Roof space over the flats
- Compartmentation
In a block built now, where a roof space runs over more than one flat, the walls between the flats below are carried up through it:
- to the underside of the roof covering
- fire-stopped where they meet it
- carried across any eaves
So the roof space over one flat is divided from the next.
- A line of compartment walls is not completed by fitting cavity barriers above them.
Here the top floor’s ceiling is the concrete roof slab, and each of the two pitched roofs covers a roof space over two flats, one north and one south.
- On the line of the wall between those two flats a wall, as thick as that wall, is carried up through the roof space to the underside of the tiles, so the roof space over each flat is divided from the next.
- Under the east roof it runs on across the roof space over the east lobby too, standing on the lobby’s concrete ceiling, so the division is unbroken from eaves to eaves.
- The lobby’s own walls, the two end walls and the east wall that stand between it and the flats around it, are carried up under the east roof in the same way, so the roof space over the lobby is closed off from the roof spaces over those flats (the walls between each flat and a lobby are compartment walls too, paras 7.11 and 7.15).
- The model draws no hatch into any roof space.
In old blocks of flats the walls between flats may not go up through the roof void, letting a fire spread across several flats.
- Problems arise in modern low-rise pitched-roof buildings too: fire spreading through the roof voids over a modern sheltered housing scheme has led to at least one death.
- So an assessor tries to look into roof voids even in a Type 1 assessment, sampling them, and records it when that was not practicable (BS 9792 15.7 b)).
- Fires have been known to spread across the top of blocks through the roof voids (LGA guide 18.4).
REI 60The walls carried up through the roof space continue the compartment walls between the flats, and between the east lobby and the flats, REI 60, to the underside of the roof covering (paras 7.11 and 7.15).
- LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
- GuidanceADB Vol 1, paras 7.11 and 7.15, with para 5.11Compartment walls in a top storey beneath a roof should be continued through the roof space (para 7.11). Where a compartment wall meets the roof, the provisions are those for houses (para 7.15): the wall should meet the underside of the roof covering or deck, with fire-stopping to keep its fire resistance continuous, and be continued across any eaves (para 5.11).
- GuidanceADB Vol 1, para 8.4It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment walls should extend to the underside of the floor or roof above.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentary (opens in a new tab)A Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.Why it applies here: BS 9792 is the code of practice for fire risk assessments in housing, and its scope takes in purpose-built blocks of flats such as this one (clause 1 b)).
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary b) (opens in a new tab)Fire can spread through a roof void, whether it starts there or reaches it from a flat below. In old blocks of flats the walls between flats might not extend through the roof void, as building regulations would now require, letting a fire spread across several flats; problems can also arise in modern low-rise pitched-roof buildings such as sheltered housing, and fire spreading within the roof voids over a modern sheltered scheme has led to at least one death. So the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and makes clear in the assessment when access was not practicable.Why it applies here: This block has two pitched roofs, and each roof space runs over two of the top floor flats.
- GuidanceFire safety in purpose-built blocks of flats, paras 18.4 and 19.2Fires have been known to spread beyond the flat of origin to involve other flats, or across the top of blocks through the roof voids, and total evacuation has then sometimes been necessary; such fires are rare, and usually the fault of failings in the construction. A stay put policy does not mean that residents not directly involved who wish to leave should be prevented from doing so.
INFIRISK guides
No INFIRISK guide on this yet.
What a fire risk assessor checks
The roof spaces, on at least a sample: whether the walls between the flats run up to the underside of the roof covering, and the fire stopping where they meet it
Benchmark: BS 9792 clause 5 and 15.7 b): where a building has a pitched roof, even a Type 1 assessment tries to include the roof voids, sampling them, and records it if access was not practicable.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5, commentaryA Type 1 assessment is non-intrusive. As well as a sample of the flat entrance doors, it extends to the roof voids of a building with a pitched roof unless access is impractical, which is recorded; it covers, so far as reasonably practicable and without opening anything up, the separating construction between the flats and the common parts, for example fire stopping at sample places in service risers; and it normally lifts a sample of reachable false ceiling tiles and opens a sample of service risers where access is practicable.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary b)Fire can spread through a roof void, whether it starts there or reaches it from a flat below. In old blocks of flats the walls between flats might not extend through the roof void, as building regulations would now require, letting a fire spread across several flats; problems can also arise in modern low-rise pitched-roof buildings such as sheltered housing, and fire spreading within the roof voids over a modern sheltered scheme has led to at least one death. So the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and makes clear in the assessment when access was not practicable.
A defect the source namesIn old blocks of flats the walls between flats might not extend through the roof void, which can let a fire spread across several flats.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary b)Fire can spread through a roof void, whether it starts there or reaches it from a flat below. In old blocks of flats the walls between flats might not extend through the roof void, as building regulations would now require, letting a fire spread across several flats; problems can also arise in modern low-rise pitched-roof buildings such as sheltered housing, and fire spreading within the roof voids over a modern sheltered scheme has led to at least one death. So the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and makes clear in the assessment when access was not practicable.
How far the walls between flats should go
Benchmark: For a building built now: Approved Document B says compartment walls in a top storey beneath a roof should be continued through the roof space, meet the underside of the roof covering with fire-stopping and be carried across any eaves, and not be completed by cavity barriers above them (paras 7.11, 7.15, 5.11 and 8.4).
- GuidanceADB Vol 1, paras 7.11 and 7.15, with para 5.11Compartment walls in a top storey beneath a roof should be continued through the roof space (para 7.11). Where a compartment wall meets the roof, the provisions are those for houses (para 7.15): the wall should meet the underside of the roof covering or deck, with fire-stopping to keep its fire resistance continuous, and be continued across any eaves (para 5.11).
- GuidanceADB Vol 1, para 8.4It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment walls should extend to the underside of the floor or roof above.