INFIRISK 3D buildings · 1(a) Residential: block of flats

Low-rise block of flats

A new four-storey block of flats round a single protected stair, with every flat fitted out and two pitched roofs. Step through each floor, follow the fire service hose from the dry riser, and see what a block whose top storey is under 11 m does without.

This building is illustrative. It is drawn to show how the guidance fits together, and it is not a fire strategy or a design for any real building. For your own building, speak to a competent fire engineer or fire risk assessor.

Every part of the building

The roof

Roof space over the flats

  • Compartmentation
Show in the 3D model

In a block built now, where a roof space runs over more than one flat, the walls between the flats below are carried up through it:

  • to the underside of the roof covering
  • fire-stopped where they meet it
  • carried across any eaves

So the roof space over one flat is divided from the next.

  • A line of compartment walls is not completed by fitting cavity barriers above them.

Here the top floor’s ceiling is the concrete roof slab, and each of the two pitched roofs covers a roof space over two flats, one north and one south.

  • On the line of the wall between those two flats a wall, as thick as that wall, is carried up through the roof space to the underside of the tiles, so the roof space over each flat is divided from the next.
  • Under the east roof it runs on across the roof space over the east lobby too, standing on the lobby’s concrete ceiling, so the division is unbroken from eaves to eaves.
  • The lobby’s own walls, the two end walls and the east wall that stand between it and the flats around it, are carried up under the east roof in the same way, so the roof space over the lobby is closed off from the roof spaces over those flats (the walls between each flat and a lobby are compartment walls too, paras 7.11 and 7.15).
  • The model draws no hatch into any roof space.
In existing buildings

In old blocks of flats the walls between flats may not go up through the roof void, letting a fire spread across several flats.

  • Problems arise in modern low-rise pitched-roof buildings too: fire spreading through the roof voids over a modern sheltered housing scheme has led to at least one death.
  • So an assessor tries to look into roof voids even in a Type 1 assessment, sampling them, and records it when that was not practicable (BS 9792 15.7 b)).
  • Fires have been known to spread across the top of blocks through the roof voids (LGA guide 18.4).

REI 60The walls carried up through the roof space continue the compartment walls between the flats, and between the east lobby and the flats, REI 60, to the underside of the roof covering (paras 7.11 and 7.15).

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, paras 7.11 and 7.15, with para 5.11Compartment walls in a top storey beneath a roof should be continued through the roof space (para 7.11). Where a compartment wall meets the roof, the provisions are those for houses (para 7.15): the wall should meet the underside of the roof covering or deck, with fire-stopping to keep its fire resistance continuous, and be continued across any eaves (para 5.11).
  • GuidanceADB Vol 1, para 8.4It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment walls should extend to the underside of the floor or roof above.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentary (opens in a new tab)A Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary b) (opens in a new tab)Fire can spread through a roof void, whether it starts there or reaches it from a flat below. In old blocks of flats the walls between flats might not extend through the roof void, as building regulations would now require, letting a fire spread across several flats; problems can also arise in modern low-rise pitched-roof buildings such as sheltered housing, and fire spreading within the roof voids over a modern sheltered scheme has led to at least one death. So the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and makes clear in the assessment when access was not practicable.Why it applies here: This block has two pitched roofs, and each roof space runs over two of the top floor flats.
  • GuidanceFire safety in purpose-built blocks of flats, paras 18.4 and 19.2Fires have been known to spread beyond the flat of origin to involve other flats, or across the top of blocks through the roof voids, and total evacuation has then sometimes been necessary; such fires are rare, and usually the fault of failings in the construction. A stay put policy does not mean that residents not directly involved who wish to leave should be prevented from doing so.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The roof spaces, on at least a sample: whether the walls between the flats run up to the underside of the roof covering, and the fire stopping where they meet it

    Benchmark: BS 9792 clause 5 and 15.7 b): where a building has a pitched roof, even a Type 1 assessment tries to include the roof voids, sampling them, and records it if access was not practicable.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentaryA Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary b)Fire can spread through a roof void, whether it starts there or reaches it from a flat below. In old blocks of flats the walls between flats might not extend through the roof void, as building regulations would now require, letting a fire spread across several flats; problems can also arise in modern low-rise pitched-roof buildings such as sheltered housing, and fire spreading within the roof voids over a modern sheltered scheme has led to at least one death. So the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and makes clear in the assessment when access was not practicable.

    A defect the source namesIn old blocks of flats the walls between flats might not extend through the roof void, which can let a fire spread across several flats.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary b)Fire can spread through a roof void, whether it starts there or reaches it from a flat below. In old blocks of flats the walls between flats might not extend through the roof void, as building regulations would now require, letting a fire spread across several flats; problems can also arise in modern low-rise pitched-roof buildings such as sheltered housing, and fire spreading within the roof voids over a modern sheltered scheme has led to at least one death. So the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and makes clear in the assessment when access was not practicable.
  2. How far the walls between flats should go

    Benchmark: For a building built now: Approved Document B says compartment walls in a top storey beneath a roof should be continued through the roof space, meet the underside of the roof covering with fire-stopping and be carried across any eaves, and not be completed by cavity barriers above them (paras 7.11, 7.15, 5.11 and 8.4).

    • GuidanceADB Vol 1, paras 7.11 and 7.15, with para 5.11Compartment walls in a top storey beneath a roof should be continued through the roof space (para 7.11). Where a compartment wall meets the roof, the provisions are those for houses (para 7.15): the wall should meet the underside of the roof covering or deck, with fire-stopping to keep its fire resistance continuous, and be continued across any eaves (para 5.11).
    • GuidanceADB Vol 1, para 8.4It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment walls should extend to the underside of the floor or roof above.
Show in the 3D model

Fire service vent at the head of the stair

  • Smoke control
  • Firefighting
Show in the 3D model

One vent at the top of the stair, opened by the fire service with a switch at the fire service access level.

  • Opening it lets out smoke that has got into the stair while doors were open.
  • The other way of meeting the guidance is a high-level openable vent at every storey; either way each vent has a free area of at least 1 m2.
  • Where a block with no more than two flats a floor leaves out the lobby, it needs instead an automatic vent with a geometric free area of at least 1 m2 at the top of the stair, opened when smoke is detected at any storey in the stair.

It is a louvred vent on the flat roof between the two pitched roofs, over an opening above the stair.

  • Here smoke detectors on the ceiling of the stair at every storey open the vent automatically, and the switch just inside the entrance, on the ground floor where the crews arrive, lets the fire service open or close it.
  • The detectors are there only to open the vent: they sound no alarm.
  • That the block has no fire alarm across it is a separate matter, which follows from its stay put strategy: residents not directly affected by the fire are expected to stay in their flats unless the fire service tells them to leave.
In existing buildings

In an existing block, an assessment works out how the vent is meant to work, and checks that it is set to open automatically and is tested.

  • Testing is usually monthly from its controls, with its detectors and controls at least once a year (BS 9792 15.11; LGA guide 81.8 and 81.9).
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 3.32(e)For the fire and rescue service, either a high-level openable vent with a free area of at least 1 m2 at each storey, or a single openable vent with a free area of at least 1 m2 at the head of the stair, operable remotely at the fire and rescue service access level.Why it applies here: For a block with lobbies like this one, the guidance would accept a vent opened only from the fire service switch (para 3.32(e)(ii)). This block also opens it on smoke detection in the stair, as para 3.57 asks of single stair buildings with smoke vents, so smoke that gets into the stair is let out before the crews arrive.
  • GuidanceADB Vol 1, Diagram 3.9 note 3Where, in a small single stair building with no more than two flats per storey, the lobby between the common stair and the flat is left out, an automatic opening vent with a geometric free area of at least 1 m2 is needed at the top of the stair, opened on detection of smoke at any storey in the stair.
  • Ongoing dutyFire Safety Order 2005, Article 38Where necessary in order to safeguard the safety of fire-fighters, the facilities and equipment provided for them, such as a vent for the fire service and its switch, are subject to a suitable system of maintenance and maintained in an efficient state, in efficient working order and in good repair.
  • GuidanceADB Vol 1, para 3.57In single stair buildings, smoke vents on the storey where the fire is initiated, and the vent at the head of the stair, should be activated by smoke detectors in the common parts.
  • StandardBS 9991, clause 16.1 (opens in a new tab)Where detection outside the flats is needed to start smoke control, it is at least a Category L5 system to BS 5839-1. Detection in other common areas, such as lounges, depends on their extent and use, the fire risk and how the building is managed.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and the detectors in this stair start the stair vent, and nothing else.
  • GuidanceFire safety in purpose-built blocks of flats, para 19.1Under a stay put policy, the people in the flat where a fire starts get out and call the fire and rescue service, and so does anyone in the common parts when a fire starts there; all other residents not directly affected by the fire would be expected to stay in their flat unless the fire and rescue service tells them to leave.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.11, commentary, and 15.11.1 to 15.11.5 (opens in a new tab)Smoke control is normally essential in a block of flats. The assessor understands how it is meant to work, records its equipment, its links to the detection, its controls and any override, and determines whether it is set to open automatically, with no faults, and is regularly tested and maintained by a competent provider; concerns are referred to a competent person.Why it applies here: The vent at the head of this block’s stair, opened by smoke detectors in the stair and by the fire service’s switch, is its smoke control.
  • GuidanceFire safety in purpose-built blocks of flats, paras 81.5, 81.8, 81.9 and 81.24Emergency lighting that does not test itself has a monthly functional test and a full duration test once a year. Automatic or electrically operated smoke vents are tested monthly from their controls, and the detectors and controls that open them at least once a year. Fire mains are inspected every six months and tested every twelve.

What a fire risk assessor checks

  1. How the vent is meant to work; whether it is set to open automatically, with no faults; and its test records

    Benchmark: BS 9792 15.11: the assessor understands how the smoke control is meant to work, records its equipment, controls and override, and determines whether it is set to open automatically and is regularly tested and maintained by a competent provider. The LGA guide: an automatic vent tested monthly from its controls, and its detectors and controls at least once a year.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.11, commentary, and 15.11.1 to 15.11.5Smoke control is normally essential in a block of flats. The assessor understands how it is meant to work, records its equipment, its links to the detection, its controls and any override, and determines whether it is set to open automatically, with no faults, and is regularly tested and maintained by a competent provider; concerns are referred to a competent person.
    • GuidanceFire safety in purpose-built blocks of flats, paras 81.5, 81.8, 81.9 and 81.24Emergency lighting that does not test itself has a monthly functional test and a full duration test once a year. Automatic or electrically operated smoke vents are tested monthly from their controls, and the detectors and controls that open them at least once a year. Fire mains are inspected every six months and tested every twelve.
Show in the 3D model

A typical floor

Protected stair

  • Means of escape
  • Compartmentation
Show in the 3D model

A small block of flats may be served by one stair if it meets every limit set for a small single stair building:

  • the top storey no more than 11 m up
  • no more than three storeys above the ground storey
  • no covered car park off the stair unless it is open sided
  • no offices, stores or other ancillary rooms opening straight off it (they need a ventilated protected lobby or corridor)
  • a vent for the fire service

The stair is a protected stairway, enclosed by fire-resisting walls and self-closing fire doors that keep smoke and fire out, so everyone above can get down and out.

It is used for nothing else, except a lift well or electricity meters.

Here the stair rises just east of the middle of the block in two flights a storey, each 1.2 m wide between the wall and the well.

  • The lift opens on to the stair’s own landing, inside the same enclosure, and a door each side of the landing leads to a lobby.
  • On the floors above, each of those doors opens into the stair, the way people escape. On the ground floor there is one door, opening out of the stair into the exit passageway. It stops at the top floor.
  • The lift is an electric traction lift without a machine room: its motor sits at the top of the lift well, inside the overrun on the roof. The model leaves the overrun’s roof off so the motor can be seen.
  • Nothing is stored in the stair: besides the stair it holds the lift and, at the top, the fixed ladder to the roof hatch; the electricity meters are in a locked cupboard off the exit passageway on the ground floor, by the entrance.
  • Where a block does have a lift machine room, the guidance puts it over the lift well where possible, and in a single stair building otherwise outside the protected stair (ADB para 3.108).
  • A hydraulic lift with all its plant and oil tank inside the well should not be used in a block of flats with a single stair (BS 9991:2024 41.2).
In existing buildings

In an existing block, an assessment checks that the stair and the lobbies are kept clear, with nothing stored in them that would burn.

  • Stay put rests on a fire in the common parts being unlikely and very limited (Fire Safety Order article 14(1); BS 9792 clause 13).

REI 60The stair is a protected shaft, built to resist fire for 60 minutes in the standard test, the Table B2 period for this block: its walls to the flats are REI 60 (Table B1 item 8(c)); between the stair and a lobby item 8(b) would allow REI 30; this model keeps REI 60. Its doors to the lobbies are E 30 Sa fire doors with self-closers: each is in the enclosure of the protected stairway, a protected shaft, and of the protected lobby that approaches it (Table C1 items 2(b), 4(a) and 5(a), each E 30 Sa).

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.32For some low rise buildings a single stair, protected as Diagram 3.9 shows, may be used where all of the following apply: the top storey is a maximum of 11 m above ground level; no more than three storeys are above the ground storey; the stair does not connect to a covered car park unless it is open sided; the stair does not serve offices, stores or other ancillary accommodation, unless they are separated from it by a protected lobby or protected corridor (minimum REI 30) with at least 0.4 m2 of permanent ventilation, or protected from smoke by a mechanical smoke control system; and a vent is provided for the fire and rescue service (para 3.32(e)).
  • GuidanceADB Vol 1, para 3.65Every common stair should be a protected stairway. Where the protected stairway passes from one compartment to another, it should be within a protected shaft.
  • GuidanceADB Vol 1, Table B1 item 8A protected shaft other than a firefighting shaft: item 8(b), REI 30 for the parts between the shaft and a protected lobby or corridor described in Diagram 7.2; item 8(c), the period in Table B2 for any other part, each side separately.
  • GuidanceADB Vol 1, para 3.81A protected stairway should not be used for anything else, except a lift well or electricity meters.
  • GuidanceADB Vol 1, para 3.102Lift wells should either be sited within the enclosures of a protected stairway or evacuation shaft, or be enclosed with fire resisting construction (minimum REI 30) when in a position that might prejudice the means of escape.
  • GuidanceADB Vol 1, Table C1 item 2bA door in a compartment wall enclosing a protected shaft that forms a stairway wholly or partly above the adjoining ground, in a building used for flats: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, Table C1 item 4aA door forming part of the enclosure of a protected stairway: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, para C5All fire doorsets, including those to flat entrances, should have a self-closing device, except fire doorsets to cupboards, to service ducts normally locked shut, and within flats.
  • GuidanceADB Vol 1, Table B2A block of flats without a sprinkler system, with its top floor more than 5 m and up to 11 m above ground: 60 minutes for the elements of structure in its ground and upper storeys. With the top floor up to 5 m it would be 30 minutes.
  • GuidanceADB Vol 1, paras 3.97 to 3.99The door of any doorway or exit should be hung to open in the direction of escape whenever reasonably practicable. It should always be hung to open in the direction of escape if more than 60 people might be expected to use it during a fire. All doors on escape routes should be hung to meet both of the following conditions. a. Open by a minimum of 90 degrees. b. Open with a swing that complies with both of the following. i. Is clear of any change of floor level, other than a threshold or single step on the line of the doorway. ii. Does not reduce the effective width of any escape route across a landing. Any door opening towards a corridor or a stair should be recessed to prevent its swing encroaching on the effective width.Why it applies here: Each stair door opens into the stair, the way people escape, as Diagram 3.9 draws the door between a lobby and the stair. Para 3.97 asks for that wherever it is reasonably practicable; its more than 60 people is the point from which a door should always open that way, not leave to do otherwise below it. Here it is practicable, and this is the model’s own design judgement, measured on its own landing, not a rule for every small block. The landing is 2.6 m square. Each door is hung on the jamb nearer the flights, so the 1.0 m leaf held open stands 0.95 m back from the head of the flights and 0.1 m short of the lift’s 1.5 m landing, and leaves 1.7 m between its edge and the far wall, more than the 1.2 m flight: its swing does not narrow the way across the landing to the flights (para 3.98(b)(ii)), and it stays on the landing, clear of the flights, so it needs no recess (para 3.99). The door shuts itself, so the leaf stands open only while someone goes through.
  • GuidanceADB Vol 1, para 3.108Lift machine rooms should be sited over the lift well where possible. Where a building, or part of a building, with only one stairway makes this impractical, the lift machine room should be sited outside the protected stairway.
  • StandardBS 9991, clause 41.2 (opens in a new tab)A hydraulic lift designed without a machine room, with all of its plant and its hydraulic oil tank inside the lift well, should not be used in a block of flats with a single stair.Why it applies here: This block has a single stair, so its lift is an electric traction lift whose motor sits at the top of the lift well, not a hydraulic one with its plant and oil tank in the well.
  • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 and 13.3 (opens in a new tab)Every assessment covers, among other sources of fire, malicious ignition, and situations such as poor housekeeping, poor waste management and battery-powered mobility scooters, e-scooters and e-bikes in the common areas or escape routes. Combustible materials left in the common parts of a block against the policy for them can lead to a fire that undermines the stay put strategy, which rests on fire being unlikely in the common parts and very limited if it occurs.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).

What a fire risk assessor checks

  1. What is kept on the stair, its landings and the lobbies: storage, furniture, bicycles, mobility scooters, anything that would burn or block the way

    Benchmark: The law: where necessary, the responsible person keeps the routes to the exits, and the exits themselves, clear at all times (Fire Safety Order article 14(1)). BS 9792 13 and 16: poor housekeeping and battery-powered vehicles in the common parts are fire hazards an assessment covers, and routine inspections check that nothing is stored on routes that should stay sterile.

    • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 and 13.3Every assessment covers, among other sources of fire, malicious ignition, and situations such as poor housekeeping, poor waste management and battery-powered mobility scooters, e-scooters and e-bikes in the common areas or escape routes. Combustible materials left in the common parts of a block against the policy for them can lead to a fire that undermines the stay put strategy, which rests on fire being unlikely in the common parts and very limited if it occurs.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 16, commentary g), j) and k), and 16.3Fire safety management is as important as the physical precautions. The assessment checks there are routine inspections, needing little specialist knowledge, that escape routes stay clear, self-closing fire doors work and nothing is stored on routes that should stay sterile, with defects reported and put right; that all fire protection is tested and maintained; and that records of inspection, testing and maintenance are kept, normally with a fire safety manual.

    A defect the source namesCombustible materials left in the common parts against the policy for them, which can lead to a fire there that undermines stay put.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 and 13.3Every assessment covers, among other sources of fire, malicious ignition, and situations such as poor housekeeping, poor waste management and battery-powered mobility scooters, e-scooters and e-bikes in the common areas or escape routes. Combustible materials left in the common parts of a block against the policy for them can lead to a fire that undermines the stay put strategy, which rests on fire being unlikely in the common parts and very limited if it occurs.
Show in the 3D model

Lobby between the stair and the flats

  • Means of escape
  • Smoke control
  • Compartmentation
Show in the 3D model

The flat doors on each floor open into a small lobby, and a fire door separates the lobby from the stair.

  • In this layout no flat door is more than 4.5 m from the stair door, measured across the lobby, or 7.5 m if the lobby has smoke control.
  • A longer lobby is designed as Diagram 3.7 shows instead.
  • So nobody walks far past a flat that is on fire.
  • A lobby laid out this way needs no smoke vent of its own, unlike the corridors and lobbies of other blocks.
  • The door into the stair has no security lock that could hold anyone up.

Here there is a lobby each side of the stair, running alongside it, each with two flat doors.

  • In the west lobby the two doors are staggered: one is in the side wall at the far end, the other in the end wall, so neither faces the other.
  • The east lobby is shorter, with a flat door in each end wall and the stair door in the side wall between them.
  • The furthest flat door is 3.1 m from its stair door; the Travel button measures the two in the west lobby.
  • On the ground floor there are no lobbies: every flat there has a front door of its own (see Entrance and final exit).

REI 60The walls between each lobby and the flats are compartment walls, REI 60 (Table B1 item 6a). The flat doors are E 30 Sa fire doors with self-closers (Table C1 item 2(a), and item 5(a) as part of the lobby’s enclosure), and so are the doors into the stair (items 2(b), 4(a) and 5(a)).

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, Diagram 3.9In a small single stair building the flats open off a lobby, separated from the stair by fire doorsets. The travel distance across the lobby is 4.5 m at most, or 7.5 m if smoke control is provided in the lobby; if it is more than 4.5 m, Diagram 3.7 applies (note 2). The door between the stair and the lobby should be free from security fastenings.
  • GuidanceADB Vol 1, Table 3.1 note 2The maximum travel distance from a flat entrance door to the storey exit, where escape is in one direction only, is 7.5 m; in a small single stair building that follows Diagram 3.9 it is reduced to 4.5 m.
  • GuidanceADB Vol 1, para 3.54Except in buildings that comply with Diagram 3.9, the corridor or lobby directly in front of each storey exit should have a smoke vent, as high as practicable, with its top edge at least as high as the top of the door to the stair.
  • GuidanceADB Vol 1, para 3.94In general, doors on escape routes should either have no lock, latch or bolt fastenings, or only simple fastenings that are easy to operate, operable from the side people escape from, without a key, and without working more than one mechanism.
  • GuidanceADB Vol 1, Table C1 item 5aA door forming part of the enclosure of a protected lobby approach to a stairway: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, para C5All fire doorsets, including those to flat entrances, should have a self-closing device, except fire doorsets to cupboards, to service ducts normally locked shut, and within flats.
Show in the 3D model

Flat entrance doors

  • Compartmentation
  • Means of escape
Show in the 3D model

Each flat door is a fire door that shuts itself.

  • It holds a fire and its smoke back inside the flat, away from the lobby, the only way to the stair, for the time it is rated for in the standard test.
  • A door that does not close fully does neither.
In existing buildings

In an existing block, a flat door that met the requirements when it was fitted may still be adequate, though an older one may have no intumescent strips or smoke seals. Whether that matters is a judgement of the risk, not in itself a reason to replace it (BS 9792 15.3; LGA guide 62.17).

  • Whatever else is done, each needs a self-closer that shuts it from any angle against its latch (LGA guide 62.19).

E 30 SaA door in a compartment wall between a flat and a space in common use (Table C1 item 2(a)), with a self-closer (para C5).

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, Table C1 item 2aDoor in a compartment wall separating a flat from a space in common use: E 30 Sa (FD 30 S).
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(1) to (3)In a building with two or more sets of domestic premises and common parts residents would evacuate through, the responsible person must tell residents that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported at once: new residents when they move in, and all residents every 12 months.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3 (opens in a new tab)Older flat entrance doors might have no intumescent strips, and so might not achieve 30 minutes of fire resistance, or no smoke seals; a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.Why it applies here: The flat entrance doors and the stair doors separate the flats from the common escape route.
  • GuidanceFire safety in purpose-built blocks of flats, paras 62.14, 62.17, 62.19 and 62.21A modern FD30S flat entrance door has intumescent strips and cold smoke seals along its sides and top, a self-closing device, and a protected letterbox, and is tested as a whole doorset. An older fire-resisting door that is a good fit in its frame and met the standard of its day may be accepted, upgraded or replaced; whichever is chosen, flat entrance doors and the doors protecting the common parts need positive action self-closing devices that close the door from any angle and overcome any latch.

What a fire risk assessor checks

  1. Flat entrance doors, on at least a sample (by common practice around one in ten, and at least two): the self-closer shuts the door fully from any angle against its latch; the leaf and frame, the intumescent strips and smoke seals, the fit in the frame and the letterbox

    Benchmark: BS 9792 15.3: the doors between the flats and the common escape route are among the most important things an assessment looks at, and it is essential that they are self-closing and give adequate fire resistance. The LGA guide, for existing purpose-built blocks: whatever else is done to a door, a positive action self-closing device that closes it from any angle and overcomes the latch.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary, and 15.3.4The doors between the dwellings and the communal escape routes are among the most important things an assessment looks at: it is essential that they are self-closing and give adequate fire resistance. The assessor tries to check around 10% of the flat entrance doors, with a minimum of two, by common practice, and every door in the protected lobbies and stairways, and the dutyholder needs arrangements for periodic routine checks of both. The dutyholder’s inspection and maintenance records help for doors the assessor cannot reach.
    • GuidanceFire safety in purpose-built blocks of flats, paras 62.14, 62.17, 62.19 and 62.21A modern FD30S flat entrance door has intumescent strips and cold smoke seals along its sides and top, a self-closing device, and a protected letterbox, and is tested as a whole doorset. An older fire-resisting door that is a good fit in its frame and met the standard of its day may be accepted, upgraded or replaced; whichever is chosen, flat entrance doors and the doors protecting the common parts need positive action self-closing devices that close the door from any angle and overcome any latch.

    A defect the source namesOlder doors may have no intumescent strips, and so may not resist fire for 30 minutes, or no smoke seals. Missing or ineffective self-closers, damaged doors or frames, locks removed without repair, poor fit from distortion, shrinkage or wear, unsuitable new door furniture, and doors replaced with ones that do not resist fire.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3Older flat entrance doors might have no intumescent strips, and so might not achieve 30 minutes of fire resistance, or no smoke seals; a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.
    • GuidanceFire safety in purpose-built blocks of flats, paras 82.3 to 82.5Good practice is to inspect timber fire-resisting doorsets every six months, flat entrance doors included where the lease gives access, for missing or ineffective self-closers, damaged doors or frames, locks removed without repair, poor fit from distortion, shrinkage or wear, unsuitable new door furniture, and doors replaced with ones that do not resist fire; defects reported are put right promptly, not left to the next inspection.
  2. An older door that does not meet today’s standard: whether it is still adequate

    Benchmark: BS 9792 15.3: a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk. The LGA guide: an older fire door that is a good fit in its frame and met the standard of its day may be accepted, upgraded or replaced.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3Older flat entrance doors might have no intumescent strips, and so might not achieve 30 minutes of fire resistance, or no smoke seals; a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.
    • GuidanceFire safety in purpose-built blocks of flats, paras 62.14, 62.17, 62.19 and 62.21A modern FD30S flat entrance door has intumescent strips and cold smoke seals along its sides and top, a self-closing device, and a protected letterbox, and is tested as a whole doorset. An older fire-resisting door that is a good fit in its frame and met the standard of its day may be accepted, upgraded or replaced; whichever is chosen, flat entrance doors and the doors protecting the common parts need positive action self-closing devices that close the door from any angle and overcome any latch.
  3. The responsible person’s own checks of the flat entrance doors, and their records

    Benchmark: The law, in this block: the Fire Safety Order reaches the doors between the flats and the common parts, and the responsible person, where necessary, keeps them maintained (articles 6(1A) and 17(1)). The regulation 10 checks, every 3 months in the common parts and every 12 at the flat entrances, start only above 11 m, which this block is not. BS 9792 15.3: the dutyholder needs arrangements for periodic routine checks. The LGA guide calls inspecting timber doorsets every six months good practice, flat entrance doors included where the lease gives access (para 82.4).

    • Ongoing dutyFire Safety Order 2005, Article 6(1A) and (1B)Where a building contains two or more sets of domestic premises, the things the Order applies to include the building’s structure and external walls and any common parts, and all doors between the domestic premises and the common parts. The external walls include doors or windows in them and anything attached to their exterior, including balconies.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary, and 15.3.4The doors between the dwellings and the communal escape routes are among the most important things an assessment looks at: it is essential that they are self-closing and give adequate fire resistance. The assessor tries to check around 10% of the flat entrance doors, with a minimum of two, by common practice, and every door in the protected lobbies and stairways, and the dutyholder needs arrangements for periodic routine checks of both. The dutyholder’s inspection and maintenance records help for doors the assessor cannot reach.
    • GuidanceFire safety in purpose-built blocks of flats, paras 82.3 to 82.5Good practice is to inspect timber fire-resisting doorsets every six months, flat entrance doors included where the lease gives access, for missing or ineffective self-closers, damaged doors or frames, locks removed without repair, poor fit from distortion, shrinkage or wear, unsuitable new door furniture, and doors replaced with ones that do not resist fire; defects reported are put right promptly, not left to the next inspection.
Show in the 3D model

Stair doors and fire door checks

  • Means of escape
  • Compartmentation
Show in the 3D model

Fire doors should be kept shut when not in use, so the doors between the stair and the lobbies, like the flat entrance doors, shut themselves.

  • Each is a whole doorset, tested as one: a modern one has intumescent strips and smoke seals along its sides and top, and a self-closing device that closes it from any angle and overcomes the latch.
  • For new building work, fire doors in the common parts are marked ‘Fire door keep shut’ on both sides; flat entrance doors are not.
  • In a block whose top storey is more than 11 m up, the law adds checks: the fire doors in the common parts at least every 3 months, and, with best endeavours, the flat entrance doors at least every 12 months.

Here there are two on each floor above the ground, one each side of the stair’s landing, and one on the ground floor, out of the stair into the exit passageway.

  • Each is marked ‘Fire door keep shut’ on both faces of its leaf, and the meter cupboard’s door ‘Fire door keep locked shut’ on the passageway side.
  • The top storey is 8.4 m above ground, not above 11 m, so the law’s 3-monthly and 12-monthly door checks do not apply to this block; the duty to keep its fire doors maintained does.
In existing buildings

In an existing block, an assessor checks every one of these doors, and the responsible person inspects them routinely:

  • that each shuts itself against its latch
  • the state of its leaf, frame, strips and seals (BS 9792 15.3)

The assessment also asks whether the signs on fire doors are needed and suitable (BS 9792 15.4).

E 30 SaEach stair door is in the enclosure of the protected stairway, a protected shaft, and of the protected lobby that approaches it (Table C1 items 2(b), 4(a) and 5(a)), with a self-closer (para C5).

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, Table C1 item 2bA door in a compartment wall enclosing a protected shaft that forms a stairway wholly or partly above the adjoining ground, in a building used for flats: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, Table C1 item 4aA door forming part of the enclosure of a protected stairway: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, Table C1 item 5aA door forming part of the enclosure of a protected lobby approach to a stairway: E 30 Sa (FD 30 S).
  • GuidanceADB Vol 1, para C5All fire doorsets, including those to flat entrances, should have a self-closing device, except fire doorsets to cupboards, to service ducts normally locked shut, and within flats.
  • GuidanceADB Vol 1, paras C11 and C12Fire doorsets should be marked on both sides with a fire safety sign to BS 5499-5: ‘Fire door keep shut’ for one kept closed when not in use, ‘Fire door keep locked shut’ for one kept locked, ‘Automatic fire door keep clear’ for one held open by an automatic release. Among others, doors to and within flats, and lift landing doors, are not required to be marked.
  • GuidanceFire safety in purpose-built blocks of flats, paras 62.14, 62.17, 62.19 and 62.21A modern FD30S flat entrance door has intumescent strips and cold smoke seals along its sides and top, a self-closing device, and a protected letterbox, and is tested as a whole doorset. An older fire-resisting door that is a good fit in its frame and met the standard of its day may be accepted, upgraded or replaced; whichever is chosen, flat entrance doors and the doors protecting the common parts need positive action self-closing devices that close the door from any angle and overcome any latch.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.Why it applies here: This block’s top storey is 8.4 m above ground, so it is not above 11 m and these checks are not required here.
  • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary, and 15.3.4 (opens in a new tab)The doors between the dwellings and the communal escape routes are among the most important things an assessment looks at: it is essential that they are self-closing and give adequate fire resistance. The assessor tries to check around 10% of the flat entrance doors, with a minimum of two, by common practice, and every door in the protected lobbies and stairways, and the dutyholder needs arrangements for periodic routine checks of both. The dutyholder’s inspection and maintenance records help for doors the assessor cannot reach.Why it applies here: The flat entrance doors and the stair doors separate the flats from the common escape route.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.4, commentary b) and f), 15.4.1 and its NOTE, and 15.4.2 (opens in a new tab)The assessment determines whether fire safety signs and notices are needed, and whether those provided are adequate: among them signs on fire doors saying they are to be kept shut or kept locked shut, and fire action notices. No signs may be needed, but there may be a need for fire action notices, and the suitability of any existing signs and notices is determined.Why it applies here: This block has a fire action notice in its exit passageway and fire doors to its stair and its meter cupboard.

What a fire risk assessor checks

  1. Every stair door: it shuts itself fully against its latch, and the leaf and frame, intumescent strips, smoke seals and fit are sound

    Benchmark: BS 9792 15.3: the assessor checks every fire door in the protected lobbies and stairways, and the dutyholder inspects them routinely; 15.4: whether the signs on fire doors are needed and suitable. For a building built now: Approved Document B says these doors should be E 30 Sa, self-closing, and marked ‘Fire door keep shut’ on both sides (Table C1, paras C5 and C11).

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary, and 15.3.4The doors between the dwellings and the communal escape routes are among the most important things an assessment looks at: it is essential that they are self-closing and give adequate fire resistance. The assessor tries to check around 10% of the flat entrance doors, with a minimum of two, by common practice, and every door in the protected lobbies and stairways, and the dutyholder needs arrangements for periodic routine checks of both. The dutyholder’s inspection and maintenance records help for doors the assessor cannot reach.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.4, commentary b) and f), 15.4.1 and its NOTE, and 15.4.2The assessment determines whether fire safety signs and notices are needed, and whether those provided are adequate: among them signs on fire doors saying they are to be kept shut or kept locked shut, and fire action notices. No signs may be needed, but there may be a need for fire action notices, and the suitability of any existing signs and notices is determined.
    • GuidanceADB Vol 1, Table C1 item 4aA door forming part of the enclosure of a protected stairway: E 30 Sa (FD 30 S).
    • GuidanceADB Vol 1, para C5All fire doorsets, including those to flat entrances, should have a self-closing device, except fire doorsets to cupboards, to service ducts normally locked shut, and within flats.
    • GuidanceADB Vol 1, paras C11 and C12Fire doorsets should be marked on both sides with a fire safety sign to BS 5499-5: ‘Fire door keep shut’ for one kept closed when not in use, ‘Fire door keep locked shut’ for one kept locked, ‘Automatic fire door keep clear’ for one held open by an automatic release. Among others, doors to and within flats, and lift landing doors, are not required to be marked.

    A defect the source namesMissing or ineffective self-closers, damaged doors or frames, poor fit from distortion, shrinkage or wear, and doors replaced with ones that do not resist fire.

    • GuidanceFire safety in purpose-built blocks of flats, paras 82.3 to 82.5Good practice is to inspect timber fire-resisting doorsets every six months, flat entrance doors included where the lease gives access, for missing or ineffective self-closers, damaged doors or frames, locks removed without repair, poor fit from distortion, shrinkage or wear, unsuitable new door furniture, and doors replaced with ones that do not resist fire; defects reported are put right promptly, not left to the next inspection.
  2. The responsible person’s routine checks of the stair doors, and their records

    Benchmark: The law, in this block: the responsible person keeps the doors maintained in efficient working order and good repair (Fire Safety Order article 17); the 3-monthly checks of regulation 10 start only above 11 m. BS 9792 16: routine inspections, needing little specialist knowledge, check that self-closing fire doors work, with defects reported and put right.

    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 16, commentary g), j) and k), and 16.3Fire safety management is as important as the physical precautions. The assessment checks there are routine inspections, needing little specialist knowledge, that escape routes stay clear, self-closing fire doors work and nothing is stored on routes that should stay sterile, with defects reported and put right; that all fire protection is tested and maintained; and that records of inspection, testing and maintenance are kept, normally with a fire safety manual.
Show in the 3D model

Lift, and residents who need help to escape

  • Means of escape
Show in the 3D model

An evacuation lift has safety measures an ordinary passenger lift does not.

  • For new building work, where one is provided it stands in an evacuation shaft with a protected stair and a lobby where people can wait for it, which no flat, store or electrical room opens into.
  • For new design, BS 9991 recommends that a building with a passenger lift to its upper floors also has a means of using lifts for escape.
  • Residents who need help to escape live in ordinary blocks of flats too, and a person-centred fire risk assessment or an evacuation plan can be made with anyone who might need help to leave.

Here the lift is an ordinary passenger lift, an electric traction lift whose motor sits at the top of its well, opening on to the stair’s own landing.

  • It is not an evacuation lift: the block follows Approved Document B, which does not ask for one here.
  • Its strategy is stay put, its top storey is 8.4 m above ground and it has four storeys, so the Residential Evacuation Plans Regulations 2025 do not apply to it.
  • The fire risk assessment still records any group of people it finds especially at risk, and a person-centred fire risk assessment or an evacuation plan can be made with any resident who might need help to leave.
In existing buildings

An assessment of an existing block records any lift used for evacuation, and may rely on its installer’s or maintainer’s evidence that it works.

  • It also checks that the arrangements for residents who need help to escape are suitable (BS 9792 15.3).
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.29Where evacuation lifts are provided, they should be in an evacuation shaft containing a protected stairway, the evacuation lift and an evacuation lift lobby. The lobby should give a refuge area for those waiting for the lift, have direct access to a protected stairway, and not be directly accessible from any flat, maisonette, storage room or electrical equipment room.
  • GuidanceADB Vol 1, 2026 amendment booklet, introductionThe edition before the 2026 amendments continues to apply where a building notice or an initial notice has been given to, or a building control approval application with full plans made to, the relevant authority before 30 September 2026, and the building work has started and is sufficiently progressed before that day, or is started and is sufficiently progressed within the period of 18 months beginning on that day.
  • StandardBS 9991, clause 7.4.1 (opens in a new tab)A building with passenger lift access to an upper or lower level should also have a means of using lifts for escape. A lift provided for escape should be designed and programmed to work as an evacuation lift, with at least one for each escape stair.Why it applies here: This block has a passenger lift to its upper floors. It follows Approved Document B, which does not ask for an evacuation lift in a block like this, so its lift is an ordinary passenger lift.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary 3), and 15.3.6 (opens in a new tab)Evacuation lifts have safety measures that ordinary passenger lifts do not. Judging whether a lift is fit to evacuate people from a particular building is an engineering assessment, not normally within a fire risk assessor’s expertise; the assessment records any lift used for evacuation, with its lobby, smoke control, signs and maintenance.Why it applies here: This block has a passenger lift; the standard says what an assessment does about a lift used for evacuation.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary 1) ii), and 15.3.2 (opens in a new tab)Residents who need help to escape are also likely to live in general housing; in blocks of flats the share of disabled residents is likely to reflect that in the general population. A person-centred fire risk assessment, an evacuation plan, or both, can be made for anyone who might need help to leave their flat or the building, and the information can be kept for the fire and rescue service in a secure information box; the assessment checks that arrangements for them are suitable.Why it applies here: Residents who need help to escape may live in any of this block’s flats.
  • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 1(2) and 3In force from 6 April 2026. A specified residential building contains two or more sets of domestic premises and is at least 18 m in height above ground level, has at least seven storeys, or is more than 11 m in height above ground level and has a simultaneous evacuation strategy, its height measured to the top storey as Appendix D to Approved Document B measures it. A simultaneous evacuation strategy is one in which the responsible person has determined that all persons in the building should leave it immediately in the event of a fire.Why it applies here: This block’s top storey is 8.4 m above ground, under 11 m, it has fewer than seven storeys, and its strategy is stay put, so it is not a specified residential building.
  • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.

What a fire risk assessor checks

  1. The lift: whether it is used for evacuation and, if it is, the evidence that it works and is tested

    Benchmark: BS 9792 15.3: the assessment records any lift used for evacuation and its arrangements, and may rely on evidence from the lift’s installer or maintainer rather than an engineering assessment of its own.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary 3), and 15.3.6Evacuation lifts have safety measures that ordinary passenger lifts do not. Judging whether a lift is fit to evacuate people from a particular building is an engineering assessment, not normally within a fire risk assessor’s expertise; the assessment records any lift used for evacuation, with its lobby, smoke control, signs and maintenance.
  2. Where an older block has a lift motor room: whether it is kept locked shut and free of anything that would burn, its fire-resisting door and sign, and the fire separation between it and the common parts, with any obvious openings in its walls

    Benchmark: The LGA guide, for existing purpose-built blocks: plant rooms are kept locked shut, and a room separated from the escape routes, such as a lift motor room, should still be kept free of combustible materials: a fire there could in time threaten the residents’ escape, and many such rooms are likelier places for a fire to start (section 43 and para 44.2); regular inspections take in plant rooms (para 44.19); a room opening on to the common parts has a fire-resisting door, self-closing or kept locked shut, and is generally signed ‘Fire Door Keep Locked Shut’ (section 16 and paras 58.3 and 63.4); and the fire separation between the common parts and plant rooms is a key consideration of the assessment, with obvious openings in it considered (paras 54.1 and 54.9). For a building built now: Approved Document B says a lift machine room should be over the lift well where possible, and in a building with one stair otherwise outside the protected stair (para 3.108). This block’s lift has no machine room: its motor is at the top of the lift well.

    • GuidanceFire safety in purpose-built blocks of flats, section 43 and paras 44.2 and 44.19Plant rooms and electrical cupboards are kept locked shut. A room separated from the escape routes, such as a lift motor room, should still be kept free of combustible materials: a fire there could in time threaten the escape of the residents, and many such rooms are likelier places for a fire to start. Regular inspections take in plant rooms as well as the stairs, lobbies and corridors.
    • GuidanceFire safety in purpose-built blocks of flats, section 16 (the list after para 16.10) and paras 58.3 and 63.4Rooms opening on to the common corridors and stairs have fire-resisting doors that are self-closing or kept locked shut. The benchmark for a door from an ancillary room on to an internal corridor or lobby is 30 minutes fire resistance, and it need not be self-closing. Doors to ancillary rooms within the common parts generally carry a ‘Fire Door Keep Locked Shut’ sign.
    • GuidanceFire safety in purpose-built blocks of flats, paras 54.1 and 54.9The fire separation between the common parts and ancillary rooms such as plant rooms is a key consideration in a fire risk assessment, and obvious openings in the walls between them should be considered.
    • GuidanceADB Vol 1, para 3.108Lift machine rooms should be sited over the lift well where possible. Where a building, or part of a building, with only one stairway makes this impractical, the lift machine room should be sited outside the protected stairway.

    A defect the source namesCombustible materials stored in a lift motor room, where a fire could in time threaten the residents’ escape even though the room is separated from the escape routes.

    • GuidanceFire safety in purpose-built blocks of flats, section 43 and paras 44.2 and 44.19Plant rooms and electrical cupboards are kept locked shut. A room separated from the escape routes, such as a lift motor room, should still be kept free of combustible materials: a fire there could in time threaten the escape of the residents, and many such rooms are likelier places for a fire to start. Regular inspections take in plant rooms as well as the stairs, lobbies and corridors.
  3. Residents who might need help to escape: what is in place for them

    Benchmark: BS 9792 15.3 and 21: the assessment checks that the arrangements for residents who need help to escape are suitable, and that there is a process for person-centred fire risk assessments, noting in the action plan where one is needed. The law: the risk assessment’s record includes any group of people it identifies as especially at risk (Fire Safety Order article 9(7)(b)). The Residential Evacuation Plans Regulations 2025 apply only to blocks at least 18 m high or with at least seven storeys, or more than 11 m high with a simultaneous evacuation strategy, which this block is not.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3, commentary 1) ii), and 15.3.2Residents who need help to escape are also likely to live in general housing; in blocks of flats the share of disabled residents is likely to reflect that in the general population. A person-centred fire risk assessment, an evacuation plan, or both, can be made for anyone who might need help to leave their flat or the building, and the information can be kept for the fire and rescue service in a secure information box; the assessment checks that arrangements for them are suitable.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 21, commentary, and 21.1 to 21.3A person-centred fire risk assessment, completed by the dutyholder with a resident, looks at the fire hazards in their home and any arrangements they need to prevent a fire, respond to one and escape when necessary. The building’s fire risk assessor does not normally carry it out, but checks there is a process for them, takes their findings into account, and notes in the action plan where one is needed.
    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.
    • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 1(2) and 3In force from 6 April 2026. A specified residential building contains two or more sets of domestic premises and is at least 18 m in height above ground level, has at least seven storeys, or is more than 11 m in height above ground level and has a simultaneous evacuation strategy, its height measured to the top storey as Appendix D to Approved Document B measures it. A simultaneous evacuation strategy is one in which the responsible person has determined that all persons in the building should leave it immediately in the event of a fire.
Show in the 3D model

Protected entrance halls

  • Means of escape
  • Compartmentation
Show in the 3D model

Inside each flat the rooms open off a protected entrance hall with fire-resisting walls and fire doors.

  • If a fire starts in a room, the hall stays clear long enough for everyone in the flat to reach the front door.
  • It runs no more than 9 m from the front door to the door of the furthest habitable room.
  • The doors off the hall are fire doors, but inside a flat they need no self-closers.

Here, on the floors above the ground, each hall runs from the front door towards the far end of the flat, with the bedrooms, the bathroom and the living room off it.

  • The longest, to the door of its furthest habitable room, is 8.8 m; the other three are shorter.
  • Of the walls inside the flat, only those round the hall, and the doors off it, resist fire: they are drawn in plaster with a dark top where they are cut.
  • The walls between the other rooms are ordinary partitions, drawn thinner in a warm plain finish, and they carry no fire resistance label.
  • The flat’s own walls to the next flat, the lobby and the stair are compartment walls, REI 60 (see Compartment walls).
  • On the ground floor every habitable room either opens on to a hall leading to the flat’s own front door, a final exit, or has a door of its own straight outside: in two of the flats the front door opens into the living room and the bedrooms have doors straight outside.
  • So no protected entrance hall is needed (paras 3.14 and 3.15), and the walls inside those flats are all drawn as ordinary partitions.

REI 30The hall walls are built to resist fire for 30 minutes in the standard test (Table B1 item 16); the doors off the hall are E 20 fire doors (Table C1 item 9), with no self-closers inside a flat (para C5). The other walls between rooms are not fire resisting.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.18(a)In flats with storeys more than 4.5 m above ground level, one approach is a protected entrance hall (minimum REI 30) serving all habitable rooms, meeting the conditions shown in Diagram 3.2.
  • GuidanceADB Vol 1, Diagram 3.2All habitable rooms open off the protected entrance hall, which runs no more than 9 m from the flat entrance door to the door of the furthest habitable room. The doors off it are fire doorsets (minimum E 20). A bathroom needs no fire doorset if it is separated from the adjacent rooms by fire resisting construction.
  • GuidanceADB Vol 1, Table B1 item 16An enclosure in a flat to a protected entrance hall, or to a protected landing: REI 30, each side separately.
  • GuidanceADB Vol 1, Table C1 item 9Any door that forms part of the enclosure to a protected entrance hall or protected landing in a flat: E 20 (FD 20).
  • GuidanceADB Vol 1, para C5All fire doorsets, including those to flat entrances, should have a self-closing device, except fire doorsets to cupboards, to service ducts normally locked shut, and within flats.
  • GuidanceADB Vol 1, paras 3.14 and 3.15In flats with no storey more than 4.5 m above ground level, every habitable room on the ground storey (kitchens excepted) should have either an opening directly on to a hall leading to a final exit, or an emergency escape window or door. Where a flat is reached through the common parts of a block, a protected entrance hall may be needed to meet para 3.32 and Diagram 3.9.Why it applies here: The four flats on this block’s ground floor each have a front door of their own to the open air, and every habitable room in them either opens on to a hall leading to the flat’s front door, a final exit, or has a door of its own straight outside: in two of the flats the front door opens into the living room and the bedrooms have doors straight outside.
Show in the 3D model

Compartment walls

  • Compartmentation
Show in the 3D model

Every flat is its own fire compartment.

  • The walls between flats, and between each flat and the lobby or the stair, resist fire for 60 minutes in the standard test.
  • That limits the spread of a fire beyond the flat where it started, for that time.

The time is the test’s, not a promise about a real fire.

In existing buildings

In an existing block, an assessment looks by eye, without opening anything up, at:

  • the walls between the flats and the common parts
  • the compartmentation it can reach in risers, cupboards, voids and roof spaces

It does this thoroughly in a stay put block: poor fire stopping has been found even in new blocks, and noise or cooking smells passing between flats can be a sign of a weakness (BS 9792 clause 5 and 15.7).

REI 60Walls between flats, and between a flat and a lobby or the stair (Table B1 item 6a; Table B2, a block of flats without sprinklers, top floor more than 5 m and up to 11 m).

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1Any wall separating a flat from another part of the building is a compartment wall, and any floor (unless within a flat) is a compartment floor.
  • GuidanceADB Vol 1, Table B1 item 6aCompartment wall separating a flat from any other part of the building: REI 60, or the Table B2 period if that is less.Why it applies here: Table B2 gives 60 minutes for a block of flats without sprinklers with its top floor more than 5 m and up to 11 m above ground, so these walls are REI 60.
  • GuidanceADB Vol 1, Table B2A block of flats without a sprinkler system, with its top floor more than 5 m and up to 11 m above ground: 60 minutes for the elements of structure in its ground and upper storeys. With the top floor up to 5 m it would be 30 minutes.
  • GuidanceADB Vol 1, para B22Fire resistance is measured in minutes. This relates to time elapsed in a standard test and should not be confused with real time.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentary (opens in a new tab)A Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3 (opens in a new tab)In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.Why it applies here: This block has a stay put strategy, which relies on the walls and floors between the flats.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The walls between the flats and the common parts, and what passes through them, so far as can be seen without opening anything up

    Benchmark: BS 9792 clause 5 and 15.7: a Type 1 assessment covers the separating construction between the flats and the common parts so far as reasonably practicable without opening up; in a block with a stay put strategy a full and thorough visual inspection of compartmentation is particularly important, and what could not be checked is recorded.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentaryA Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.

    A defect the source namesPoor fire stopping of junctions and service penetrations, found even in new and recently built blocks; noise or cooking smells passing between flats can be a sign of a weakness.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.
  2. When a deeper investigation is warranted

    Benchmark: BS 9792 15.7 and 19: concerns that could compromise the evacuation strategy are referred to a competent person for further investigation; another type of assessment or a specialist is recommended only for a stated reason, not as a matter of course.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 19, commentary, and 19.4, 19.7 and 19.9The action plan’s measures should be proportionate, reasonably practicable and possible to maintain, and the plan should say which recommendations are needed to comply with the law and which go further. A Type 1 assessment recommends another type of assessment or a specialist only for a stated reason, not as a matter of course.
Show in the 3D model

Compartment floor

  • Compartmentation
Show in the 3D model

Every floor between the flats is a compartment floor.

  • It limits the spread of a fire from one flat to the flats above and below.
  • It is built to resist fire for 60 minutes in the standard test, the period Table B2 gives this block.

REI 60Table B2: a block of flats without sprinklers, top floor more than 5 m and up to 11 m above ground.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1(a)Any floor, unless it is within a flat, should be a compartment floor.
  • GuidanceADB Vol 1, para 7.13Where a compartment floor meets an external wall with no fire resistance, the wall should be restrained at floor level.
  • GuidanceADB Vol 1, Table B1 item 3cAny floor other than those between a shop and a flat or in a two storey house, including compartment floors: REI for the period in Table B2, tested from the underside.
  • GuidanceADB Vol 1, Table B2A block of flats without a sprinkler system, with its top floor more than 5 m and up to 11 m above ground: 60 minutes for the elements of structure in its ground and upper storeys. With the top floor up to 5 m it would be 30 minutes.
  • GuidanceADB Vol 1, para B22Fire resistance is measured in minutes. This relates to time elapsed in a standard test and should not be confused with real time.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Service penetrations and fire stopping

  • Compartmentation
Show in the 3D model

Pipes, cables and ducts have to pass through the walls and floors that divide a block into compartments.

  • Every joint, gap and opening they leave is sealed with fire-stopping so the wall or floor keeps its fire resistance, and the openings are kept as few and as small as practicable.
  • A plastic pipe through a compartment floor is sealed by a proprietary tested system, or by one of the other ways the guidance allows.
  • Fire-stopping delays the spread of fire, and generally of smoke too.

Here the soil stack from the south-west flats’ bathrooms runs down through every floor above the ground, against the north wall between the WC and the bath.

  • The two sides of its boxing, one across its front and one on the WC’s side, are drawn cut down to 0.3 m so the stack shows, and the WC’s branch joins the stack above them.
  • Where it passes through each compartment floor it wears a fire collar, drawn in red, which seals the opening round it in a fire.
In existing buildings

In an existing block most of this is hidden. An assessment:

  • looks, without opening anything up, at a sample of service risers, cupboards and ceiling voids
  • records what it could not see
  • asks whether the flats’ extracts share a common duct, which in older blocks could undermine stay put (BS 9792 clause 5 and 15.7)

E 30 casingThe soil stack’s casing has fire resistance of at least E 30, as Table 9.1 and Diagram 9.1 ask of a stack enclosed this way, and where the stack passes through each compartment floor its fire collar keeps the floor’s fire resistance.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 9.2Pipes passing through a fire-separating element, unless in a protected shaft, should meet one of alternatives A, B or C.
  • GuidanceADB Vol 1, para 9.3Alternative A: a proprietary, tested sealing system that will maintain the fire resistance of the wall, floor or cavity barrier.
  • GuidanceADB Vol 1, Table 9.1 and Diagram 9.1A uPVC stack pipe through a compartment floor between flats may be up to 160 mm across when enclosed as in Diagram 9.1, with fire-stopping around it. The casing should not have fire resistance less than E 30.
  • GuidanceADB Vol 1, para 9.5Alternative C: a pipe up to 160 mm across in lead, aluminium, fibre-cement or uPVC may pass through inside a sleeve of high melting point metal.
  • GuidanceADB Vol 1, para 9.1Every joint, imperfect fit and opening for services through a fire-separating element should be sealed with fire-stopping to ensure that the fire resistance of the element is not impaired. Fire-stopping delays the spread of fire and, generally, the spread of smoke as well.
  • GuidanceADB Vol 1, para 9.24Joints between fire-separating elements should be fire-stopped, and openings through a fire resisting element for pipes, ducts, conduits or cable should be as few as possible, as small as practicable and fire-stopped (allowing thermal movement in the case of a pipe or duct).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentary (opens in a new tab)A Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3 (opens in a new tab)In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.Why it applies here: This block has a stay put strategy, which relies on the walls and floors between the flats.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary d) (opens in a new tab)In older blocks the bathroom or kitchen extracts of the flats sometimes share a common duct with no effective measures against fire or smoke passing between flats, which could undermine a stay put strategy. An assessment cannot usually examine the arrangement, but determines whether a common extract system is present so that further investigation can be recommended.Why it applies here: Each flat in this block has a bathroom and a kitchen, whose extracts an assessment of an older block would ask about.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Fire stopping where services pass through the walls and floors between the flats and the common parts, at a sample of places: service risers and cupboards that can be opened, and above lifted ceiling tiles

    Benchmark: BS 9792 clause 5 and 15.7: a Type 1 assessment looks, without opening anything up, at fire stopping at sample places in service risers, opening a sample of risers and lifting a sample of ceiling tiles where it can; in a stay put block the inspection is full and thorough, and anything not checked is recorded with an action. That level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews may take a sample.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentaryA Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.

    A defect the source namesPoor fire stopping of junctions and service penetrations, and incomplete construction in risers, found even in new and recently built blocks.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary a), and 15.7.1 to 15.7.3In a block with a stay put strategy, which relies on compartmentation, a full and thorough visual inspection of compartmentation and fire stopping is particularly important: preferably the corridors, stairs, voids, risers, cupboards and roof spaces are accessed and inspected, and anything not checked is recorded with an action. Poor fire stopping of junctions and service penetrations has been found even in new and recently built blocks, and noise or cooking smells passing between flats can be a sign of a weakness. Concerns are referred for further investigation by a competent person. This level of detailed scrutiny will not be required for every Type 1 assessment, and later reviews and assessments may take a sample unless there is reason to suspect that building work or a lack of maintenance has brought in new deficiencies.
  2. Ventilation: whether the flats’ bathroom or kitchen extracts share a common duct

    Benchmark: BS 9792 15.7 d): the assessment determines whether a common extract system is present, so that further investigation can be recommended.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary d)In older blocks the bathroom or kitchen extracts of the flats sometimes share a common duct with no effective measures against fire or smoke passing between flats, which could undermine a stay put strategy. An assessment cannot usually examine the arrangement, but determines whether a common extract system is present so that further investigation can be recommended.

    A defect the source namesIn older blocks, extracts sharing a common duct with no effective measures against fire or smoke passing between flats, which could undermine stay put.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary d)In older blocks the bathroom or kitchen extracts of the flats sometimes share a common duct with no effective measures against fire or smoke passing between flats, which could undermine a stay put strategy. An assessment cannot usually examine the arrangement, but determines whether a common extract system is present so that further investigation can be recommended.
  3. How a pipe, cable or duct through a compartment wall or floor is sealed

    Benchmark: For a building built now: Approved Document B says every joint, imperfect fit and opening for services through a fire-separating element should be fire-stopped, with openings as few and as small as practicable (paras 9.1 and 9.24).

    • GuidanceADB Vol 1, para 9.1Every joint, imperfect fit and opening for services through a fire-separating element should be sealed with fire-stopping to ensure that the fire resistance of the element is not impaired. Fire-stopping delays the spread of fire and, generally, the spread of smoke as well.
    • GuidanceADB Vol 1, para 9.24Joints between fire-separating elements should be fire-stopped, and openings through a fire resisting element for pipes, ducts, conduits or cable should be as few as possible, as small as practicable and fire-stopped (allowing thermal movement in the case of a pipe or duct).
Show in the 3D model

Smoke alarms in the flats

  • Detection and alarm
Show in the 3D model

Each flat has its own mains-powered alarms with a backup supply: smoke alarms in the hall and the living area, and a heat alarm in the kitchen area.

  • They warn the people in that flat only, in time to get out and call the fire service. There is no alarm that sounds across the block, because the block is designed for stay put.
  • Stay put: the people in the flat on fire leave and call the fire service, and other residents not directly affected by the fire are expected to stay in their flats unless the fire service tells them to leave, though anyone who wishes to leave is not stopped.
  • Stay put rests on the walls, floors and doors between the flats, which resist fire for a set time in the standard test and so limit its spread.
  • Fires have been known to spread beyond the flat where they started, usually through failings in the construction, so the protection has to be kept as it was built, and the fire risk assessment, reviewed regularly, keeps the strategy under review.

Stay put is not a promise that a fire in one flat cannot reach another.

In existing buildings

Older flats may have battery-only alarms, or none.

  • In England the landlord of a rented home must make sure a smoke alarm is fitted on each storey that has a room used as living accommodation, and check that it works on the day each new tenancy begins.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 1.1All dwellings should have a fire detection and alarm system, minimum Grade D2 Category LD3, in accordance with BS 5839-6.
  • GuidanceADB Vol 1, para 1.2Smoke alarms should be mains operated and conform to BS EN 14604.
  • GuidanceADB Vol 1, para 1.10Each flat in a block should have alarms as set out in paragraphs 1.1 to 1.4. With effective compartmentation, a communal fire alarm system is not normally needed.
  • LawSmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)The immediate landlord of a home in England let on a tenancy the regulations cover must ensure that, while it is occupied under that tenancy, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker; that each alarm is checked and in proper working order on the day a new tenancy begins; and that, when a tenant reports an alarm, it is checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.
  • StandardBS 5839-6, clause 9.2 a) and Table 1 (opens in a new tab)Where the occupants are not known, as in a new flat, Table 1 applies: Grade D1, Category LD2 for a rented flat, which this model uses; an owner-occupied flat may be Grade D2, Category LD2. Category LD2 adds detectors in the kitchen (heat only) and the principal habitable room (heat or smoke; this model uses smoke).Why it applies here: ADB para 1.1 asks for at least Grade D2, Category LD3 to BS 5839-6. These flats are new and their occupants are not known, so this model follows the higher recommendation of the standard’s Table 1.
  • StandardBS 5839-6, Foreword and Introduction (opens in a new tab)Communal fire alarm systems should not normally be installed in purpose-built blocks of flats: they are normally undesirable and can even put residents at risk.Why it applies here: This is a purpose-built block of flats, so its lobbies and stair have no general fire alarm; each flat has its own.
  • GuidanceFire safety in purpose-built blocks of flats, para 19.1Under a stay put policy, the people in the flat where a fire starts get out and call the fire and rescue service, and so does anyone in the common parts when a fire starts there; all other residents not directly affected by the fire would be expected to stay in their flat unless the fire and rescue service tells them to leave.
  • GuidanceFire safety in purpose-built blocks of flats, paras 18.4 and 19.2Fires have been known to spread beyond the flat of origin to involve other flats, or across the top of blocks through the roof voids, and total evacuation has then sometimes been necessary; such fires are rare, and usually the fault of failings in the construction. A stay put policy does not mean that residents not directly involved who wish to leave should be prevented from doing so.
  • GuidanceADB Vol 1, Table B2A block of flats without a sprinkler system, with its top floor more than 5 m and up to 11 m above ground: 60 minutes for the elements of structure in its ground and upper storeys. With the top floor up to 5 m it would be 30 minutes.
  • Ongoing dutyFire Safety Order 2005, Article 9(1), (3) and (6)The responsible person must make a suitable and sufficient assessment of the risks to which relevant persons are exposed (article 9(1)), must review it regularly so as to keep it up to date, particularly if there is reason to suspect it is no longer valid or there has been a significant change (article 9(3)), and must make a record of the assessment or review as soon as practicable afterwards (article 9(6)).
Show in the 3D model

Emergency lighting

  • Means of escape
Show in the 3D model

Lights in the lobbies and the stair that stay on if the mains power fails, so the way out stays lit.

  • The stair’s lighting is on a circuit of its own, separate from the rest of the escape route.
In existing buildings

In an existing block, an assessor judges by eye whether the lighting covers the stair and the lobbies, and whether it lasts long enough, normally 3 hours.

  • The assessment also checks that it is tested, in most cases monthly with a full duration test once a year.
  • An older system that does not meet current recommendations in full may still be acceptable (BS 9792 15.5; LGA guide 81.5).
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.45Except for two storey blocks of flats, all escape routes should have adequate artificial lighting. If the mains electricity power supply fails, escape lighting should illuminate the route.
  • GuidanceADB Vol 1, para 3.47Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
  • StandardBS 5266-1 (opens in a new tab)Emergency lighting of premises: where it goes, how much light it gives, how long it lasts and how it is tested.Why it applies here: ADB Volume 1 para 3.48 asks for escape lighting to conform to BS 5266-1, so the fittings on this escape route follow it. ADB names the 2016 edition; this page uses the current edition, BS 5266-1:2025.
  • Ongoing dutyFire Safety Order 2005, Article 17The responsible person keeps the fire safety equipment in the common parts, such as emergency lighting, maintained in efficient working order and good repair.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.5, commentary, and 15.5.1 and 15.5.2 (opens in a new tab)Emergency escape lighting is normally needed on all escape routes in housing. The assessor judges by eye whether the existing system covers the routes, and whether it lasts long enough, normally 3 hours, and confirms that it is routinely tested and maintained; an existing system that does not meet current recommendations in full may be acceptable.Why it applies here: The block’s lobbies and stair, its escape routes, have emergency escape lighting.
  • GuidanceFire safety in purpose-built blocks of flats, paras 81.5, 81.8, 81.9 and 81.24Emergency lighting that does not test itself has a monthly functional test and a full duration test once a year. Automatic or electrically operated smoke vents are tested monthly from their controls, and the detectors and controls that open them at least once a year. Fire mains are inspected every six months and tested every twelve.

What a fire risk assessor checks

  1. Whether the lighting covers the stair and the lobbies and lasts long enough, and its test records

    Benchmark: BS 9792 15.5: emergency escape lighting is normally needed on all escape routes; the assessor judges by eye whether it covers the routes, and whether it lasts long enough, normally 3 hours, and confirms it is routinely tested and maintained. The LGA guide: a monthly functional test and a full duration test once a year, unless the fittings test themselves. The law: escape routes that need lighting have emergency lighting, kept in efficient working order (Fire Safety Order articles 14(2)(h) and 17).

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.5, commentary, and 15.5.1 and 15.5.2Emergency escape lighting is normally needed on all escape routes in housing. The assessor judges by eye whether the existing system covers the routes, and whether it lasts long enough, normally 3 hours, and confirms that it is routinely tested and maintained; an existing system that does not meet current recommendations in full may be acceptable.
    • GuidanceFire safety in purpose-built blocks of flats, paras 81.5, 81.8, 81.9 and 81.24Emergency lighting that does not test itself has a monthly functional test and a full duration test once a year. Automatic or electrically operated smoke vents are tested monthly from their controls, and the detectors and controls that open them at least once a year. Fire mains are inspected every six months and tested every twelve.
    • Ongoing dutyFire Safety Order 2005, Article 14(2)(h)Where necessary to safeguard the people in and around the premises, emergency routes and exits that need illumination must have emergency lighting of adequate intensity in case their normal lighting fails.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
Show in the 3D model

Dry riser

A dry riser is an empty pipe that runs up the stair, with an outlet on every landing.

  • Firefighters pump water in at the inlet outside the entrance and take it off at the outlet on the floor they need, instead of running hose all the way from the street.

Why this block has one: without it, a hose from where the pump appliance parks would need about 61.3 m to reach the furthest point in any flat, the far corner of a bedroom on the top floor (8.4 m from the pump to the entrance, 6.5 m along the exit passageway to the stair, 2.3 m across the ground floor landing to the first flight, 22.9 m up the flights and landings to floor 3, 2.6 m across the landing to the stair door, 18.6 m across the lobby and through flat 3.04).

  • Even if the appliance could stop right at the entrance door, it would need about 52.9 m.
  • That is more than the 45 m allowed when there is no fire main, so the block has one.
  • From the outlet on floor 3 the same corner is 21.3 m away; the Travel button shows the route.
In existing buildings

In an existing block a dry riser should be inspected every six months and tested every twelve (LGA guide 81.24).

  • An assessment checks there are arrangements for it.

One is rarely added to a block built without one (BS 9792 15.12).

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 14.4The outlets from fire mains should be located within the protected stairway enclosure.
  • GuidanceADB Vol 1, para 13.2For flats, either provide access for a pumping appliance to within 45 m of all points inside each flat of a block, measured along the route of the hose, with a door at least 750 mm wide on every elevation that has vehicle access, or provide fire mains in accordance with paras 13.5 and 13.6.
  • GuidanceADB Vol 1, para 14.3Buildings without firefighting shafts should have fire mains where fire service vehicle access does not meet para 13.2(a). The fire mains are in the protected stairway, with a hose distance of no more than 45 m from the outlet to the furthest point inside each flat, measured on a route suitable for laying a hose.
  • GuidanceADB Vol 1, para 14.5Guidance on the design and construction of fire mains is given in BS 9990.
  • StandardBS 9990 (opens in a new tab)Design and construction of fire mains, inlets and landing valves.Why it applies here: This block has a fire main because a hose from the pump appliance would need more than 45 m to reach the furthest point in a flat, and ADB para 14.5 sends the design of fire mains to BS 9990.
  • StandardBS 9990, clause 4.1.5 (opens in a new tab)A landing valve on every floor, including the ground floor. In blocks of flats it sits on the full landing inside the stair enclosure, with its lowest point about 750 mm above the floor.Why it applies here: This is the valve firefighters connect their hose to on each floor, and the clause sets where it goes and how high.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.12, commentary a) to c), and 15.12.5 and 15.12.6 (opens in a new tab)Where stay put applies, the fire and rescue service putting a fire out quickly can be essential to the strategy, so the assessment takes account of the facilities for firefighters: that fire mains are tested and maintained (an assessment rarely recommends fitting one where there was none), the hydrants nearby, and access for appliances and to the inlets. If a fault in any of them cannot be put right within 24 hours, the dutyholder is advised to tell the fire and rescue service.Why it applies here: This block has a dry riser with its inlet, a hydrant in the street and access for a pump appliance.
  • GuidanceFire safety in purpose-built blocks of flats, paras 81.5, 81.8, 81.9 and 81.24Emergency lighting that does not test itself has a monthly functional test and a full duration test once a year. Automatic or electrically operated smoke vents are tested monthly from their controls, and the detectors and controls that open them at least once a year. Fire mains are inspected every six months and tested every twelve.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The dry riser, its inlet and outlets, the way to the inlet, and the test records

    Benchmark: BS 9792 15.12: the assessment checks that fire mains are tested and maintained and that access for appliances and to the inlet is not impeded; a fault not put right within 24 hours is reported to the fire and rescue service. The LGA guide: fire mains inspected every six months and tested every twelve. The law: facilities for firefighters are maintained in efficient working order (Fire Safety Order article 38).

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.12, commentary a) to c), and 15.12.5 and 15.12.6Where stay put applies, the fire and rescue service putting a fire out quickly can be essential to the strategy, so the assessment takes account of the facilities for firefighters: that fire mains are tested and maintained (an assessment rarely recommends fitting one where there was none), the hydrants nearby, and access for appliances and to the inlets. If a fault in any of them cannot be put right within 24 hours, the dutyholder is advised to tell the fire and rescue service.
    • GuidanceFire safety in purpose-built blocks of flats, paras 81.5, 81.8, 81.9 and 81.24Emergency lighting that does not test itself has a monthly functional test and a full duration test once a year. Automatic or electrically operated smoke vents are tested monthly from their controls, and the detectors and controls that open them at least once a year. Fire mains are inspected every six months and tested every twelve.
    • Ongoing dutyFire Safety Order 2005, Article 38(1)Where necessary to safeguard firefighters in a fire, the responsible person must ensure that the facilities, equipment and devices provided for their use or protection are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
Show in the 3D model

Roof hatch and ladder

  • Compartmentation
Show in the 3D model

A hatch over the top of the stair, reached by a fixed ladder, lets the people who look after the roof get on to it.

  • It is for maintenance, not for escape.
  • Fixed ladders should not be provided as a means of escape for members of the public, and should only be provided where a conventional stair is impractical, such as for access to plant rooms that are not normally occupied.
  • Nor should a ladder form part of the escape route from any flat.

Here a locked hatch in the ceiling at the top of the stair opens on to the flat roof between the two pitched roofs, where the stair vent and the lift overrun are.

  • Its steel ladder is fixed to the stair’s west wall.
  • On this floor, where the stair stops, the floor is carried a little way over the head of the first flight: the ladder and the space to climb it stand there, clear of every door, of the lift’s landing and of the flight people use.
  • In this model the hatch and its frame are part of the stair’s enclosure, as the ceiling they sit in is.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.88Fixed ladders should not be provided as a means of escape for members of the public. They should only be provided where a conventional stair is impractical, such as for access to plant rooms which are not normally occupied.
  • StandardBS 9991, clause 9 (opens in a new tab)Ladders should not form part of a means of escape route from any dwelling. A note (NOTE 3) adds that ladders to BS EN ISO 14122-4 may form part of an escape route from areas reached only occasionally, for maintenance and repair.Why it applies here: BS 9991 is the code of practice for fire safety in residential buildings, and this block’s roof hatch is reached by a fixed ladder, for maintenance only: the flats escape by the stair.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

External wall build-up

The external walls are masonry, with a brick outer leaf, under pitched roofs of plain concrete tiles.

  • Which rules apply depends on which height is measured.
  • Table 10.1, for the outer surface, takes the height of the building to its mean roof level, for a pitched roof half way between the lowest and highest points of its slopes (Diagram D4): 12.2 m to each of the two pitched roofs here, and the flat roof between them is 11.2 m up: more than 11 m either way.
  • Following Table 10.1, the surface should be class A2-s1, d0 or better however far it is from the boundary, and timber cladding is not one of the exceptions it allows (the other route is a full-scale test to BR 135, para 10.3(b)).
  • Para 10.7, for the insulation and filler inside the wall, takes the height of the top storey to its floor: 8.4 m here, so it does not apply, and nor does para 10.10 on balconies, which starts at the same storey height of 11 m.
In existing buildings

In an existing block, masonry walls like these, without attachments likely to give a serious risk of fire spreading over the outside, are normally taken to be an acceptable risk without a specialist appraisal (BS 9792 clause 5).

See Balconies and the external walls of existing blocks.

  • LawBuilding Regulations 2010, Schedule 1, B4External fire spread.
  • GuidanceADB Vol 1, Table 10.1For residential buildings (purpose groups 1 and 2) more than 11 m high, the outermost surface of an external wall should be class A2-s1, d0 or better wherever it is. At 11 m or less: class B-s3, d2 or better less than 1000 mm from the relevant boundary, and no provision 1000 mm or more from it. Timber cladding at least 9 mm thick is accepted only where the table asks for class C-s3, d2 (note 3).
  • GuidanceADB Vol 1, Appendix A and Diagrams D4 and D6The height of a building is measured as Diagram D4 shows, from the mean ground level to the mean roof level. The height of the top storey is measured as Diagram D6 shows, from ground level on the lowest side of the building to the upper surface of the top floor. They are different heights: a block whose top storey is under 11 m can be more than 11 m high.
  • GuidanceADB Vol 1, para 10.3The external walls of buildings other than those described in regulation 7(4) should either follow paras 10.5 to 10.9 (external surfaces, materials and products, cavities and cavity barriers), or meet the performance criteria in BRE report BR 135, using full-scale test data from BS 8414-1 or BS 8414-2.
  • GuidanceADB Vol 1, para 10.7In buildings that include a residential purpose with a storey 11 m or more in height (Diagram D6), any insulation product or filler material used in the construction of an external wall should be class A2-s1, d0 or better. This does not apply to masonry cavity walls that comply with Diagram 8.2.
  • GuidanceADB Vol 1, para 10.10In buildings that include a residential purpose with a storey 11 m or more in height, balconies should meet one of two conditions; the first is that they contain only materials of class A1 or A2-s1, d0, apart from listed items such as cavity trays between two leaves of masonry, membranes, seals, fixings and electrical installations.
  • GuidanceADB Vol 1, para 10.4In buildings of any height or use, the choice of materials for the external wall and its attachments, such as balconies, should be considered, to reduce the risk of fire spread over the wall.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentary (opens in a new tab)A Type 1 assessment considers the external walls, including any cladding and attachments such as balconies. Where the walls are of traditional masonry, two leaves of masonry or a solid masonry leaf, concrete or stone, without attachments likely to give a serious risk of fire spreading over the outside, it is normally reasonable to assume that the risk from the walls is acceptable without further investigation, which does not mean the assessor has checked them against the building regulations. For other walls a fire risk appraisal of external walls (FRAEW) might be appropriate.Why it applies here: This block’s external walls are masonry with a brick outer leaf, and it has balconies.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Balconies and the external walls of existing blocks

Since the Fire Safety Act 2021, the Fire Safety Order applies to the structure and external walls of any building with two or more flats.

  • That includes the doors and windows in those walls and anything attached to them such as balconies, so the fire risk assessment of a block takes in its walls.
  • Where it is not obvious to the assessor that the walls are low risk, a specialist may be asked for a fire risk appraisal of external walls (FRAEW), PAS 9980 being one method.
  • For new building work, the choice of materials for balconies is to be considered at any height, and where a storey is 11 m or more up they are limited to the highest classes of reaction to fire, with listed exceptions, or built to a second set of conditions.

Here the walls are masonry with a brick outer leaf, the balconies are slabs with railings, and the top storey is 8.4 m above ground, so para 10.10 does not apply to the balconies.

  • Masonry walls like these, without attachments likely to give a serious risk of fire spreading over the outside, are the kind an assessor normally takes to be an acceptable risk without a specialist appraisal.
  • Whether the balconies are such an attachment is part of what the assessment looks at.
In existing buildings

An assessment of an existing block describes the walls and any cladding, and asks about changes since it was built.

  • It recommends a specialist appraisal (an FRAEW, PAS 9980 being one method) only where it is not obvious that the risk is acceptable (BS 9792 15.10).
  • LawBuilding Regulations 2010, Schedule 1, B4External fire spread.
  • LawFire Safety Act 2021, Section 1Inserted article 6(1A) and (1B) into the Fire Safety Order, in force in England from 16 May 2022: where a building contains two or more sets of domestic premises, the Order applies to its structure and external walls, including doors and windows in them and anything attached to them such as balconies, to any common parts, and to all doors between the flats and the common parts.
  • Ongoing dutyFire Safety Order 2005, Article 6(1A) and (1B)Where a building contains two or more sets of domestic premises, the things the Order applies to include the building’s structure and external walls and any common parts, and all doors between the domestic premises and the common parts. The external walls include doors or windows in them and anything attached to their exterior, including balconies.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.10, commentary, and 15.10.1 to 15.10.4 (opens in a new tab)In a block of flats the assessment addresses the construction and fire performance of the external walls. Often it is obvious to a competent assessor that the risk does not warrant a separate specialist appraisal, for example where the walls can readily be confirmed as traditional masonry, though combustible materials may have been added over time. Otherwise the assessor may recommend an FRAEW by a specialist, PAS 9980 being one method. The assessment describes the walls and any cladding, takes account of any FRAEW, asks the dutyholder about known concerns and later alterations, and recommends investigation where there is good reason to suspect the walls did not meet the regulations when built.Why it applies here: This block is a block of flats with masonry external walls and balconies.
  • StandardPAS 9980 Fire risk appraisal of external wall construction and cladding of existing blocks of flats. Code of practice, clause 1 and its NOTE 3A method for appraising the risk to occupants from fire spreading over the external walls and cladding of an existing multistorey block of flats of any height, where the risk is known or suspected to come from how the walls are built, such as combustible materials; its outcome informs the fire risk assessment. Walls of masonry or concrete only, or whose only combustible material is insulation in the cavity of double skin masonry, are usually considered an acceptable risk, and an appraisal is not considered necessary for them.Why it applies here: This block’s external walls are masonry with a brick outer leaf; PAS 9980 says when an appraisal of such walls is and is not needed.
  • GuidanceADB Vol 1, para 10.4In buildings of any height or use, the choice of materials for the external wall and its attachments, such as balconies, should be considered, to reduce the risk of fire spread over the wall.
  • GuidanceADB Vol 1, para 10.10In buildings that include a residential purpose with a storey 11 m or more in height, balconies should meet one of two conditions; the first is that they contain only materials of class A1 or A2-s1, d0, apart from listed items such as cavity trays between two leaves of masonry, membranes, seals, fixings and electrical installations.Why it applies here: This block’s top storey is 8.4 m above ground, under 11 m, so para 10.10 does not apply to its balconies.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentary (opens in a new tab)A Type 1 assessment considers the external walls, including any cladding and attachments such as balconies. Where the walls are of traditional masonry, two leaves of masonry or a solid masonry leaf, concrete or stone, without attachments likely to give a serious risk of fire spreading over the outside, it is normally reasonable to assume that the risk from the walls is acceptable without further investigation, which does not mean the assessor has checked them against the building regulations. For other walls a fire risk appraisal of external walls (FRAEW) might be appropriate.Why it applies here: This block’s external walls are masonry with a brick outer leaf, and it has balconies.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. What the external walls are made of, any cladding, the balconies and other attachments, and any changes since the block was built

    Benchmark: BS 9792 15.10: the assessment describes the walls and any cladding, takes account of any appraisal of them, and asks the dutyholder about known concerns and alterations since construction, such as new cladding, windows or attachments.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.10, commentary, and 15.10.1 to 15.10.4In a block of flats the assessment addresses the construction and fire performance of the external walls. Often it is obvious to a competent assessor that the risk does not warrant a separate specialist appraisal, for example where the walls can readily be confirmed as traditional masonry, though combustible materials may have been added over time. Otherwise the assessor may recommend an FRAEW by a specialist, PAS 9980 being one method. The assessment describes the walls and any cladding, takes account of any FRAEW, asks the dutyholder about known concerns and later alterations, and recommends investigation where there is good reason to suspect the walls did not meet the regulations when built.
  2. Whether a specialist fire risk appraisal of the external walls (FRAEW) is needed

    Benchmark: BS 9792 clause 5 and 15.10: for traditional masonry walls without attachments likely to give a serious risk of fire spreading over the outside, it is normally reasonable to assume the risk is acceptable without further investigation, though combustible materials may have been added over time; for other walls a specialist appraisal may be recommended. PAS 9980: walls of masonry or concrete only, or whose only combustible material is insulation in the cavity of double skin masonry, usually need no appraisal.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentaryA Type 1 assessment considers the external walls, including any cladding and attachments such as balconies. Where the walls are of traditional masonry, two leaves of masonry or a solid masonry leaf, concrete or stone, without attachments likely to give a serious risk of fire spreading over the outside, it is normally reasonable to assume that the risk from the walls is acceptable without further investigation, which does not mean the assessor has checked them against the building regulations. For other walls a fire risk appraisal of external walls (FRAEW) might be appropriate.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.10, commentary, and 15.10.1 to 15.10.4In a block of flats the assessment addresses the construction and fire performance of the external walls. Often it is obvious to a competent assessor that the risk does not warrant a separate specialist appraisal, for example where the walls can readily be confirmed as traditional masonry, though combustible materials may have been added over time. Otherwise the assessor may recommend an FRAEW by a specialist, PAS 9980 being one method. The assessment describes the walls and any cladding, takes account of any FRAEW, asks the dutyholder about known concerns and later alterations, and recommends investigation where there is good reason to suspect the walls did not meet the regulations when built.
    • StandardPAS 9980 Fire risk appraisal of external wall construction and cladding of existing blocks of flats. Code of practice, clause 1 and its NOTE 3A method for appraising the risk to occupants from fire spreading over the external walls and cladding of an existing multistorey block of flats of any height, where the risk is known or suspected to come from how the walls are built, such as combustible materials; its outcome informs the fire risk assessment. Walls of masonry or concrete only, or whose only combustible material is insulation in the cavity of double skin masonry, are usually considered an acceptable risk, and an appraisal is not considered necessary for them.
  3. What the law brings into the assessment

    Benchmark: The law: since 16 May 2022 in England the Fire Safety Order covers the structure and external walls of a building with two or more flats, including windows, doors and attachments such as balconies (articles 6(1A) and 6(1B), inserted by the Fire Safety Act 2021). The record of the external walls’ design and materials in regulation 5 of the Fire Safety (England) Regulations 2022 is required only for high-rise residential buildings, which this block is not.

    • LawFire Safety Act 2021, Section 1Inserted article 6(1A) and (1B) into the Fire Safety Order, in force in England from 16 May 2022: where a building contains two or more sets of domestic premises, the Order applies to its structure and external walls, including doors and windows in them and anything attached to them such as balconies, to any common parts, and to all doors between the flats and the common parts.
    • Ongoing dutyFire Safety Order 2005, Article 6(1A) and (1B)Where a building contains two or more sets of domestic premises, the things the Order applies to include the building’s structure and external walls and any common parts, and all doors between the domestic premises and the common parts. The external walls include doors or windows in them and anything attached to their exterior, including balconies.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3 and 5The responsible person for a high-rise residential building, one with two or more sets of domestic premises at least 18 m high or with at least seven storeys, must prepare a record of the design and materials of its external walls, with the level of risk the risk assessment finds they give rise to and any mitigating steps, revised after any significant change to them.
Show in the 3D model

The site and the ground floor

Entrance and final exit

  • Means of escape
Show in the 3D model

The stair leads out through its east door and along a protected exit passageway to the front door.

  • No flat opens onto it, so anyone coming down the stair reaches the open air without passing a flat door.
  • The front door opens easily from inside.

No flat on the ground floor opens on to the passageway or any other common part: each of the four flats there has a front door of its own in an external wall.

  • Nor does the refuse room, which is entered only from outside.
  • The passageway is 1.5 m wide, with the locked meter cupboard set back into its wall.
  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.93Doors on escape routes should be readily openable, to avoid undue delay to people escaping.
  • GuidanceADB Vol 1, para 3.84Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
  • StandardBS 9991, clause 15.1 and Figure 31 (opens in a new tab)A protected stairway should discharge directly to a final exit, or into a protected corridor leading to one. Any such corridor should have the same standard of fire-resisting enclosure and lobby protection as the stair it serves: the route from the stair to the final exit is protected as the stair is protected from the flats on the other storeys. Figure 31 shows examples, with the doors on these routes as self-closing E 30 Sa fire doors, and shows as not acceptable a final exit reached through the access corridor or lobby that the flats open on to.Why it applies here: This block’s single stair reaches its final exit along a passageway on the ground floor, and no flat opens on to the passageway: the flats on the ground floor have front doors of their own.
Show in the 3D model

Fire action notice and fire safety records

  • Means of escape
Show in the 3D model

In a building with two or more flats and common parts residents would escape through, the responsible person must display fire safety instructions in a conspicuous part of the building:

  • the evacuation strategy
  • how to report a fire
  • what residents must do once there is one

Behind the notice sit records the law asks for:

  • the fire risk assessment with its findings
  • the arrangements for running fire safety
  • the fire safety information given to residents

When a new responsible person takes over, the outgoing one passes on the risk assessment records and any fire safety information the builder handed over when the block was built; an older block may have none.

Here the fire action notice hangs on the wall of the exit passageway on the ground floor, which everyone living on the floors above passes on the way in and out.

  • The ground floor flats have front doors of their own, and every resident is also given a copy (regulation 9(3)).
  • It sets out the stay put strategy, how to report a fire, and what residents must do once there is one.
In existing buildings

An assessment of an existing block checks the notice and what residents are told, and the records:

  • the assessment and its reviews
  • the fire safety arrangements
  • the testing and maintenance of every fire safety measure, normally kept with a fire safety manual (BS 9792 clause 16)

It also determines whether fire safety signs and notices, fire action notices among them, are needed, and whether those provided are suitable (BS 9792 15.4).

  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9The responsible person must display fire safety instructions in a conspicuous part of any building which contains two or more sets of domestic premises and common parts through which residents would need to evacuate, covering the evacuation strategy, how to report a fire and what residents must do, and give them to residents.
  • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.
  • Ongoing dutyFire Safety Order 2005, Article 11The responsible person must make and give effect to arrangements for the effective planning, organisation, control, monitoring and review of the preventive and protective measures, and must record those arrangements.
  • Ongoing dutyFire Safety Order 2005, Article 21AIn a building with two or more sets of domestic premises, the responsible person must give residents comprehensible and relevant information about the risks the risk assessment identifies, the preventive and protective measures, the responsible person’s name and an address in the UK for notices, and who has been appointed to help with the risk assessment; and must keep records of these matters.
  • Ongoing dutyFire Safety Order 2005, Article 22AWhen one responsible person takes over from another, the outgoing one must give the new one the fire safety information they hold, including the records of the risk assessments and reviews and any fire safety information given under regulation 38 of the Building Regulations 2010; a responsible person must keep records of that information.
  • LawBuilding Regulations 2010, Regulation 38(1) to (3)Where building work erects or extends a building to which the Fire Safety Order will apply, or goes with a change of use that brings the Order to it, and Part B applies to the work, the person carrying out the work must give the responsible person fire safety information, about the design and construction of the building and its services, fittings and equipment, that will help them operate and maintain it with reasonable safety, no later than completion or occupation; the responsible person acknowledges receiving it.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 16, commentary g), j) and k), and 16.3 (opens in a new tab)Fire safety management is as important as the physical precautions. The assessment checks there are routine inspections, needing little specialist knowledge, that escape routes stay clear, self-closing fire doors work and nothing is stored on routes that should stay sterile, with defects reported and put right; that all fire protection is tested and maintained; and that records of inspection, testing and maintenance are kept, normally with a fire safety manual.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 16, commentary l) (information for residents) (opens in a new tab)It is important that housing providers engage with residents on fire safety, giving them at least, among other things: how to prevent fire in their flat and the common parts, why flat entrance doors and their closers matter, what to do in a fire, the means of escape, what stay put means where it applies, keeping the escape routes and the fire service’s access and inlets clear, and how to report defects.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.4, commentary b) and f), 15.4.1 and its NOTE, and 15.4.2 (opens in a new tab)The assessment determines whether fire safety signs and notices are needed, and whether those provided are adequate: among them signs on fire doors saying they are to be kept shut or kept locked shut, and fire action notices. No signs may be needed, but there may be a need for fire action notices, and the suitability of any existing signs and notices is determined.Why it applies here: This block has a fire action notice in its exit passageway and fire doors to its stair and its meter cupboard.

What a fire risk assessor checks

  1. The fire action notice, and what residents are told

    Benchmark: The law: fire safety instructions displayed in a conspicuous part of the building and given to residents (Fire Safety (England) Regulations 2022, regulation 9); comprehensible information about the risks and the fire safety measures, with records kept (Fire Safety Order article 21A). BS 9792 16: at least, among other things, what stay put means, keeping the escape routes and the fire service’s inlets clear, and how to report defects. BS 9792 15.4: whether fire safety signs and notices, fire action notices among them, are needed, and whether those provided are suitable.

    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9The responsible person must display fire safety instructions in a conspicuous part of any building which contains two or more sets of domestic premises and common parts through which residents would need to evacuate, covering the evacuation strategy, how to report a fire and what residents must do, and give them to residents.
    • Ongoing dutyFire Safety Order 2005, Article 21AIn a building with two or more sets of domestic premises, the responsible person must give residents comprehensible and relevant information about the risks the risk assessment identifies, the preventive and protective measures, the responsible person’s name and an address in the UK for notices, and who has been appointed to help with the risk assessment; and must keep records of these matters.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 16, commentary l) (information for residents)It is important that housing providers engage with residents on fire safety, giving them at least, among other things: how to prevent fire in their flat and the common parts, why flat entrance doors and their closers matter, what to do in a fire, the means of escape, what stay put means where it applies, keeping the escape routes and the fire service’s access and inlets clear, and how to report defects.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.4, commentary b) and f), 15.4.1 and its NOTE, and 15.4.2The assessment determines whether fire safety signs and notices are needed, and whether those provided are adequate: among them signs on fire doors saying they are to be kept shut or kept locked shut, and fire action notices. No signs may be needed, but there may be a need for fire action notices, and the suitability of any existing signs and notices is determined.
  2. The records: the risk assessment and its reviews, the fire safety arrangements, and the inspection, testing and maintenance of each fire safety measure

    Benchmark: The law: the risk assessment and each review are recorded (article 9(6)), the arrangements for managing fire safety are recorded (article 11), and the risk assessment records and any fire safety information from the builder are passed to any new responsible person (article 22A; Building Regulations 2010, regulation 38; an older block may have none). BS 9792 16: records of inspection, testing and maintenance, normally with a fire safety manual.

    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.
    • Ongoing dutyFire Safety Order 2005, Article 11The responsible person must make and give effect to arrangements for the effective planning, organisation, control, monitoring and review of the preventive and protective measures, and must record those arrangements.
    • Ongoing dutyFire Safety Order 2005, Article 22AWhen one responsible person takes over from another, the outgoing one must give the new one the fire safety information they hold, including the records of the risk assessments and reviews and any fire safety information given under regulation 38 of the Building Regulations 2010; a responsible person must keep records of that information.
    • LawBuilding Regulations 2010, Regulation 38(1) to (3)Where building work erects or extends a building to which the Fire Safety Order will apply, or goes with a change of use that brings the Order to it, and Part B applies to the work, the person carrying out the work must give the responsible person fire safety information, about the design and construction of the building and its services, fittings and equipment, that will help them operate and maintain it with reasonable safety, no later than completion or occupation; the responsible person acknowledges receiving it.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 16, commentary g), j) and k), and 16.3Fire safety management is as important as the physical precautions. The assessment checks there are routine inspections, needing little specialist knowledge, that escape routes stay clear, self-closing fire doors work and nothing is stored on routes that should stay sterile, with defects reported and put right; that all fire protection is tested and maintained; and that records of inspection, testing and maintenance are kept, normally with a fire safety manual.
  3. Who makes the assessment, and how often it is reviewed

    Benchmark: The law: the assessment is reviewed regularly and whenever it may no longer be valid (article 9(3)). BS 9792 7 and 20: a competent assessor; as a general guide, not a rule, a low-risk low-rise block might be reviewed every two years, with a new assessment every four.

    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clauses 7.1 to 7.3A fire risk assessment should be carried out by a competent person, who understands, among other things, fire precautions in older existing buildings as well as current standards, and who recognises the limits of their own competence and draws on specialist advice where needed, for example for an FRAEW or a person-centred fire risk assessment.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 20, commentary, and 20.1An assessment is reviewed after material alterations, significant changes, a fire, or when a set period has passed. As a general guide, not a rule, for a low-risk, low-rise block of flats a review every two years might be enough, with a new assessment every four years.
Show in the 3D model

Electricity meter cupboard

  • Compartmentation
  • Means of escape
Show in the 3D model

Here the electricity meters are in a locked cupboard recessed into the north wall of the protected exit passageway on the ground floor, by the entrance, so the passageway keeps its full width.

  • In a single stair building the meters should be in a securely locked cupboard, separated from the escape route by fire resisting construction (ADB para 3.82).
  • Here that is the whole enclosure: the cupboard’s walls, its door and the door’s frame, and where the meters’ cables pass through its walls, the openings are fire-stopped (para 9.24).
  • The passageway is protected as the stair is (para 3.84), and a protected stairway may hold nothing but a lift well and electricity meters (para 3.81).
  • Gas pipes and meters are kept out of the stair unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998 (para 3.83).
In existing buildings

An assessment of an existing block asks when the electrical installation was last inspected and tested, and may record the date (BS 9792 clause 13).

REI 60Assumed: ADB asks for the meters to be separated from the escape route by fire-resisting construction, without a period, and for the exit passageway to be protected as the stair is, so the model gives the cupboard the stair’s REI 60, with an E 30 Sa door like the stair’s own.

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • GuidanceADB Vol 1, para 3.81A protected stairway should not be used for anything else, except a lift well or electricity meters.
  • GuidanceADB Vol 1, para 3.82In single stair buildings, electricity meters should be in securely locked cupboards, separated from the escape route by fire resisting construction.
  • GuidanceADB Vol 1, para 3.83Gas service and installation pipes and meters should not be within a protected stairway, unless installed in accordance with the Pipelines Safety Regulations 1996 and the Gas Safety (Installation and Use) Regulations 1998.Why it applies here: This model has no gas supply in the stair.
  • GuidanceADB Vol 1, para 3.84Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
  • GuidanceADB Vol 1, para 9.24Joints between fire-separating elements should be fire-stopped, and openings through a fire resisting element for pipes, ducts, conduits or cable should be as few as possible, as small as practicable and fire-stopped.Why it applies here: The meter cupboard is fire resisting construction, and the meters’ cables pass through its walls.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 b) (opens in a new tab)Electrical faults are one of the sources of fire every assessment covers. One control is a policy that the electrical installation is inspected and tested periodically; the assessor checks it is followed, for example from the last certificate of inspection and test, and it can help to record its date.Why it applies here: The block has electrical installations in its common parts, its meter cupboard among them.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The electrical installation in the common parts: when it was last inspected and tested

    Benchmark: BS 9792 13: electrical faults are one of the sources of fire every assessment covers; the policy of periodic inspection and testing is checked against the last certificate, and recording its date can help.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 b)Electrical faults are one of the sources of fire every assessment covers. One control is a policy that the electrical installation is inspected and tested periodically; the assessor checks it is followed, for example from the last certificate of inspection and test, and it can help to record its date.
Show in the 3D model

Fire service switch for the stair vent

  • Smoke control
  • Firefighting
Show in the 3D model

One vent at the top of the stair, opened by the fire service with a switch at the fire service access level.

  • Opening it lets out smoke that has got into the stair while doors were open.
  • The other way of meeting the guidance is a high-level openable vent at every storey; either way each vent has a free area of at least 1 m2.
  • Where a block with no more than two flats a floor leaves out the lobby, it needs instead an automatic vent with a geometric free area of at least 1 m2 at the top of the stair, opened when smoke is detected at any storey in the stair.

The switch is the fire service override: crews can open the vent, or close it, whatever the detectors have done (para 3.32(e)(ii)).

  • LawBuilding Regulations 2010, Schedule 1, B1Means of warning and escape.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 3.32(e)For the fire and rescue service, either a high-level openable vent with a free area of at least 1 m2 at each storey, or a single openable vent with a free area of at least 1 m2 at the head of the stair, operable remotely at the fire and rescue service access level.
  • GuidanceADB Vol 1, Diagram 3.9 note 3Where, in a small single stair building with no more than two flats per storey, the lobby between the common stair and the flat is left out, an automatic opening vent with a geometric free area of at least 1 m2 is needed at the top of the stair, opened on detection of smoke at any storey in the stair.
  • Ongoing dutyFire Safety Order 2005, Article 38Where necessary in order to safeguard the safety of fire-fighters, the facilities and equipment provided for them, such as a vent for the fire service and its switch, are subject to a suitable system of maintenance and maintained in an efficient state, in efficient working order and in good repair.
Show in the 3D model

Fire service hardstanding

The pump appliance parks here, on the access road beside the entrance, within 18 m of the dry riser inlet and in sight of it.

  • The access road and its surface are wide and strong enough for a pump appliance.

The access road ends in a turning head, so the fire appliance never has to reverse more than 20 m (para 13.4, Diagram 13.1).

  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 13.3Access routes and hardstandings should comply with the guidance in Table 13.1.
  • GuidanceADB Vol 1, Table 13.1For a pump appliance: at least 3.7 m between kerbs, gateways at least 3.1 m wide, clearance height at least 3.7 m, and a carrying capacity of at least 12.5 tonnes.
  • GuidanceADB Vol 1, para 13.5Pumping appliance access to within 18 m of each inlet, and the inlet visible from where the appliance parks.
  • GuidanceADB Vol 1, para 13.4Dead-end access routes longer than 20 m require turning facilities, as in Diagram 13.1, which shows a turning circle, hammerhead or other point at which the vehicle can turn: fire and rescue service vehicles should not have to reverse more than 20 m from the end of an access road. Turning facilities should comply with the guidance in Table 13.1, which for a pump appliance gives a turning circle of at least 16.8 m between kerbs (19.2 m between walls).

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Dry riser inlet

This is where the fire engine connects to the dry riser.

  • It is on the face of the building, in a locked red box, within 18 m of where the engine parks and in sight of it.
  • Water pumped in here fills the main all the way to the top.

Here two lines of hose run to the inlet from two deliveries at the back of the pump appliance, one to each of its two connections: the inlet is a two-way breeching inlet (BS 9990 clause 4.1.3.2).

  • In general fire service practice, crews charge a dry riser through two lines of hose rather than one.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 13.5For buildings fitted with dry fire mains, a pumping appliance should be able to get within 18 m of each fire main inlet. Inlets should be on the face of the building, visible from where the appliance parks, and meet Section 8 of BS 9990.
  • StandardBS 9990, clause 4.1.3.2 and Section 8 (opens in a new tab)Clause 4.1.3.2 sets the inlet itself: a two-way breeching inlet in an inlet box, its lower edge 400 mm to 600 mm above the ground. Section 8 covers signage: identifying the equipment and giving information about the system.Why it applies here: ADB para 13.5(b) asks the inlet to meet Section 8 of BS 9990, which is about signing and identifying it; clause 4.1.3.2 is where the standard sets out the inlet.
  • Ongoing dutyFire Safety Order 2005, Article 38Facilities and equipment provided for firefighters, such as the fire main and its inlet, are kept maintained in efficient working order and good repair.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Refuse room and bin store

  • Compartmentation
Show in the 3D model

The bins are kept in a refuse room inside the block on the ground floor, west of the stair, and in a store of its own across the access road.

  • The refuse room is entered only from the open air, through a wide door in the block’s west wall, and has no door to the stair, the exit passageway or any other common part.
  • Its walls, and the floor over it, are built to resist fire for 60 minutes in the standard test, and it is not within the stair or a protected lobby. No flat’s window is above its door.
  • The guidance asks for the door to be kept away from final exits and from the windows of flats but gives no distance: here it is 3.75 m along the wall from a bedroom’s door straight outside, and about 4.7 m from another flat’s front door.
  • Because the room is part of the block, those provisions for a refuse room in a building apply to it.
  • The store across the road is a small building of its own: BS 5906 still sets how it is built and run, and what matters for the block is its distance from the block and from the block’s doors and windows.
  • It serves the flats above, whose way out is the entrance on the east side, and the two east flats on the ground floor: its door is in its north face, facing away from the entrance, 8.8 m from the nearest window of a flat.
  • Burning waste gives very toxic smoke and many waste fires are started deliberately, so both are built to hold a fire and kept locked.
In existing buildings

Malicious ignition and poor waste management are among the fire hazards every assessment of an existing block covers (BS 9792 clauses 13.2 and 13.3).

REI 60The refuse room’s walls, and the floor over it, are REI 60, as para 3.60 asks where the top storey is more than 5 m above ground, and it opens only to the open air. The store across the road is a building of its own.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, para 7.1(c)Any wall enclosing a refuse storage chamber should be a compartment wall.
  • GuidanceADB Vol 1, para 3.60Rooms for storing refuse should be separated from other parts of the building by fire resisting construction (minimum REI 30 where the top storey is up to 5 m above ground, otherwise REI 60), and should not be in a protected stairway, evacuation shaft or protected lobby.Why it applies here: The refuse room is inside the block, so its walls and the floor over it are REI 60, as the top storey is more than 5 m above ground, and it is not within the stair or a protected lobby: it opens only to the open air. The store across the road stands apart from the block, so open air separates them.
  • GuidanceADB Vol 1, para 3.61The approach to a refuse store should be directly from the open air, or through a protected lobby with at least 0.2 m2 of permanent ventilation.
  • GuidanceADB Vol 1, para 3.62Access openings to refuse storage chambers should not be next to escape routes or final exits, or near the windows of flats.
  • GuidanceADB Vol 1, para 3.59Refuse storage chambers, refuse chutes and refuse hoppers should be sited and constructed in accordance with BS 5906.
  • StandardBS 5906, clauses 4.9 and 8.1 to 8.5 (opens in a new tab)A waste store is sited at vehicle access level, preferably away from the main entrance, so that containers go straight outside without passing through the building, with at least 2 m of headroom and 150 mm clear between containers and round them. Its walls and roof are non-combustible and resist fire for an hour; its door is steel or resists fire for 30 minutes, in a metal, hardwood or metal-clad frame, lockable with a lock the collection service can use, openable from inside, and self-closing unless it opens straight to the open air. Its floor is at least 100 mm thick, hard and impervious, with no step at the entrance. Permanent vents of at least 0.2 m² in all, as near the ceiling and the floor as possible and away from the windows of homes, let out odours and dense flammable gases. It is ideally outside the building or cut off from it, so nobody can get in through it. Burning waste gives very toxic smoke, up to half of waste fires are started deliberately, and one 1100 litre wheeled bin of loose paper can burn at about 930 kW, so stores are built to hold a fire, and kept locked and signed.Why it applies here: ADB Vol 1 para 3.59 says refuse stores are sited and built to BS 5906, and these are the block’s refuse room and bin store.
  • GuidanceADB Vol 1, para 3.32For some low rise buildings a single stair, protected as Diagram 3.9 shows, may be used where all of the following apply: the top storey is a maximum of 11 m above ground level; no more than three storeys are above the ground storey; the stair does not connect to a covered car park unless it is open sided; the stair does not serve offices, stores or other ancillary accommodation, unless they are separated from it by a protected lobby or protected corridor (minimum REI 30) with at least 0.4 m2 of permanent ventilation, or protected from smoke by a mechanical smoke control system; and a vent is provided for the fire and rescue service (para 3.32(e)).Why it applies here: Para 3.32(d)’s note sends refuse storage to paras 3.59 to 3.62; the refuse room has no door to the stair or the passageway, so the stair does not serve it.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 and 13.3 (opens in a new tab)Every assessment covers, among other sources of fire, malicious ignition, and situations such as poor housekeeping, poor waste management and battery-powered mobility scooters, e-scooters and e-bikes in the common areas or escape routes. Combustible materials left in the common parts of a block against the policy for them can lead to a fire that undermines the stay put strategy, which rests on fire being unlikely in the common parts and very limited if it occurs.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).

What a fire risk assessor checks

  1. The refuse room and the bin store: how the waste is kept, and the risk of it being set alight

    Benchmark: BS 9792 13.2 and 13.3: malicious ignition and poor waste management are among the fire hazards every assessment covers.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary, and 13.2 and 13.3Every assessment covers, among other sources of fire, malicious ignition, and situations such as poor housekeeping, poor waste management and battery-powered mobility scooters, e-scooters and e-bikes in the common areas or escape routes. Combustible materials left in the common parts of a block against the policy for them can lead to a fire that undermines the stay put strategy, which rests on fire being unlikely in the common parts and very limited if it occurs.
Show in the 3D model

Cycle store

  • Compartmentation
Show in the 3D model

Bicycles and e-bikes are kept in a store of their own in the courtyard, not in the lobbies or the stair, so a battery fire cannot block the only stair.

  • There are no sockets in the store, and the sign by the door says no charging.
  • It is clad in timber boards.
  • It is a small building of its own, so Table 10.1 is read for it as a building in its own right, against its own boundaries: it stands well away from every relevant boundary, including the notional one between it and the block, so the table sets no class for its outer surface.
  • The block’s walls are a separate question, read against the block’s own height: more than 11 m high to its mean roof level, they should be class A2-s1, d0 or better.
In existing buildings

An assessment of an existing block notes any e-bikes or e-scooters, assesses their risk and deals with them in its action plan (BS 9792 clause 13).

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceFire safety in purpose-built blocks of flats, para 44.18 and the checklist after itSuitable communal storage, and for example charging rooms for mobility scooters, can greatly help residents keep the common parts clear. Mobility scooters, batteries and other electrical equipment should never be charged in the common parts; dedicated charging rooms, suitably fire separated from the rest of the block, should be considered.
  • GuidanceADB Vol 1, Table 10.1For residential buildings (purpose groups 1 and 2) more than 11 m high, the outermost surface of an external wall should be class A2-s1, d0 or better wherever it is. At 11 m or less: class B-s3, d2 or better less than 1000 mm from the relevant boundary, and no provision 1000 mm or more from it. Timber cladding at least 9 mm thick is accepted only where the table asks for class C-s3, d2 (note 3).
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary (opens in a new tab)Lithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.Why it applies here: The block’s bicycles and e-bikes are kept in a store of their own.

What a fire risk assessor checks

  1. E-bikes and e-scooters: where they are kept and charged

    Benchmark: BS 9792 13: the assessment notes any lithium-ion battery vehicles, assesses their risk and deals with them in its action plan.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentaryLithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.

    A defect the source namesLithium-ion vehicles can give very rapid fire development, toxic fumes and explosion if damaged or faulty.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentaryLithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.
Show in the 3D model

Fire hydrant in the street

A fire hydrant under a cover in the footway, with its plate on a post nearby so it can be found.

  • Approved Document B asks a new building for hydrants of its own where it has a compartment of more than 280 m2 and stands more than 100 m from an existing hydrant.
  • Then, with a dry fire main, they should be within 90 m of its inlets.
  • Each hydrant should be clearly marked by a plate fixed nearby in a conspicuous position.

Here the hydrant is in the street’s footway, 29.6 m from the dry riser inlet.

  • ADB para 14.8 asks this block for no hydrant of its own: its largest compartment, a flat, is 90.9 m2, well under 280 m2, and it stands well within 100 m of an existing hydrant, this one.
  • LawBuilding Regulations 2010, Schedule 1, B5Access and facilities for the fire service.
  • GuidanceADB Vol 1, para 14.8A building requires additional fire hydrants if both of the following apply: it has a compartment with an area of more than 280 m2, and it is being erected more than 100 m from an existing fire hydrant.
  • GuidanceADB Vol 1, para 14.9Where additional hydrants are needed, for a building with fire mains they should be within 90 m of the dry fire main inlets.
  • GuidanceADB Vol 1, para 14.10Each fire hydrant should be clearly indicated by a plate, fixed nearby in a conspicuous position, in accordance with BS 3251.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

What changes above 11 m

  • Firefighting
  • External wall
  • Means of escape
Show in the 3D model

Many provisions for blocks of flats start once the top storey is more than 11 m above ground, measured to the floor of the top storey, and they are of two kinds.

Some are design guidance for new building work:

  • a sprinkler system throughout the building, the common stairs, corridors and landings left out only where they are fire sterile (ADB para 7.4)
  • floor and flat signs for the fire service (para 15.13)
  • a secure information box (para 15.19)
  • from a storey of 11 m or more, limits on the insulation in the external walls (para 10.7) and on the materials of balconies (para 10.10)
  • Above 11 m the small single stair layout is no longer available (para 3.32): a single stair is still possible, with smoke vents in the lobbies or corridors and travel of up to 7.5 m, and only while the top storey is under 18 m (Diagram 3.7 note 6).
  • Since the 2026 amendments, the guidance asks for more than one stair once the top storey is 18 m or more (para 3.30), with transitional provisions for work already under way.

Others are legal duties on whoever runs a building that already stands:

  • Above 11 m to the top storey, the responsible person must check the fire doors, at least every 3 months in the common parts and, with best endeavours, at least every 12 months at the flat entrances (Fire Safety (England) Regulations 2022, regulation 10).
  • The same regulations ask for an information box and floor and flat signs only in a high-rise residential building, at least 18 m high or with at least seven storeys (regulations 3, 4 and 8): the guidance above 11 m is for new work, not a duty on every existing block over 11 m.
  • Since 6 April 2026 the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 apply to blocks of flats at least 18 m high or with at least seven storeys, and to those more than 11 m high with a simultaneous evacuation strategy.

One table measures differently: Table 10.1 takes the height of the building to its roof, so its rule for the outside of the walls can apply while the top storey is still under 11 m.

Here the top storey is 8.4 m above ground, measured to its floor (Diagram D6), so none of the provisions measured that way apply, and with a stay put strategy it is outside the evacuation plans regulations.

  • One more storey would put it at 11.2 m, and they all would.
  • Table 10.1’s row for buildings more than 11 m high already applies, because the building, measured to its mean roof level (Diagram D4), is 12.2 m high.
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.
  • GuidanceADB Vol 1, para 15.13To help the fire service identify each floor, a block of flats with a top storey more than 11 m above ground level should have floor identification signs and flat indicator signs.
  • GuidanceADB Vol 1, para 15.19Blocks of flats with a top storey more than 11 m above ground level should be provided with a secure information box.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.
  • GuidanceADB Vol 1, para 10.7In buildings that include a residential purpose with a storey 11 m or more in height (Diagram D6), any insulation product or filler material used in the construction of an external wall should be class A2-s1, d0 or better. This does not apply to masonry cavity walls that comply with Diagram 8.2.
  • GuidanceADB Vol 1, para 10.10In buildings that include a residential purpose with a storey 11 m or more in height, balconies should meet one of two conditions; the first is that they contain only materials of class A1 or A2-s1, d0, apart from listed items such as cavity trays between two leaves of masonry, membranes, seals, fixings and electrical installations.
  • GuidanceADB Vol 1, para 3.32For some low rise buildings a single stair, protected as Diagram 3.9 shows, may be used where all of the following apply: the top storey is a maximum of 11 m above ground level; no more than three storeys are above the ground storey; the stair does not connect to a covered car park unless it is open sided; the stair does not serve offices, stores or other ancillary accommodation, unless they are separated from it by a protected lobby or protected corridor (minimum REI 30) with at least 0.4 m2 of permanent ventilation, or protected from smoke by a mechanical smoke control system; and a vent is provided for the fire and rescue service (para 3.32(e)).
  • GuidanceADB Vol 1, para 3.27(a)From the flat entrance door, a single escape route is acceptable on a storey served by a single common stair where every flat is separated from the stair by a protected lobby or common protected corridor (Diagram 3.7) and the travel distance in Table 3.1 for escape in one direction only is not exceeded.
  • GuidanceADB Vol 1, Table 3.1 note 2The maximum travel distance from a flat entrance door to the storey exit, where escape is in one direction only, is 7.5 m; in a small single stair building that follows Diagram 3.9 it is reduced to 4.5 m.
  • GuidanceADB Vol 1, para 3.54Except in buildings that comply with Diagram 3.9, the corridor or lobby directly in front of each storey exit should have a smoke vent, as high as practicable, with its top edge at least as high as the top of the door to the stair.
  • GuidanceADB Vol 1, Diagram 3.7 note 6A single common stair arrangement is only suitable for buildings with a top storey less than 18 m in height.
  • GuidanceADB Vol 1, Table 10.1For residential buildings (purpose groups 1 and 2) more than 11 m high, the outermost surface of an external wall should be class A2-s1, d0 or better wherever it is. At 11 m or less: class B-s3, d2 or better less than 1000 mm from the relevant boundary, and no provision 1000 mm or more from it. Timber cladding at least 9 mm thick is accepted only where the table asks for class C-s3, d2 (note 3).
  • GuidanceADB Vol 1, Appendix A and Diagrams D4 and D6The height of a building is measured as Diagram D4 shows, from the mean ground level to the mean roof level. The height of the top storey is measured as Diagram D6 shows, from ground level on the lowest side of the building to the upper surface of the top floor. They are different heights: a block whose top storey is under 11 m can be more than 11 m high.
  • GuidanceADB Vol 1, para 3.30Flats should be served by more than one common stair if either of the following applies. a. The flat is on a storey that does not meet the criteria for a single escape route or a small single stair building (see paragraphs 3.27 and 3.32). b. The building has a top storey of 18m or more in height (see Diagram D6 in Appendix D).
  • GuidanceADB Vol 1, 2026 amendment booklet, introductionThe edition before the 2026 amendments continues to apply where a building notice or an initial notice has been given to, or a building control approval application with full plans made to, the relevant authority before 30 September 2026, and the building work has started and is sufficiently progressed before that day, or is started and is sufficiently progressed within the period of 18 months beginning on that day.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulations 3, 4 and 8A high-rise residential building contains two or more sets of domestic premises and is at least 18 m above ground level or has at least seven storeys, its height measured to the top storey as Appendix D to Approved Document B measures it (regulation 3). Its responsible person installs a secure information box, readily accessible to the fire and rescue service (regulation 4), and must ensure the building contains clear markings of floor identification and identification of domestic premises (regulation 8, wayfinding signage).
  • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 1(2) and 3In force from 6 April 2026. A specified residential building contains two or more sets of domestic premises and is at least 18 m in height above ground level, has at least seven storeys, or is more than 11 m in height above ground level and has a simultaneous evacuation strategy, its height measured to the top storey as Appendix D to Approved Document B measures it. A simultaneous evacuation strategy is one in which the responsible person has determined that all persons in the building should leave it immediately in the event of a fire.Why it applies here: This block’s top storey is 8.4 m above ground, under 11 m, it has fewer than seven storeys, and its strategy is stay put, so it is not a specified residential building.
Show in the 3D model
  • This is guidance on what an assessor looks at, not an assessment of any real building.
  • BS 9792 and the LGA guide are guidance, not law. A code of practice is a benchmark, applied in proportion to the risk, and an older block that differs from today’s guidance does not need upgrading for that alone (BS 9792:2025 clauses 8 and 9).
  • A fire risk assessment should be made by a competent person (BS 9792:2025 clause 7).
  • The LGA guide dates from 2011, and its cover note says it is no longer comprehensive; it is cited here for existing doors, routine testing, lift motor rooms in older blocks and the history of the standards. Approved Document B is cited only for what new building work would need.

Fire scenarios, step by step

Each is an illustrative order of events, not a fire engineering model, and keeps to no timetable. Each plays step by step in the model above, from its tile or the Fire button.

A flat on floor 2: A fire starts in flat 2.04

A flat on floor 2

A kitchen fire in flat 2.04 in a block with no sprinklers: the flat's own alarms, the protected hall and the self-closing door, staying put, the vent at the head of the stair, and the fire service working from the floor below to put it out.

10 steps. Shown at Over 5 m.

The refuse room: A fire starts in a bin

The refuse room

A bin fire in the refuse room of a block with no sprinklers: the fire-resisting walls and floor round it, why it opens only to the open air, the flats staying put, and the fire service putting it out from outside.

8 steps. Shown at Over 5 m.

Ongoing duties once people live here

Fire safety does not stop when the building is finished. These are the duties the law puts on whoever runs this building once people live and work in it: what must be done, by whom, when, and the law it comes from. Some apply only from a certain height; each says where it applies in this building.

  1. A fire risk assessment, kept up to date

    Who
    The responsible person for the common parts
    What
    Make a suitable and sufficient assessment of the fire risks to the people in and around the premises, and review it regularly to keep it up to date. Record it, and each review, with its findings and any group of people it finds especially at risk.
    When
    From the day the block is in use. Review it whenever there is reason to think it is no longer valid, or after a significant change to the premises or how they are run.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3) and (6)The responsible person must make a suitable and sufficient assessment of the risks to which relevant persons are exposed (article 9(1)), must review it regularly so as to keep it up to date, particularly if there is reason to suspect it is no longer valid or there has been a significant change (article 9(3)), and must make a record of the assessment or review as soon as practicable afterwards (article 9(6)).
    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.

    In the model: Fire action notice and fire safety records, Protected stair, Lobby between the stair and the flats

  2. Fire safety arrangements, recorded

    Who
    The responsible person
    What
    Make and carry out arrangements for planning, organising, controlling, monitoring and reviewing the fire safety measures, and record them.
    When
    From the day the block is in use.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 11The responsible person must make and give effect to arrangements for the effective planning, organisation, control, monitoring and review of the preventive and protective measures, and must record those arrangements.

    In the model: Fire action notice and fire safety records

  3. Fire safety measures kept in working order

    Who
    The responsible person
    What
    Where necessary to keep people safe, keep the premises and their fire safety measures under a suitable system of maintenance, in efficient working order and good repair: here the stair doors and the flat entrance doors with their closers, the emergency lighting, and the stair vent with its detectors. Escape routes that need lighting have emergency lighting.
    When
    From the day the block is in use. In a building with two or more flats the Fire Safety Order reaches its structure, external walls and common parts, and the doors between the flats and the common parts.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
    • Ongoing dutyFire Safety Order 2005, Article 14(2)(h)Where necessary to safeguard the people in and around the premises, emergency routes and exits that need illumination must have emergency lighting of adequate intensity in case their normal lighting fails.
    • Ongoing dutyFire Safety Order 2005, Article 6(1A) and (1B)Where a building contains two or more sets of domestic premises, the things the Order applies to include the building’s structure and external walls and any common parts, and all doors between the domestic premises and the common parts. The external walls include doors or windows in them and anything attached to their exterior, including balconies.

    In the model: Stair doors and fire door checks, Flat entrance doors, Emergency lighting, Fire service vent at the head of the stair

  4. Escape routes kept clear

    Who
    The responsible person
    What
    Where necessary to keep people safe, keep the routes to the exits, and the exits themselves, clear at all times: here the lobbies, the stair, the exit passageway and the entrance.
    When
    From the day the block is in use.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.

    In the model: Protected stair, Lobby between the stair and the flats, Entrance and final exit

  5. Fire safety instructions for residents

    Who
    The responsible person
    What
    Display fire safety instructions in a conspicuous part of the building, in a form residents can be expected to understand: the evacuation strategy, how to report a fire to the fire and rescue service, and anything else residents must do once there is a fire. Give a copy to each new resident as soon as reasonably practicable after they move in, to every resident in each 12 month period counted from 23 January 2023, when the regulations came into force, and again after any material change.
    When
    Any building with two or more flats and common parts that residents would escape through: this block.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9In a building with two or more sets of domestic premises and common parts residents would evacuate through, the responsible person must display fire safety instructions in a conspicuous part of the building, covering the evacuation strategy, how to report a fire and what to do once a fire has occurred, and must give residents a copy when they move in, every 12 months and after any material change.

    In the model: Fire action notice and fire safety records, Protected stair, Lobby between the stair and the flats

  6. Fire safety information for residents

    Who
    The responsible person
    What
    Give residents comprehensible and relevant information about the risks the fire risk assessment finds, the fire safety measures, the responsible person’s name and an address in the UK for notices, and who has been appointed to help with the assessment; and keep records of it.
    When
    Any building with two or more flats: this block. In force since 1 October 2023.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 21AIn a building with two or more sets of domestic premises, the responsible person must give residents comprehensible and relevant information about the risks the risk assessment identifies, the preventive and protective measures, the responsible person’s name and an address in the UK for notices, and who has been appointed to help with the risk assessment; and must keep records of these matters.

    In the model: Fire action notice and fire safety records

  7. Fire door information for residents

    Who
    The responsible person
    What
    Tell residents that fire doors should be kept shut when not in use, that they and their guests should not tamper with the self-closing devices, and that they should report any fault or damage to a door at once. Give it to each new resident as soon as reasonably practicable after they move in, and to every resident in each 12 month period counted from 23 January 2023, when the regulations came into force.
    When
    Any building with two or more flats and common parts that residents would escape through: this block.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(1) to (3)In a building with two or more sets of domestic premises and common parts residents would evacuate through, the responsible person must tell residents that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported at once: new residents when they move in, and all residents every 12 months.

    In the model: Flat entrance doors, Stair doors and fire door checks

  8. The dry riser and the stair vent kept working

    Who
    The responsible person
    What
    Keep the facilities provided for firefighters, here the dry riser and its inlet, and the vent at the head of the stair with its switch and the detectors that open it, maintained in efficient working order and good repair.
    When
    Wherever facilities are provided for firefighters: this block.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 38Where necessary in order to safeguard the safety of fire-fighters, the facilities and equipment provided for them, such as the fire main and its inlet, are subject to a suitable system of maintenance and maintained in an efficient state, in efficient working order and in good repair.

    In the model: Dry riser, Dry riser inlet, Fire service vent at the head of the stair, Fire service switch for the stair vent

  9. Fire safety information handed on

    Who
    The outgoing responsible person, and the new one; at completion, whoever carried out the building work
    What
    When another person becomes the responsible person, the outgoing one gives the new one, among other things, the records of the fire risk assessments and their reviews, who was appointed to help with them, and any fire safety information handed over when the block was built (an older block may have none); the new one keeps them. That information, on the design, construction and fire safety equipment of the block, is given to the responsible person by whoever carried out the building work, no later than completion or occupation.
    When
    Whenever the responsible person changes; the builder’s information when the block was built, as Part B applied to the work.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 22AWhen one responsible person takes over from another, the outgoing one must give the new one the fire safety information they hold, including the records of the risk assessments and reviews and any fire safety information given under regulation 38 of the Building Regulations 2010; a responsible person must keep records of that information.
    • LawBuilding Regulations 2010, Regulation 38(1) to (3)Where building work erects or extends a building to which the Fire Safety Order will apply, or goes with a change of use that brings the Order to it, and Part B applies to the work, the person carrying out the work must give the responsible person fire safety information, about the design and construction of the building and its services, fittings and equipment, that will help them operate and maintain it with reasonable safety, no later than completion or occupation; the responsible person acknowledges receiving it.

    In the model: Fire action notice and fire safety records

  10. Smoke alarms in rented flats

    Who
    The landlord of each rented flat
    What
    Make sure there is a smoke alarm on each storey of the flat that has a room used as living accommodation, and, where a fixed combustion appliance other than a gas cooker is in a room used as living accommodation, a carbon monoxide alarm in that room. Check each alarm works on the day a new tenancy begins. When a tenant reports an alarm, it must be checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.
    When
    Each flat let on a tenancy the regulations cover, which is most residential tenancies, private and social.
    In this building
    Applies here at every height.
    • Ongoing dutySmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)A relevant landlord of a specified tenancy must ensure that, while the premises are occupied under it, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, a carbon monoxide alarm is equipped in any such room containing a fixed combustion appliance other than a gas cooker, and the alarms are checked to be in proper working order on the day a new tenancy begins. When a tenant reports an alarm, it must be checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.

    In the model: Smoke alarms in the flats

  11. Electrical safety in rented flats

    Who
    The landlord of each rented flat, private or social (all social tenancies since 1 May 2026)
    What
    Make sure the electrical safety standards are met while the flat is let. Have every electrical installation in it inspected and tested by a qualified person before the tenancy starts and at intervals of no more than 5 years, or sooner if the last report says so; give each tenant a copy of the report within 28 days of the inspection, and a new tenant a copy before they move in; and where the report finds further investigation or remedial work is needed, have it done within 28 days or any shorter period it sets.
    When
    Each flat let on a tenancy the regulations cover: the tenant’s only or main home, let for rent, and not a long lease or another kind of tenancy their Schedule 1 leaves out.
    In this building
    Applies here at every height.
    • Ongoing dutyThe Electrical Safety Standards in the Private Rented Sector and Social Rented Sector (England) Regulations 2020, Regulations 2, 3(1) to (4) and Schedule 1A landlord who grants or intends to grant a specified tenancy, a tenancy of a home as the tenant’s only or main residence, for rent, not of a kind Schedule 1 excludes (such as a long lease or a home shared with the landlord), must ensure the electrical safety standards are met while it is occupied, and have every electrical installation inspected and tested by a qualified person before the tenancy starts and at intervals of no more than 5 years, or sooner if the last report says so; give each tenant a copy of the report within 28 days of the inspection, and a new tenant a copy before they move in; and, where the report shows the standards may not be met and requires further investigation or remedial work, have it done by a qualified person within 28 days or any shorter period the report sets. Since 1 May 2026 the regulations reach every social tenancy as well as private ones.

Background reading

How the documents behind this building fit together, and where its standards came from. Each is a guide of its own, with its sources.

Guides behind this model

Read more on the topics this building shows.

See all 8 guides linked from this model

What this model assumes

  • Illustrative: drawn to show how the guidance fits together. The plan, the rooms and the finishes are modelled on recent planning applications for blocks of this type, simplified.
  • Top storey 8.4 m above ground level: a ground storey and three upper storeys, all flats, 2.8 m floor to floor.
  • No sprinklers: ADB Volume 1 para 7.4 asks for them only where the top storey is more than 11 m above ground.
  • The ground storey is about 402 m2 and each floor above about 387 m2, where the balconies are set into the plate, with four flats on every floor. On each floor above the ground there are three flats with three bedrooms for four people (80.5 to 90.1 m2, against 74 m2) and one flat with two bedrooms for three people (65.9 m2, against 61 m2); on the ground floor two flats with two bedrooms for four people (72.6 to 90.9 m2, against 70 m2) and two flats with one bedroom for two people (62.5 to 81.7 m2, against 50 m2). Each figure is the flat’s area inside its walls, against the area the Nationally Described Space Standard sets for that size of flat.
  • Stay put: the people in the flat on fire, or in the common parts if the fire is there, leave and call the fire service; other residents not directly affected are expected to stay in their flats unless the fire service tells them to leave, and anyone who wishes to leave is not stopped (LGA guide paras 19.1 and 19.2). The strategy depends on the walls, floors and doors between the flats being kept as built, and the fire risk assessment keeps it under review. There is no communal fire alarm.
  • Fire service vehicle access level is ground level all round: the site is flat.
  • Hose distances are measured along the middle of each stair flight on its slope, across landings and rooms on plan, by a route a hose can be laid. From the pump appliance they start at its pump delivery, 0.8 m up at the rear.
  • The external walls are masonry with a brick outer leaf, and the roofs plain concrete tiles. The walls are taken to be class A2-s1, d0 or better as ADB Volume 1 Table 10.1 asks; the model does not show any product’s classification.
  • There is no gas supply in the stair (ADB Volume 1 para 3.83).
  • The flats are new and let on tenancies, so their alarms are Grade D1, Category LD2 (BS 5839-6 Table 1).
  • The stair stops at the top floor. A locked hatch over its top landing, reached by a fixed ladder, opens on to the flat roof for maintenance.
  • The lift is an electric traction lift without a machine room, an ordinary passenger lift, not an evacuation lift.
  • The top floor’s ceiling is the concrete roof slab. Under each pitched roof, the wall between the flats below is carried up through the roof space to the underside of the tiles.
  • The Fire risk assessment tab says what an assessor would look at were this an existing block. It is guidance on what to look at, not an assessment of this or any real building.
  • Where neither a part’s own text nor the guidance it cites settles a fire resistance period, the model assumes one from Approved Document B Volume 1, taking the more onerous value where the guidance leaves the choice to the fire risk assessment: the meter cupboard takes the stair’s REI 60, with an E 30 Sa door. Each such value is marked as assumed where it is shown.

Approved Document B is the 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments, read for this building on 13 November 2026, with paras 3.62, 3.84, 3.88, 13.4 and 14.8 to 14.10, Diagram 13.1, Table 13.1 and Diagram D4 read again for its redesign (13.4 with its diagram and table on 14 November 2026), and paras 3.14, 3.15, 3.18, 3.27, 3.30, 3.32, 3.59 to 3.62, 3.81 to 3.84, 3.97 to 3.99, 3.102, 9.24, 14.3 and B22, Table 3.1, Diagrams 3.2, 3.9 and D4 and Table C1 read again on 14 November 2026 for the re-planned core, flats and refuse room. BS 9991:2024 clause 9 (ladders) was read in BSI’s own document on 13 November 2026, and clauses 7.1, 7.2.4 and 15.1 with Figure 31 on 14 November 2026. The Fire Safety (England) Regulations 2022 regulations 3 and 8 and the Fire Safety (Residential Evacuation Plans) (England) Regulations 2025 regulations 1 and 3 were read on legislation.gov.uk on 14 November 2026. The British Standard references reuse readings made for the 12-storey tower on 10 and 11 November 2026: BS 9990:2015, BS 5839-6:2019+A1:2020, BS 5266-1:2025 and BS 5906:2005. The Local Government Association guide is its 2011 edition, which the LGA says is no longer comprehensive; it is cited for stay put (paras 18.4, 19.1 and 19.2, the first and last read again on 14 November 2026), for charging in stores, and, in the existing building content, for existing flat doors, routine testing, lift motor rooms in older blocks and the history of the standards. Where ADB names an older edition of a standard, the reference says so. For the existing building content, read on 14 November 2026: BS 9792:2025 (clauses 1, 5, 7 to 9, 13, 15.3, 15.5, 15.7, 15.10 to 15.12, 16 and 19 to 21) and PAS 9980:2022 (clause 1) in BSI’s own documents, BS 9991:2024 clause 7.4.1, ADB paras 0.9, 3.29, 5.11, 7.11, 7.15, 8.4, 9.1, 9.24, 10.4, 10.10, C11 and C12, the LGA guide’s paras 62, 81 and 82 and its Appendix 1, CP 3 Chapter IV Part 1 in its 1962 and 1971 editions (historical, superseded), and the Fire Safety Act 2021, the Fire Safety Order, the Building Regulations 2010 regulation 38 and the Electrical Safety Standards regulations on legislation.gov.uk. Read on 15 November 2026 for the source check: the forewords of BS 9792:2025 and BS 9991:2024, BS 9792 clauses 15.4 and 15.7 (on the page images), the LGA guide’s paras 2.1 to 3.1, and regulation 9 of the Fire Safety (England) Regulations 2022 and regulation 3 of the Electrical Safety Standards regulations on legislation.gov.uk. Read on 16 November 2026, for lift motor rooms in older blocks: the LGA guide’s sections 16 (the list after para 16.10) and 43 and paras 44.2, 44.19, 54.1, 54.9, 58.3 and 63.4, and ADB para 3.108 again.

Technical review by INFIRISK editorial: 16 November 2026 · Next review: 16 February 2027