rooms with a fixed engine.
  • Put a boiler or a generator in here and it would become one, with fire-resisting walls and a fire door like the switch room.
  • It has sprinklers, and its own smoke outlet to the street.

This model puts this plant in the basement. Other buildings put it on the ground floor, on the roof or elsewhere, and the same protection applies wherever it is.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, Appendix APlaces of special fire hazard include oil-filled transformer rooms, switch gear rooms, boiler rooms, storage spaces for fuel or other highly flammable substances, and rooms housing a fixed internal combustion engine.
  • GuidanceADB Vol 1, paras 16.2 and 16.3Each basement space should have one or more smoke outlets. Where that is not practicable (for example, a deep plan whose external wall is restricted by adjoining buildings), the perimeter spaces may be vented and the other spaces vented indirectly by opening connecting doors, but not a place of special fire hazard. Every basement storey needs outlets direct to the open air unless it is both no more than 200 m² and no more than 3 m below the adjacent ground. A basement storey or compartment containing rooms with doors or windows does not need smoke outlets.
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.Why it applies here: Throughout the building takes in this basement’s plant rooms: the note excepts only fire-sterile common areas, here the corridor, the lobby and the stair.
  • StandardBS 9251, clause 5.4 and Table 3 (opens in a new tab)Sprinkler protection is provided in all parts of the premises, with a short list of exceptions such as small bathrooms, enclosed stairs and shafts of the stated construction, and plant rooms with no direct access from inside the building. Table 3 names electrical rooms and plant rooms among the areas protected in Category 2, 3 and 4 systems.Why it applies here: A room reached from inside the building meets none of the exceptions, so it is sprinklered.
  • StandardBS 9991, clauses 35 and 36 (opens in a new tab)Places of special fire hazard, and rooms that house engineering services.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this room houses engineering services.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Basement walls and the floor over

  • Compartmentation
Show in the 3D model

The basement is one storey under the west half of the building, its floor 3.5 m below the street.

  • Any storey with a floor that is, at any point, more than 1.2 m below the highest level of the ground beside its outside walls counts as a basement.
  • The floor over it is a compartment floor, keeping a fire down here out of the shops and the entrance above.
  • ADB Table B2 gives 60 minutes for a basement up to 10 m deep in a sprinklered block of flats, but the floor over a basement takes the higher of that and the figure for the rest of the building, which rises with the height of the top storey.
  • The basement walls hold up the building above them, and anything that supports another part of the structure must last at least as long, so they take the tower’s figure too.
  • Firefighters come down Stair A, while the smoke outlets let the heat out.

In deeper basements, more applies.

  • A basement more than 10 m below where fire engines park needs firefighting shafts, with firefighting lifts in them, and two or more basement storeys of at least 900 m² each need firefighting shafts too, though not lifts.
  • In a block of flats, each basement storey and the floor over it needs 90 minutes of fire resistance once the lowest basement is more than 10 m deep, against 60 minutes up to 10 m.
  • Where several basement storeys each have natural smoke outlets, the outlet shafts from different storeys are kept apart by class A1 construction that resists fire as long as those storeys.
  • None of this applies here: this basement is one storey, about 3.5 m deep and about 196 m².

REI 120Floor over the basement: the higher of 60 minutes for a basement up to 10 m deep and 120 minutes for a sprinklered block of flats with a top storey more than 30 m (Table B2). The loadbearing basement walls hold up the building above, so they need at least the same: R 120.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, Appendix ABasement storey: a storey with a floor that, at some point, is more than 1200 mm below the highest level of ground beside the outside walls.
  • GuidanceADB Vol 1, para 7.1(a)Any floor, unless it is within a flat, should be a compartment floor.
  • GuidanceADB Vol 1, Table B1 item 3c and Table B2Floors take the period in Table B2. For a block of flats with sprinklers, a basement up to 10 m deep is 60 minutes, and for the floor over a basement the higher of the basement period and the period for the ground and upper storeys applies.
  • GuidanceADB Vol 1, Appendix B, para B25(a)If one element of structure supports or carries or gives stability to another, the fire resistance of the supporting element should be no less than the minimum period of fire resistance for the other element.
  • GuidanceADB Vol 1, para 15.3A basement needs firefighting shafts where it is more than 10 m below fire and rescue service vehicle access level (with firefighting lifts), or where there are two or more basement storeys each with a minimum area of 900 m² (lifts not needed).
  • GuidanceADB Vol 1, para 15.3(a)A building with a basement more than 10 m below the fire and rescue service vehicle access level should have firefighting shafts, and the shafts should contain firefighting lifts.
  • GuidanceADB Vol 1, para 15.3(b)A building with two or more basement storeys, each with a minimum area of 900 m², should have firefighting shafts; these do not need to include firefighting lifts.
  • GuidanceADB Vol 1, Table B2For a block of flats, a basement storey, including the floor over it, needs 90 minutes of fire resistance where the lowest basement is more than 10 m deep, and 60 minutes where it is up to 10 m deep.
  • GuidanceADB Vol 1, para 16.14(b)Natural smoke outlet shafts from different basement storeys should be separated from each other by construction of class A1 rating, with fire resistance at least equal to that of the storeys they serve.
  • StandardBS 9991, clause 22.1 and Table 5 (opens in a new tab)Minimum fire resistance for elements of structure.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the basement walls and the floor over the basement are elements of structure.

INFIRISK guides

No INFIRISK guide on this yet.

Fire resistance by height of the top storey
Over 11 mREI 60
Over 18 mREI 90
Over 30 mREI 120
Over 50 mREI 120
Show in the 3D model

Fire scenarios, step by step

Each is an illustrative order of events, not a fire engineering model, and keeps to no timetable. Each plays step by step in the model above, from its tile or the Fire button.

A flat on floor 6: The smoke alarm in the flat goes off

A flat on floor 6

A kitchen fire in flat 6.02: the flat's own alarm, the self-closing door, the smoke vents, one sprinkler head, staying put, and the fire service arriving.

20 steps. Shown at Over 18 m, Over 30 m, Over 50 m.

The Bookshop: The sprinkler head in the store room opens

The Bookshop

A fire in the Bookshop's store room: its own detector and alarm, staff and customers leaving by both exits, a sprinkler head, the fire service taking a hose in, and the floor that keeps the fire out of the flats above.

10 steps. Shown at Over 11 m, Over 18 m, Over 30 m, Over 50 m.

The refuse store: A fire starts in a bin

The refuse store

A fire in a bin: a sprinkler head, the fire-resisting walls round the store, why it opens only to the open air and keeps its door away from the ways out, and the fire service putting it out from the doorway.

9 steps. Shown at Over 11 m, Over 18 m, Over 30 m, Over 50 m.

The basement switch room: A fire starts in the switch room

The basement switch room

A fire in the electrical switch room: a place of special fire hazard, with sprinklers, its own fire-resisting walls and smoke outlet, the lobby that keeps Stair A clear, and the fire service working from a bridgehead above it.

14 steps. Shown at Over 11 m, Over 18 m, Over 30 m, Over 50 m.

Ongoing duties once people live here

Fire safety does not stop when the building is finished. These are the duties the law puts on whoever runs this building once people live and work in it: what must be done, by whom, when, and the law it comes from. Some apply only from a certain height; each says where it applies in this building.

  1. A fire risk assessment, kept up to date

    Who
    The responsible person for the common parts, and each shop’s own responsible person for the shop
    What
    Make a suitable and sufficient assessment of the fire risks to the people in and around the premises, record it, and review it regularly to keep it up to date.
    When
    From the day the premises are in use, at every height. Review it whenever there is reason to think it is no longer valid, or after a significant change to the premises or how they are run.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3) and (6)The responsible person must make a suitable and sufficient assessment of the risks to which relevant persons are exposed (article 9(1)), must review it regularly so as to keep it up to date, particularly if there is reason to suspect it is no longer valid or there has been a significant change (article 9(3)), and must make a record of the assessment or review as soon as practicable afterwards (article 9(6)).

    In the model: Entrance lobby and final exits, Common corridor, Shops on the ground floor

  2. Fire safety instructions for residents

    Who
    The responsible person
    What
    Display fire safety instructions in a conspicuous part of the building, in a form residents can be expected to understand: the evacuation strategy, how to report a fire to the fire and rescue service, and anything else residents must do once there is a fire. Give a copy to each new resident as soon as reasonably practicable after they move in, to every resident in each 12 month period counted from 23 January 2023, when the regulations came into force, and again after any material change.
    When
    Any building with two or more flats and common parts that residents would escape through: this block at every height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9In a building with two or more sets of domestic premises and common parts residents would evacuate through, the responsible person must display fire safety instructions in a conspicuous part of the building, covering the evacuation strategy, how to report a fire and what to do once a fire has occurred, and must give residents a copy when they move in, every 12 months and after any material change.

    In the model: Entrance lobby and final exits, Common corridor

  3. Fire door information for residents

    Who
    The responsible person
    What
    Tell residents that fire doors should be kept shut when not in use, that they and their guests should not tamper with the self-closing devices, and that they should report any fault or damage to a door at once. Give it to each new resident as soon as reasonably practicable after they move in, and to every resident in each 12 month period counted from 23 January 2023, when the regulations came into force.
    When
    Any building with two or more flats and common parts that residents would escape through: this block at every height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(1) to (3)In a building with two or more sets of domestic premises and common parts residents would evacuate through, the responsible person must tell residents that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported at once: new residents when they move in, and all residents every 12 months.

    In the model: Flat entrance doors

  4. Fire door checks

    Who
    The responsible person
    What
    Check the fire doors in the communal areas at least every 3 months. Use best endeavours to check every flat entrance door at least every 12 months, and keep a record of the steps taken, including the attempts made where a resident did not give access. Every check includes making sure the self-closing device works.
    When
    Two or more flats and a top storey above 11 m, measured as for regulation 3: this block at every height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.

    In the model: Flat entrance doors, Firefighting stair (Stair A), Second staircase (Stair B), Firefighting lobby

  5. Smoke alarms in rented flats

    Who
    The landlord of each rented flat
    What
    Make sure there is a smoke alarm on each storey of the flat that has a room used as living accommodation, and, only where a fixed combustion appliance other than a gas cooker is in a room used as living accommodation (which includes a hall, landing, bathroom or lavatory), a carbon monoxide alarm in that room. Check each alarm works on the day a new tenancy begins. When a tenant reports an alarm, it must be checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable. The flats here are heated from the communal boilers on the roof, so a carbon monoxide alarm is needed only where a fixed appliance that burns fuel is fitted in a flat.
    When
    Each flat let on a tenancy the regulations cover, which is most residential tenancies, private and social: at every height.
    In this building
    Applies here at every height.
    • Ongoing dutySmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)A relevant landlord of a specified tenancy must ensure that, while the premises are occupied under it, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, a carbon monoxide alarm is equipped in any such room containing a fixed combustion appliance other than a gas cooker, and the alarms are checked to be in proper working order on the day a new tenancy begins. When a tenant reports an alarm, it must be checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.

    In the model: Smoke alarms in the flats

  6. A secure information box

    Who
    The responsible person
    What
    Install and maintain a secure information box in or on the building, readily accessible to the fire and rescue service and secure from unauthorised access. Keep in it the responsible person’s name, address and UK telephone number, the contacts of others who can let firefighters in, and the documents these regulations and the evacuation plans regulations require. Give the fire and rescue service the means to open it, and inspect it at least once a year.
    When
    A high-rise residential building: two or more flats, and at least 18 m to the top storey or at least seven storeys, not counting storeys below ground (regulation 3). This block from Over 18 m. Below that, ADB still recommends a box in a block over 11 m, as guidance.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3 and 4, with regulation 4(2)(b) as amended by SI 2025/797The responsible person for a high-rise residential building must install and maintain a secure information box, readily accessible to the fire and rescue authority, able to hold the documents these Regulations and, since 6 April 2026, the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 require, and reasonably secure; must keep their own name, UK address and telephone number and other key holders’ details in it; must give the fire and rescue authority the means to access it; and must inspect it at least annually.

    In the model: Secure information box

  7. A record of the external walls

    Who
    The responsible person
    What
    Prepare a record of the design of the external walls and the materials they are built from, with the level of risk they give rise to, as the fire risk assessment found it, and any steps taken to reduce it. Revise it after any significant change to the walls, and send it to the fire and rescue service electronically.
    When
    A high-rise residential building: two or more flats, and at least 18 m to the top storey or at least seven storeys, not counting storeys below ground (regulation 3). This block from Over 18 m.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3, 5 and 11The responsible person for a high-rise residential building must prepare a record of the design of its external walls, including the materials, and of the level of risk the article 9 risk assessment identifies from them with any mitigating steps; must revise it after any significant change to the walls; and must provide it to the local fire and rescue authority by electronic means.

    In the model: External wall build-up

  8. Floor plans and a building plan

    Who
    The responsible person
    What
    Prepare plans of the floors that show every lift, whether each is a lift for firefighters or an evacuation lift, and the key fire-fighting equipment, and a single-page building plan showing, among other things, access for fire engines, the fire main inlets, the sprinkler shut-off controls, the smoke control and evacuation alert controls, the firefighting shaft and the main stairs. Put hard copies in the secure information box, send them to the fire and rescue service electronically, and update them as soon as reasonably practicable after any change.
    When
    A high-rise residential building: two or more flats, and at least 18 m to the top storey or at least seven storeys, not counting storeys below ground (regulation 3). This block from Over 18 m.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3, 6 and 11The responsible person for a high-rise residential building must prepare floor plans identifying all lifts, whether each is for firefighters or for evacuation, and the key fire-fighting equipment, and a single-page building plan of the matters regulation 6(4) lists; must place hard copies in the secure information box; must update them as soon as reasonably practicable after a change; and must provide them to the local fire and rescue authority by electronic means.

    In the model: Secure information box, Firefighting lift, Dry riser outlet, Smoke shafts and vents, Evacuation alert control panel

  9. Monthly checks of the lift and the fire-fighting equipment

    Who
    The responsible person
    What
    Check every month that the firefighters’ lift and the essential fire-fighting equipment are in efficient working order and good repair: the fire main with its inlets and outlets, the smoke control, the sprinklers, the detectors that start the smoke control, and the evacuation alert system. Put right any fault found. A fault that cannot be put right within 24 hours is reported to the fire and rescue service electronically, and reported again when it is fixed. Keep a record of the checks that residents can see.
    When
    A high-rise residential building: two or more flats, and at least 18 m to the top storey or at least seven storeys, not counting storeys below ground (regulation 3). This block from Over 18 m.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3 and 7The responsible person for a high-rise residential building must undertake monthly routine checks of lifts for use by firefighters, evacuation lifts and essential fire-fighting equipment; must take steps to rectify any fault, reporting it to the local fire and rescue authority by electronic means if it cannot be rectified within 24 hours, and again when it is; and must record the checks and make the record accessible to residents.

    In the model: Firefighting lift, Dry riser outlet, Smoke shafts and vents, Sprinklers in the flats, Category 4, Evacuation alert control panel

  10. Floor and flat signs

    Who
    The responsible person
    What
    Keep clear floor identification and flat identification signs, designed and placed as ADB Volume 1 describes, on every landing of the stairs and in the lift lobbies, readable in low light or by torch.
    When
    A high-rise residential building: two or more flats, and at least 18 m to the top storey or at least seven storeys, not counting storeys below ground (regulation 3). This block from Over 18 m. Below that, ADB still recommends the signs in a block over 11 m, as guidance.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3 and 8The responsible person for a high-rise residential building must ensure it contains clear markings of floor identification and identification of domestic premises, designed and located in accordance with ADB Volume 1, on each landing within the stairways and in the lift lobbies, visible in low level lighting or by torch.

    In the model: Floor and flat signs

  11. Residents who may need help to escape

    Who
    The responsible person
    What
    Use reasonable endeavours to identify residents whose ability to get out unaided in a fire is compromised by an impairment or condition, and offer each a person-centred fire risk assessment, carrying it out if they ask. Put in place the measures that are reasonable and proportionate, agree an emergency evacuation statement with the resident where possible and give them a copy, and review it all at least every 12 months, and sooner if it may need changing or the resident reasonably asks. With the resident’s explicit consent, tell the fire and rescue service their flat and floor, the help they may need, and whether they have a statement.
    When
    A building with two or more flats that is at least 18 m to the top storey, or has at least seven storeys, or is over 11 m and evacuates everyone at once. This block from Over 18 m; below that its residents stay put, so these regulations do not apply.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 3 to 10In a building with two or more sets of domestic premises that is at least 18 m high, has at least seven storeys, or is over 11 m with a simultaneous evacuation strategy, the responsible person must use reasonable endeavours to identify residents whose ability to evacuate unaided is compromised by a cognitive or physical impairment or condition; offer, and on request carry out, a person-centred fire risk assessment; implement reasonable and proportionate mitigating measures; try to agree and record an emergency evacuation statement; review them at least every 12 months; and, with explicit consent, give the fire and rescue authority the resident’s flat, floor, the help they may need and whether they have a statement. In force from 6 April 2026.

    In the model: Firefighting lift

  12. A building emergency evacuation plan

    Who
    The responsible person
    What
    Prepare an evacuation plan for the building: the residents’ instructions on the evacuation strategy, whether any residents need help to escape, and any other arrangements. Give a copy to the fire and rescue service and put one in the secure information box. Review it at least every 12 months and whenever it may need changing, and send any amended copy on.
    When
    A building with two or more flats that is at least 18 m to the top storey, or has at least seven storeys, or is over 11 m and evacuates everyone at once. This block from Over 18 m; below that its residents stay put, so these regulations do not apply.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 3 and 13The responsible person for a specified residential building must prepare a building emergency evacuation plan, including the evacuation strategy instructions, whether there are relevant residents and any other evacuation arrangements; must provide it to the local fire and rescue authority and place it in the secure information box; must review it at least every 12 months and when it may need amending; and must provide any amended plan.

    In the model: Secure information box, Evacuation alert control panel

  13. Registration and building safety risks

    Who
    The principal accountable person for registration and the safety case report, and each accountable person for assessing the risks and taking steps to manage them in the part of the building they are responsible for
    What
    The principal accountable person must have the building registered with the Building Safety Regulator: it is an offence for it to be occupied while not registered (s.77). Each accountable person must assess the building safety risks as soon as reasonably practicable after it is occupied, at regular intervals, whenever there is reason to suspect the current assessment is no longer valid, and when the regulator directs (s.83(2)), and take all reasonable steps, promptly, to stop those risks happening and to reduce how severe an incident would be. The principal accountable person prepares a safety case report from those assessments and steps, and revises it when, after a further assessment or further steps, they consider that necessary or appropriate (s.85(2)).
    When
    A higher-risk building: in England, at least 18 m high or at least seven storeys, with at least two residential units (section 65(1)). This block from Over 18 m.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyBuilding Safety Act 2022, Sections 65, 77, 83, 84 and 85A higher-risk building is a building in England at least 18 m in height or with at least 7 storeys, containing at least 2 residential units (section 65(1)). Its principal accountable person commits an offence if it is occupied but not registered (section 77). An accountable person must assess the building safety risks as soon as reasonably practicable after it is occupied, at regular intervals, whenever there is reason to suspect the current assessment is no longer valid, and when the regulator directs (section 83(2)), and must take all reasonable steps, promptly, to prevent a building safety risk materialising and to reduce the severity of any incident (section 84). The principal accountable person must prepare a safety case report and revise it when, after a further assessment or further steps, they consider that necessary or appropriate (section 85(2)).
    • Ongoing dutyHigher-Risk Buildings (Management of Safety Risks etc) Regulations 2023, Regulations 4 and 5Regulation 4 sets out the principles that the measures taken under section 84 must follow. Regulation 5 sets out what a safety case report must contain and requires it to be kept electronically.
    • Ongoing dutyHigher-Risk Buildings (Descriptions and Supplementary Provisions) Regulations 2023, Regulations 5, 6 and 8These regulations set out how the height and the number of storeys of a building are measured, and which buildings are excluded from being higher-risk buildings.

    In the model: External wall build-up, Compartment walls, Firefighting stair (Stair A), Second staircase (Stair B)

  14. Occurrence reporting and residents’ engagement

    Who
    The principal accountable person, and each accountable person for the part of the building they are responsible for
    What
    Report each safety occurrence to the Building Safety Regulator: a notice as soon as reasonably practicable and a full report within 10 days of it coming to your attention, in the way the regulator specifies (s.87(1); SI 2023/907 reg 6). The principal accountable person must establish and operate an effective mandatory occurrence reporting system, open to residents and users, so that occurrences reach the accountable persons (s.87(5)). Prepare a residents’ engagement strategy for promoting the participation of residents aged 16 or over and flat owners in building safety decisions (s.91(1)(a), (7)); review it at least every two years and after an occurrence report or significant material alterations, and consult residents and owners on it when first prepared and after each revision (SI 2023/907 reg 10).
    When
    A higher-risk building: in England, at least 18 m high or at least seven storeys, with at least two residential units (section 65(1)). This block from Over 18 m.
    In this building
    Applies here at: Over 18 m, Over 30 m, Over 50 m.
    • Ongoing dutyBuilding Safety Act 2022, Sections 87 and 91An accountable person must give the regulator prescribed information about building safety risks in prescribed circumstances, and the principal accountable person must establish and operate an effective mandatory occurrence reporting system (section 87). The principal accountable person must prepare a residents’ engagement strategy, review it at prescribed times and act in accordance with it, and each accountable person must give a copy to residents aged 16 or over and to the owners of the flats (section 91).
    • Ongoing dutyHigher-Risk Buildings (Management of Safety Risks etc) Regulations 2023, Regulation 6An accountable person reports each safety occurrence to the regulator: a notice as soon as reasonably practicable and a full report within 10 days of it coming to their attention, in the way the regulator specifies.
    • Ongoing dutyHigher-Risk Buildings (Management of Safety Risks etc) Regulations 2023, Regulation 10The residents’ engagement strategy is reviewed at least every two years and after an occurrence report or significant material alterations, and residents and owners are consulted on it when it is first prepared and after each revision.

    In the model: Common corridor, Entrance lobby and final exits

Guides behind this model

Read more on the topics this building shows.

See all 13 guides linked from this model

What this model assumes

  • Design basis: Approved Document B Volume 1, 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments. Where this model also follows a recommendation of BS 9991:2024, it says so and names the clause; it is not a complete BS 9991 design.
  • Top storey 34.5 m above ground level.
  • Sprinklers throughout the building: in every flat, in both shops, in the basement’s rooms and in the refuse and cycle stores. The fire-sterile common parts (stairs, corridors and landings) have none, as the note to ADB Volume 1 para 7.4 allows. BS 9991 clause 17 recommends sprinklers in those common parts as well, so a design to BS 9991 would add them.
  • Each storey is about 416 m2, under the 900 m2 at which ADB Volume 1 para 15.5 asks for a second firefighting shaft.
  • Hose laying distance is within 60 m of the fire main outlet in the firefighting shaft (ADB Volume 1 para 15.7).
  • Fire service vehicle access level is ground level all round: the site is flat.
  • One sprinklered basement storey under the west half of the building, its floor 3.5 m below ground, holding the plant.
  • From 18 m Stair A, and with it its firefighting shaft, carries on down to the basement. This model reads ADB Volume 1 Diagram 15.1 note 2 cautiously: a shaft that also serves plant no longer serves only flats, so its smoke control would be designed to BS 9999 (clause 27.1), which vents the lobby as well as the stair. Below 30 m the lobby’s vent in its outside wall, an openable louvred vent, is the kind BS 9999 accepts. Its louvres are 2.9 m² on their face; this model illustratively assumes a free-area ratio of 55 per cent (plain weather louvres are typically 40 to 60 per cent), so about 1.6 m² of free area, above the 1.5 m² asked for, and an aerodynamic free area of at least 1.0 m², also assumed (BS 9999 Table 21 item 5). From 30 m this model does not show the smoke control BS 9999:2017 asks for in the firefighting lobby. BS 9999 accepts an outside-wall lobby vent only where the top floor is under 30 m; above that the lobby needs an automatic vent into a smoke shaft of at least 3 m², a pressure differential system, or a mechanical system shown to do as well. The corridor smoke shafts outside the lobby door do not vent the lobby. The basement’s firefighting lobby has no vent either (see the basement lobby).
  • From 30 m the corridor’s two smoke shafts are mechanical, as BS 9991 clause 20.2.4 asks, although ADB Volume 1 para 3.55 would accept natural shafts at any height. Their fans, their control panel and the air paths described are this model’s own; a real design sets them from a computer model of the smoke flow.

Every reference was checked on 11 November 2026 against the editions in force. Approved Document B is the 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments (the 2026 amendments are in force from 30 September 2026). British Standards are the current editions on that date, among them BS 5839-1:2025, BS 5266-1:2025, BS EN 12845:2015+A2:2026, and BS EN 12101-2:2017, BS EN 12101-3:2015, BS EN 12101-8:2011, BS EN 12101-10:2005 and BS EN 12101-13:2022. Approved Document K is the 2013 edition. Where ADB names an older edition of a standard, the reference says so.

Technical review by INFIRISK editorial: 14 November 2026 · Next review: 14 February 2027