INFIRISK 3D buildings · 2(a) Residential (institutional): care home

Care home

A 70-bed care home on three floors, the top one in the roof, drawn to show care home fire safety in a new building. If there is a fire, residents are moved sideways through fire doors into the next protected area, so progressive horizontal evacuation keeps most of them where they are while staff deal with the fire. Every bedroom is fitted out with its en-suite, and the model draws the fire design where it is: the protected areas, the compartment walls and doors, the stairs, refuges and lifts, the sprinklers and the alarm. Drawn from a real consented scheme’s layout, not any real address: illustrative, to show how the guidance fits together.

This building is illustrative. It is drawn to show how the guidance fits together, and it is not a fire strategy or a design for any real building. For your own building, speak to a competent fire engineer or fire risk assessor.

Every part of the building

The roof

Compartment walls in the roof space

  • Compartmentation
Show in the 3D model

In the top storey of a care home beneath a roof, ADB asks for a compartment wall to continue through the roof space, meeting the underside of the roof covering or deck with fire-stopping and continuing across any eaves.

  • Completing the line with cavity barriers above is not appropriate, and cavity barriers belong at the edges of cavities and at the junctions with compartment walls and floors.
  • Where the fire-resisting construction of a protected corridor stops short of the roof, ADB asks for cavity barriers on its line or a fire-resisting ceiling of at least EI 30.
  • A cavity between a roof and a ceiling is limited to 20 m in any direction.
  • To limit spread over the roof, ADB asks for a 1500 mm zone either side of the wall with a covering of the class it sets on a deck of class A2-s3, d2 or better, or for the wall to extend through the roof.

Regulation 28 report 2022-0043 records the inquest jury’s findings after the Newgrange care home fire, 2017: inadequate compartmentation in the roof space let the fire spread faster than expected and the roof collapse.

Here the second floor is in the roof, so its compartment walls rise through the roof space to the underside of the deck. The roof in front of them fades while this part is open, so they can be seen.

  • Along the bedroom wing the lengths of roof space between the walls, and between the last wall and the east gable, are about 16.9, 17.2 and 11.7 m, each under the 20 m of Table 9.1.
  • In the service wing a cavity barrier on the line of the dining room’s south wall keeps every length under 20 m too.
  • Cavity barriers are not used to complete a wall: the wall goes up to the deck.

REI 60The compartment walls between protected areas, REI 60, carry on through the roof space to the underside of the roof deck, so they keep that period there.

  • GuidanceADB Vol 2, para 8.21“Compartment walls in a top storey beneath a roof should be continued through the roof space.”
  • GuidanceADB Vol 2, para 8.25A compartment wall should meet the underside of the roof covering or deck, with fire-stopping to maintain the continuity of fire resistance, and be continued across any eaves.
  • GuidanceADB Vol 2, para 8.26To reduce the risk of fire spreading over the roof from one compartment to another, a 1500 mm wide zone of the roof, either side of the wall, should have a covering of the class ADB sets, on a substrate or deck of a material rated class A2-s3, d2 or better.
  • GuidanceADB Vol 2, para 8.29As an alternative to the 1500 mm zone, the compartment wall may extend through the roof for at least 375 mm above the adjoining roof covering where the height difference between the two roofs is less than 375 mm, or at least 200 mm where the difference is 375 mm or more or the coverings either side are of the best class.
  • GuidanceADB Vol 2, para 9.3Cavity barriers should be provided at the edges of cavities, at the junction between an external cavity wall and every compartment floor and compartment wall, and at the junction between an internal cavity wall and every compartment floor, compartment wall or other fire resisting barrier.
  • GuidanceADB Vol 2, para 9.4“It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should extend to the underside of the floor or roof above.”
  • GuidanceADB Vol 2, para 9.5Where the fire resisting construction of a protected escape route is not carried to the underside of the roof covering at the top storey, the cavity above should be fitted with cavity barriers on the line of the enclosure or enclosed on its lower side by a fire resisting ceiling (minimum EI 30) that extends throughout.
  • GuidanceADB Vol 2, Table 9.1Maximum dimension of an undivided cavity in a building other than a dwelling: 20 m between a roof and a ceiling; 20 m for any other cavity with a surface of class C-s3, d2 or better, and 10 m for worse.Why it applies here: Every length of roof space between walls is under 20 m: about 16.9, 17.2 and 11.7 m along the wing, with a cavity barrier in the service wing.
  • GuidanceRegulation 28 report to prevent future deaths 2022-0043, section 3The inquest jury found a fire in a care home had been started by resistive heating in electrical wiring at ceiling level in a linen cupboard, and that inadequate compartmentation in the roof space let it spread faster than expected and led to the roof collapsing. Its conclusion was an accidental fire contributed to by inadequate compartmentation in the roof space.

What a fire risk assessor checks

  1. Hot work by contractors is carried out only under a permit to work, with the area checked afterwards

    Benchmark: The 2006 guide asks for a written permit to work for hot work near flammable materials, and for the area to be checked afterwards for ignition or smouldering.

    • GuidanceFire safety risk assessment: residential care premises, pages 18 and 53Areas where hot work such as welding has been carried out are checked afterwards for ignition or smouldering, and a written permit to work controls hot work near flammable materials.
  2. Holes made for new services through fire-resisting walls and floors are fire-stopped

    Benchmark: The 2006 guide says unsealed holes round services let fire and smoke spread, and that openings made through fire-resisting walls and floors are fire stopped by competent contractors. The inquest into the Newgrange care home fire, 2017, found inadequate compartmentation in the roof space (Regulation 28 report 2022-0043).

    • GuidanceFire safety risk assessment: residential care premises, pages 53 and 124Unsealed holes where pipes, cables and other services pass through walls and ceilings let smoke and fire spread, and openings made by services through fire-resisting walls and floors are fire stopped by competent contractors.
    • GuidanceRegulation 28 report to prevent future deaths 2022-0043, section 3The inquest jury found a fire in a care home had been started by resistive heating in electrical wiring at ceiling level in a linen cupboard, and that inadequate compartmentation in the roof space let it spread faster than expected and led to the roof collapsing. Its conclusion was an accidental fire contributed to by inadequate compartmentation in the roof space.
  3. The roof void is not used for storage

    Benchmark: The 2006 guide asks for roof voids not to be used to store combustible material.

    • GuidanceFire safety risk assessment: residential care premises, page 48Voids, including roof voids, should not be used to store combustible material, and are sealed off or kept open for inspection and the removal of combustible material.
Show in the 3D model

Vent at the head of Stair 2

Where an evacuation lift’s lobby is protected by natural smoke ventilation, BS 9991 recommends a vent at the head of the stairway as well.

  • With a smoke shaft in the lobby or corridor it is a smoke control damper at as high a level as practicable on the top storey of the stairway, with a free area of at least 1 m2.
  • With vents to outside in the corridor or lobby it is a vent at the top of the stairway of at least 0.7 m2 aerodynamic free area.
  • It opens automatically on smoke detection in the lobby or corridor next to the stair.

Here the vent is a 1 m2 vent at the head of Stair 2, where the stair meets the roof, for Lift 2.

  • There is none at the head of Stair 1 or Stair 3, because their lifts are not evacuation lifts or they have none.
  • StandardBS 9991, clause 20.2.2.2 (opens in a new tab)A natural ventilation system has either vents to outside of at least 0.9 m2 aerodynamic free area next to the stair and at least 0.7 m2 at the top of the stairway, or a smoke shaft in the lobby or corridor with a smoke control damper of at least 1 m2 at the top storey of the stairway.Why it applies here: Clause 56.2 sends the smoke protection of evacuation lift lobbies in care homes to this ventilation.
  • StandardBS 9991, clause 56.2 (opens in a new tab)In the lobbies of evacuation lifts in care homes the standard recommends smoke ventilation in the adjacent areas, natural per 20.2.2.2 or mechanical, or a pressure differential system to the lobby.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Roof covering and the zone at each compartment wall

Fire can also spread over a roof from one compartment to another.

  • ADB asks for a 1500 mm wide zone of the roof either side of a compartment wall to have a covering of the class it sets, on a deck or substrate of class A2-s3, d2 or better, or for the wall to extend through the roof.
  • The option in paragraph 8.27, of a combustible substrate bedded in mortar over the wall, is not open to a residential (institutional) building.
  • ADB Table 14.1 accepts only a BROOF(t4) covering on any part of a roof less than 6 m from the relevant boundary.

Here the roof covering runs unbroken over each compartment wall, and the 1500 mm zone either side of each wall is part of it.

  • The option for a combustible substrate bedded in mortar over the wall is not open to a care home.
  • GuidanceADB Vol 2, para 8.26A 1500 mm wide zone of the roof, either side of a compartment wall, should have a covering of the class ADB sets, on a substrate or deck of a material rated class A2-s3, d2 or better, to reduce the risk of fire spreading over the roof from one compartment to another.
  • GuidanceADB Vol 2, para 8.27A substrate of class B-s3, d2 or worse, fully bedded in mortar for the width of the wall, may extend over the wall in buildings up to 15 m high in the residential purpose groups other than ‘residential (institutional)’ (purpose group 2(a)), and in some other purpose groups. It is not open to a care home.
  • GuidanceADB Vol 2, para 8.29As an alternative to the 1500 mm zone, the compartment wall may extend through the roof for at least 375 mm or 200 mm above the adjoining roof covering, depending on the height difference between the roofs and the class of the coverings.
  • GuidanceADB Vol 2, Table 14.1Limitations on roof coverings by distance from the relevant boundary: at less than 6 m only a BROOF(t4) covering is acceptable, and from 6 m further classes become acceptable with distance, subject to the table’s notes on building size.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

The first and second floors

Protected areas on every floor

  • Means of escape
  • Compartmentation
Show in the 3D model

In a care home where residents need help to get out, the usual plan is progressive horizontal evacuation.

  • Staff move residents sideways, through a fire door, into the next protected area, not straight outside.
  • ADB asks for each storey used for the care of residents to be divided by compartment walls into at least three protected areas, with every floor a compartment floor, and for every protected area to have at least two exits to adjoining protected areas (para 2.37).
  • At a wing end there is only one neighbour, so there is a second way out by a protected stair, the arrangement BS 9991 draws in Figure 48.
  • A protected area holds no more than 10 residents’ beds, and fewer where the assessment of the staff available and the help residents need says so.
  • It needs floor space for its own occupants and those of the largest adjoining area. BS 9991 sizes that holding space at 2 m2 a person, says bedrooms are not holding space, and expects that residents will not normally be taken outside.
  • The 2006 guide describes the same idea for existing homes: residents are moved from the area of a fire to the next protected area, then on, and down a stair if it comes to that.

Here every floor has at least three protected areas: five on the ground floor and six on each of the first and second floors.

  • The three along the bedroom wing hold 10, 8 and 3 beds on the ground and first floors and 8, 6 and 2 on the second, and wing west on the ground and first floors holds 10 beds, the most ADB allows: a ceiling, not a target.
  • BS 9991:2024 clause 55.2.2 recommends at least three sub-compartments a floor, none over 750 m2; the largest here is about 313 m2.
  • At the ends of the wing there is only one neighbour: the wing’s east end on every floor and the service wing’s north end have one exit into the next protected area and a second way out by a protected stair.
  • BS 9991 draws exactly this arrangement for a straight wing (Figure 48), and one real scheme’s fire statement does the same in practice.
  • It does not meet the words of para 2.37 literally: in a real building a fire engineer would justify it in the fire strategy.
  • At mealtimes the day areas hold more people than their beds, so a fire in one sends them both ways, into the areas on either side.
  • Take ten residents who all need two staff, with seven waking staff at night, an INFIRISK teaching assumption: at about 2.5 minutes a resident for two staff, one pair needs about 25 minutes and two pairs about 12.5, against the 2006 guide’s 2½ minutes for a whole protected area.
  • So the number of beds the assessment of staff and dependency allows (para 2.39) is the figure that counts.

Good practice is to review the fire risk assessment every year, and more often may be appropriate in a care home, where residents’ dependency and a complex evacuation raise the risk.

  • GuidanceADB Vol 2, para 2.34“In care homes for the elderly, some or all residents are likely to need help to evacuate. Buildings should generally be designed for progressive horizontal evacuation (PHE) in accordance with paragraphs 2.35 to 2.46.”
  • GuidanceADB Vol 2, para 2.35PHE needs the areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors. Protected areas are a place of relative safety, from which further evacuation can be made if necessary.
  • GuidanceADB Vol 2, para 2.36“Each storey used for the care of residents should be divided by compartment walls into at least three protected areas. All floors should be compartment floors.”
  • GuidanceADB Vol 2, para 2.37“Every protected area should have a minimum of two exits to adjoining protected areas.” Travel distance within a protected area should not exceed the distance in Table 2.1 to the exit to the adjoining area, nor 64 m from any point to a storey exit or a final exit.Why it applies here: The wing’s east end on every floor and the service wing’s north end have one neighbour, so each has a second way out by a protected stair.
  • GuidanceADB Vol 2, para 2.39The number of residents’ beds in protected areas should be based on an assessment of the number of staff likely to be available and the level of assistance residents may need. The maximum number of beds in one protected area should not exceed 10, but may need to be lower depending on the assessment.Why it applies here: Wing west holds 10 beds on the ground and first floors, the ceiling ADB sets, so the staffing assessment decides how many beds it really holds.
  • GuidanceADB Vol 2, para 2.40A protected area used for horizontal evacuation from an adjoining protected area should have a floor area able to accommodate its own occupants plus those from the largest adjoining protected area.
  • GuidanceADB Vol 2, Diagram 2.11Shows progressive horizontal evacuation in a care home: compartment walls with fire doorsets divide a corridor into protected areas, with an escape route from each area to the next, a storey exit or a final exit. Its note says bedrooms and all ancillary accommodation should be enclosed in fire-resisting construction.
  • StandardBS 9991, clause 55.2.2 (opens in a new tab)For a progressive horizontal evacuation strategy the standard recommends at least three sub-compartments on each floor, none larger than 750 m2, each with at least two exits to an adjoining sub-compartment or an escape route, with bedrooms and ancillary rooms enclosed in 30 minute construction. Residents are evacuated to an adjoining corridor or communal room sized for both populations at 2 m2 a person, bedrooms are not used as holding space, and residents will not normally be evacuated outside the building.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • StandardBS 9991, Figure 48 (opens in a new tab)Shows a care home wing with a stair at each end, divided into sub-compartments by two sub-compartment walls with E 30 Sa or FD 30 S doors, with 60 minute construction round the stairs. The figure does not give the period of the sub-compartment walls themselves.Why it applies here: It is the standard’s picture of an end area with one neighbour and a stair, the arrangement ADB’s wording for two exits leaves to the designer.
  • GuidanceFire safety risk assessment: residential care premises, page 68In existing care premises, protected areas are separated on the same level by walls and doors of at least 30 minutes. They need capacity for their own occupants and those of the largest neighbouring area, progressive movement through adjoining protected areas, and a way out by stairs if that becomes necessary. The time to move people into the next area is best found by a simulated evacuation assuming the lowest staffing, as at night.
  • GuidanceFire safety risk assessment: residential care premises, pages 68 to 70It should be possible, in normal operating conditions, to evacuate any protected area in 2½ minutes using the staff present. The time is checked by a simulated evacuation assuming the lowest staffing, as at night, and the 2½ minutes is a starting point for the assessment. If the movement times are excessive the options include a smaller protected area, more staff, fewer residents in the area or a sprinkler system.
  • GuidanceCare and nursing homes: short term staffing shortages and implications for evacuation strategies and operational response, section 5.6Research has shown that it can take two staff about 2.5 minutes to evacuate each resident with impaired mobility, so moving every resident into an adjacent protected area could take more than twenty minutes. The guidance cites no study.
  • StandardPAS 79 Fire risk assessment. Code of practice (parts 1 and 2), PAS 79-1:2020, clause 20 (opens in a new tab)The specification says a fire risk assessment stops being valid after a material alteration, a significant change such as more residents with impairments, a change in the fire precautions, or a fire. PAS 79-1 says there is no set frequency for review: an annual review is the usual good practice, and more often may be appropriate where residents’ dependency and a complex evacuation raise the risk, which it names as true of care homes.Why it applies here: A care home’s assessment has to follow the residents’ changing needs, and PAS 79-1 is the code of practice for how an assessment is made and reviewed.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. A simulated evacuation, timed at the lowest staffing, as at night, and the routes between protected areas kept clear

    Benchmark: The 2006 guide asks for any protected area to be evacuable in 2½ minutes with the staff present, as a starting point, and checks it by a simulated evacuation at the lowest staffing. The Fire Safety Order requires the responsible person to keep the routes to the exits, and the exits, clear.

    • GuidanceFire safety risk assessment: residential care premises, pages 68 to 70It should be possible, in normal operating conditions, to evacuate any protected area in 2½ minutes using the staff present. The time is checked by a simulated evacuation assuming the lowest staffing, as at night, and the 2½ minutes is a starting point for the assessment.
    • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.
  2. Fire drills at least once a year, or as the assessment sets, with one at night or simulating the night’s staffing, involving residents where their condition allows

    Benchmark: The 2006 guide asks for a drill at least annually or as the fire risk assessment determines, simulated with residents where their condition permits, and advises one drill at night or simulating night time conditions.

    • GuidanceFire safety risk assessment: residential care premises, page 115A fire drill is carried out at least annually or as the fire risk assessment determines. A properly simulated drill includes residents, or a significant number of them, where their condition permits, and it is advisable to hold one drill at night or to simulate night time conditions, including the applicable staffing levels.
  3. The assessment and the size of the protected areas are reviewed when residents’ dependency rises

    Benchmark: The 2006 guide asks for the number and size of protected areas to be reviewed when dependency changes significantly, and the Fire Safety Order requires the assessment to be reviewed regularly and after a significant change.

    • GuidanceFire safety risk assessment: residential care premises, page 29In a purpose-built care home the level of structural protection is likely to be adequate, but the number and size of protected areas may need to be reviewed if circumstances change significantly, for example when residents’ dependency increases.
    • GuidanceFire safety risk assessment: residential care premises, page 72The number of resident beds allowed in each sub-compartment should depend on the minimum number of staff who are awake and available, which is normally the night-time staffing level, and the risk assessment should identify the number of staff needed to carry out the emergency plan.
    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.
Show in the 3D model

Doors between protected areas (first and second floors)

  • Means of escape
  • Compartmentation
Show in the 3D model

The doors in the walls between protected areas are the doors residents and staff cross in a fire.

  • So ADB counts a door in a compartment wall as a storey exit when the building is planned for progressive horizontal evacuation.
  • ADB Table C1 asks for such a door to match the wall it is in, with the Sa smoke suffix added when it is used for evacuation, so a 60 minute compartment wall takes an E 60 Sa door.
  • Where a closer on a corridor door could be an obstacle to residents, ADB says a hold-open device to BS EN 1155 is appropriate, released by the fire detection and alarm system.
  • Door openings should take up no more than 25 per cent of the length of a compartment wall unless the doors give insulation as well as integrity.
  • BS 9991’s clause for communal facilities recommends corridors used for evacuation at least 1 200 mm wide and door openings at least 850 mm clear, so wheelchairs get through.

Here every compartment doorset on the first and second floors is a pair of 0.90 m leaves, E 60 Sa, held open by devices that the alarm releases, so one leaf gives about 850 mm clear.

  • The first fire signal releases every device in the building.
  • The doorways take between about 6 and 20 per cent of the length of each compartment line, every one inside the 25 per cent that ADB’s para C8 allows for doors that give no insulation.
In existing buildings

Older homes were often divided by a set of fire-resisting self-closing doors across a corridor rather than by full compartment walls.

  • The 2006 guide says reducing the size of a protected area may be no more than that (page 70).

E 60 SaA door in a compartment wall between protected areas takes the same period as the wall, 60 minutes here, with the Sa smoke suffix because it is used for progressive horizontal evacuation (Table C1 item 2(e)).

  • GuidanceADB Vol 2, Table C1, item 2(e)A door in a compartment wall that is not one of the other kinds listed should be the “same as for the wall in which it is fitted, but add Sa(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1”.
  • GuidanceADB Vol 2, para 2.45(b)If doors fitted with a self-closing device could present an obstacle to residents, hold-open devices in accordance with BS EN 1155 are appropriate on circulation spaces.
  • GuidanceADB Vol 2, para C6(b)If a self-closing device would interfere with the normal approved use of the building, self-closing fire doors may be held open by an automatic release mechanism activated by an automatic fire detection and alarm system.
  • GuidanceADB Vol 2, para C8Fire doorsets often give no significant insulation. Unless they give both integrity and insulation, a maximum of 25% of the length of a compartment wall should consist of door openings. Where a clear space can be kept on both sides of the doorway, the percentage may be greater.Why it applies here: The doorway or doorways in each compartment line are under 25 per cent of its length.
  • GuidanceADB Vol 2, Appendix AStorey exit: “If an institutional building is planned to enable progressive horizontal evacuation, a door in a compartment wall is considered a storey exit for the purposes of requirement B1.”
  • StandardBS 9991, clause 55.3.3 (opens in a new tab)The standard recommends that corridors used for evacuation are at least 1 200 mm wide and that doors have an effective clear opening of at least 850 mm, so wheelchairs can use them. Where double doors are fitted, one of them gives the 850 mm.Why it applies here: Each doorset is a pair of 0.90 m leaves, so one leaf gives about 850 mm clear.

What a fire risk assessor checks

  1. Hold-open devices on the compartment doors release when the fire alarm signals, and the doors close on to their frames

    Benchmark: ADB says hold-open devices to BS EN 1155 are appropriate on circulation spaces where a self-closing device could be an obstacle to residents, and lets them be released by the fire detection and alarm system. The Fire Safety Order requires the responsible person to keep the premises and the safety devices in efficient working order.

    • GuidanceADB Vol 2, para C6(b)If a self-closing device would interfere with the normal approved use of the building, self-closing fire doors may be held open by an automatic release mechanism activated by an automatic fire detection and alarm system.
    • GuidanceADB Vol 2, para 2.45(b)If doors fitted with a self-closing device could present an obstacle to residents, hold-open devices in accordance with BS EN 1155 are appropriate on circulation spaces.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
  2. The compartment doors are checked monthly to close fully, with their frames and seals intact, and the doors on hold-open devices release when they are tested

    Benchmark: The 2006 guide asks for a monthly check that fire doors close correctly with frames and seals intact, and its sample checklist asks whether a linked door holder releases when the alarm is tested. BS 9991 recommends that hold-open devices are tested monthly, by simulating a power failure or the alarm, and the result recorded.

    • GuidanceFire safety risk assessment: residential care premises, page 34Daily, doors on escape routes are checked to swing freely and close fully, and a routine closes all compartmentation corridor fire doors at night. Weekly, the fire detection and warning systems and manually operated devices are tested. Monthly, every fire door is checked to work and close correctly with its frame and seals intact, and the emergency lighting is tested. Every six months a competent person tests the emergency lighting and the detection and warning system.
    • GuidanceFire safety risk assessment: residential care premises, page 118The sample maintenance checklist asks, in its weekly checks, whether the alarm test made the linked fire protection systems operate, giving a magnetic door holder releasing as the example.
    • StandardBS 9991, Annex I, I.4.8The standard recommends that doors held open by hold-open devices are tested monthly, by simulating a power failure or a fire alarm, and that the results are recorded.
  3. Every week a fire alarm signal releases every hold-open door among the compartment doors and each is seen to close. The test is done at a quiet time, or with a warning first, because a door swinging shut can hurt a frail resident

    Benchmark: BS 7273-4 recommends a weekly release test of every door release mechanism, at about the same time each week, and its note says doors released in working hours can affect residents.

    • StandardBS 7273-4 Code of practice for the operation of fire protection measures. Actuation of release mechanisms for doors, clause 21.1.2The standard recommends that every week a fire alarm signal releases every door release mechanism and each door is seen to close, at about the same time each week. Doors released in working hours can affect residents, so people are warned first or the test is done at a quiet time.
  4. A competent person inspects the compartment doors and records it, as often as the fire risk assessment sets

    Benchmark: BS 8214 recommends regular inspection of fire doors at the interval the risk assessment sets, with a record, and like-for-like repair by a competent person.

    • StandardBS 8214 Fire resisting and smoke control doors. Code of practice, clause 15.1The standard recommends that fire doors are inspected regularly, as often as the risk assessment sets and the door’s use makes sensible, with the inspection recorded. A major failure is put right at once, parts are replaced like for like, and a competent person does the work and records what changed.
  5. A routine closes the compartment doors held on hold-open devices at night

    Benchmark: The 2006 guide asks for a routine for closing the compartmentation corridor fire doors at night, and says doors on electromagnetic hold-open devices should be closed at night.

    • GuidanceFire safety risk assessment: residential care premises, page 34Daily, doors on escape routes are checked to swing freely and close fully, and a routine closes all compartmentation corridor fire doors at night. Weekly, the fire detection and warning systems and manually operated devices are tested. Monthly, every fire door is checked to work and close correctly with its frame and seals intact, and the emergency lighting is tested. Every six months a competent person tests the emergency lighting and the detection and warning system.
Show in the 3D model

Compartment walls between protected areas

  • Compartmentation
Show in the 3D model

The walls that divide a storey into protected areas are compartment walls.

  • ADB asks for them, and for compartment floors, in a care home planned for progressive horizontal evacuation.
  • Their fire resistance comes from Table B2 by the height of the top floor: for a residential (institutional) building with its top floor more than 5 m and up to 11 m above ground, 60 minutes.
  • Completing a line of compartment walls by fitting cavity barriers above them is not appropriate: the wall should extend to the underside of the floor or roof above.
  • Where a duct crosses a compartment wall in a building with a sleeping risk, ADB asks for dampers released by smoke detection as well as by heat, and its exceptions need every occupant to be able to escape unaided, which is not true in a care home.

Here the compartment lines on each upper floor follow the existing walls, stepping along bedroom party walls and en-suite and store walls, and are REI 60 from slab to slab and through any ceiling void.

  • On the second floor they rise through the roof space to the underside of the roof deck.
  • Where a duct crosses one, its fire or fire and smoke dampers should close on smoke detection as well as on heat, because people sleep here and cannot all escape unaided.

REI 60Compartment walls between protected areas take the period Table B2 sets for the top floor’s height: 60 minutes at 6.3 m (Table B1 item 7).

  • GuidanceADB Vol 2, para 2.35PHE needs the areas used for the care of residents to be divided into protected areas by compartment walls and compartment floors.
  • GuidanceADB Vol 2, para 8.9Paragraphs 2.35 and 2.36 give the guidance on the provisions for compartment walls in care homes that use progressive horizontal evacuation.
  • GuidanceADB Vol 2, para 9.4“It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should extend to the underside of the floor or roof above.”
  • GuidanceADB Vol 2, para 10.22Where the use of the building involves a sleeping risk, fire dampers or fire and smoke dampers should be actuated by smoke detector-controlled automatic release mechanisms and by thermally actuated devices. The exceptions need all occupants to be able to make an unaided escape and an L1 system to BS 5839-1.
  • GuidanceADB Vol 2, Table B1, item 7Compartment walls: REI as set in Table B2, tested from each side separately.
  • GuidanceADB Vol 2, Table B2Residential (institutional), height of top floor above ground: up to 5 m, 30 minutes; up to 11 m, 60 minutes; up to 18 m, 60 minutes; up to 30 m, 90 minutes; more than 30 m, 120 minutes.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Bedrooms and en-suites

  • Means of escape
  • Compartmentation
Show in the 3D model

ADB asks for each bedroom in a care home to be enclosed in fire-resisting construction (at least REI 30) with fire-resisting doors (at least E 30).

  • ADB asks for every corridor serving bedrooms to be a protected corridor.
  • A bedroom should not hold more than one single or double bed.
  • The wall between a bedroom and a common escape route should have no uninsulated glazing.
  • Linings should meet Table 6.1: class B-s3, d2 on circulation spaces, C-s3, d2 in other rooms, and D-s3, d2 only in rooms of up to 4 m2 in residential accommodation.
  • Where a wall between bedrooms, or on a protected corridor, stops at a suspended ceiling, ADB asks for cavity barriers on the line of the wall or a fire-resisting ceiling (at least EI 30) over the whole area.

Here every bedroom has one bed, a level-access shower in its en-suite, a smoke detector and a sprinkler head, and the first floor has 27 of them.

  • Travel inside a bedroom is in one direction, to its door: the Travel panel works one, from the far corner of a bedroom in wing west, at about 6.6 m, under the 9 m of Table 2.1.
  • GuidanceADB Vol 2, para 2.42“Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30). Every corridor serving bedrooms should be a protected corridor.”
  • GuidanceADB Vol 2, para 2.43“Bedrooms should not contain more than one single or double bed.”Why it applies here: Every bedroom has a single bed.
  • GuidanceADB Vol 2, para 6.1The surface linings of walls and ceilings should meet the classifications in Table 6.1.
  • GuidanceADB Vol 2, para 9.5If the fire resisting construction of a protected escape route is not carried to full storey height, or at the top storey not to the underside of the roof covering, the cavity above or below it should be fitted with cavity barriers on the line of the enclosure or, above, enclosed on its lower side by a fire resisting ceiling (minimum EI 30) that extends throughout the building, compartment or separated part.
  • GuidanceADB Vol 2, para 9.7Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.
  • GuidanceADB Vol 2, Table B1, item 13Enclosure of a protected lobby or protected corridor: REI 30, tested from each side separately.
  • GuidanceADB Vol 2, Table B1, item 15(d)Construction that encloses bedrooms and ancillary accommodation in care homes: REI 30, tested from each side separately.
  • GuidanceADB Vol 2, Table B3, item 6Between residential or sleeping accommodation and a common escape route (corridor, lobby or stair), the permitted area of uninsulated glazed elements is nil.
  • GuidanceADB Vol 2, Table 6.1Classification of linings: small rooms of up to 4 m2 in residential accommodation, D-s3, d2; other rooms, C-s3, d2; other circulation spaces, B-s3, d2.
  • GuidanceEmollients: new information about risk of severe and fatal burns with paraffin-containing and paraffin-free emollientsThe medicines regulator advises that clothing and bedding that have been in contact with an emollient or emollient-treated skin can ignite rapidly. The fire risk exists with all paraffin-containing emollients whatever the concentration, and cannot be excluded with paraffin-free ones. People should not smoke or go near naked flames, and washing at a high temperature may reduce the build-up but does not remove it.
  • GuidanceSafe use of emollient skin creams to treat dry skin conditionsThe medicines regulator and the National Fire Chiefs Council advise that dried-on skin cream makes fabric more flammable and the fire burns quickly and intensely. People should avoid smoking and naked flames, change and wash clothes and bedding often, keep cream off furniture fabric, and tell relatives and carers about their treatment.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Smoking is controlled in bedrooms, a high ignition risk in the guide’s sample assessment, with ashtrays emptied daily into a metal bin taken outside and smoking areas checked at night once vacated

    Benchmark: The 2006 guide’s sample assessment rates smoking in resident bedrooms as a high risk, and asks for deep ashtrays emptied daily into a metal bin taken outside, with inspections of smoking areas once they are vacated at night.

    • GuidanceFire safety risk assessment: residential care premises, page 52In places where smoking is allowed, ashtrays are emptied daily into a metal bin that is taken outside, never into a plastic sack left inside, and regular inspections include smoking areas once they have been vacated at night.
    • GuidanceFire safety risk assessment: residential care premises, page 110The guide’s sample record of significant findings rates the risk as high in resident bedrooms where smoking occurs and low elsewhere.
  2. Upholstered furniture, mattresses, mattress overlays and bedding meet a recognised fire performance standard, and residents’ own furniture is allowed only if it does too

    Benchmark: The 2006 guide asks for furniture, mattresses, overlays and bedding to meet a recognised fire performance standard, and for residents’ own items to meet a similar one.

    • GuidanceFire safety risk assessment: residential care premises, pages 55 and 56Upholstered furniture, soft furnishings, textiles, mattresses, mattress overlays, bedding and sleepwear should meet a recognised fire performance standard. Residents should only be allowed to provide items of their own furniture or textiles for their own bedroom if they meet a similar standard.
  3. Mattresses and bed bases meet BS 7177 at the hazard level the person responsible for fire safety sets. The standard lists homes for older people under both medium and high hazard

    Benchmark: BS 7177 sets four hazard levels, lists homes for older people under both the medium and the high level, and says placing a building in a level is a decision for the person accountable for its fire safety.

    • StandardBS 7177 Specification for resistance to ignition of mattresses, mattress pads, divans and bed bases, clause 4 (note) and Table 1The standard sets four hazard levels for mattresses and bed bases by the ignition sources they have to resist, and lists homes for older people under both the medium and the high level. Its note says that placing a building in a level is a decision for the person accountable for its fire safety.
  4. How furniture and furnishings are rated. NHS guidance for hospitals treats the furniture and furnishings in accommodation for older people as high hazard

    Benchmark: This is a comparison, not a care home standard: NHS guidance for hospitals treats the furniture and furnishings in accommodation for older people as high hazard.

    • GuidanceHealth Technical Memorandum 05-03: Fire safety in the NHS, operational provisions, Part C, paragraph 2.14NHS guidance for hospitals treats the furniture and furnishings in accommodation for older people, people with learning difficulties, young people with disabilities and secure mental health premises as high hazard. It is written for NHS premises, so for a care home it is a comparison, not a requirement.
  5. Electric blankets and portable electrical equipment in use, including equipment staff bring in, are PAT tested, and residents and visitors are discouraged from bringing portable heaters

    Benchmark: The 2006 guide asks for electric blankets to be PAT tested and used to the maker’s instructions, for portable electrical equipment in use to be inspected and tested, and for residents, visitors and staff to be discouraged from bringing their own portable heaters.

    • GuidanceFire safety risk assessment: residential care premises, pages 51 and 56Electric blankets should be PAT tested and used only in accordance with the manufacturer’s instructions, and portable electrical equipment in use, including items brought in by staff, should be covered by the fire risk assessment’s inspection and portable appliance testing.
    • GuidanceFire safety risk assessment: residential care premises, page 51Common causes of fire in equipment include blocked ventilation points and inadequate cleaning of equipment such as tumble driers. A competent person should maintain machinery and equipment adequately and regularly. Residents, visitors and staff should be discouraged from bringing their own portable heaters.
  6. Residents who use emollient skin creams are known to staff. The creams, with or without paraffin, transfer onto clothing, bedding and bandages and make the fabric burn quickly and intensely, so those residents are kept from smoking and naked flames while wearing fabric that has been in contact with the cream, and their clothes and bedding are changed and washed often, which may reduce the build-up but does not remove it

    Benchmark: The medicines regulator advises that fabric that has been in contact with an emollient can ignite rapidly, that the risk cannot be excluded with paraffin-free creams, that people should not smoke or go near naked flames, and that washing at a high temperature may reduce the build-up but does not remove it.

    • GuidanceEmollients: new information about risk of severe and fatal burns with paraffin-containing and paraffin-free emollientsThe medicines regulator advises that clothing and bedding that have been in contact with an emollient or emollient-treated skin can ignite rapidly. The fire risk exists with all paraffin-containing emollients whatever the concentration, and cannot be excluded with paraffin-free ones. People should not smoke or go near naked flames, and washing at a high temperature may reduce the build-up but does not remove it.
    • GuidanceSafe use of emollient skin creams to treat dry skin conditionsThe medicines regulator and the National Fire Chiefs Council advise that dried-on skin cream makes fabric more flammable and the fire burns quickly and intensely. People should avoid smoking and naked flames, change and wash clothes and bedding often, keep cream off furniture fabric, and tell relatives and carers about their treatment.
Show in the 3D model

Bedroom doors (free-swing closers)

  • Means of escape
Show in the 3D model

A bedroom door in a care home is a fire door: ADB asks for at least E 30.

  • Table C1 puts the Sa smoke suffix on doors that form part of a protected corridor’s enclosure.
  • Where a self-closing device on a bedroom door could be an obstacle to a resident, ADB says a free-swing door closer to BS EN 1155 is appropriate.
  • A free-swing closer leaves the door free to swing in daily use, and ADB asks for the sign “Automatic fire door keep clear” on a door held open by an automatic release mechanism or free swing device.
  • ADB exempts bedroom doors from signs only in residential (other) premises, so a care home’s bedroom doors carry them.

Here every bedroom door is E 30 Sa with a free-swing closer that the first fire signal releases, and carries the “Automatic fire door keep clear” sign on both faces.

In existing buildings

In an existing home the closers are released by the alarm, not wedged open.

  • The 2006 guide suggests controlled closing devices so that doors are not wedged open, and lists wedged fire doors among the ways fire and smoke get through (pages 85 and 53).

E 30 SaEach bedroom is enclosed in REI 30 construction with doors of at least E 30 (para 2.42), and a door in a protected corridor’s enclosure carries the Sa suffix (Table C1).

  • GuidanceADB Vol 2, para 2.42“Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30).”
  • GuidanceADB Vol 2, para 2.45(a)If doors fitted with a self-closing device could present an obstacle to residents, free-swing door closers in accordance with BS EN 1155 are appropriate on bedrooms.
  • GuidanceADB Vol 2, Table C1, item 5(b)A door forming part of the enclosure of any other protected corridor: E 20 Sa. Unless pressurisation to BS EN 12101-6 is used, such doors should have a leakage rate not over 3 m3/m/hour at 25 Pa, or meet the Sa classification.
  • GuidanceADB Vol 2, para C11Fire doorsets are marked on both sides with a sign to BS 5499-5: “Fire door keep shut”, “Fire door keep locked shut”, or, where held open by an automatic release mechanism or free swing device, “Automatic fire door keep clear”.
  • GuidanceADB Vol 2, para C12The doorsets that do not need the signs are doors to and within flats and dwellinghouses, bedroom doors in ‘residential (other)’ premises, and lift entrance and landing doors.
  • GuidanceFire safety risk assessment: residential care premises, page 85To avoid the risk of doors being wedged open, controlled door closing devices with an electromagnetic hold open function can be installed, which let the door close when the fire alarm actuates.
  • GuidanceFire safety risk assessment: residential care premises, page 53Fire-resisting partitions being breached, or fire doors being wedged open, are among the things that can let smoke and fire spread.

What a fire risk assessor checks

  1. Free-swing closers on the bedroom doors release when the fire alarm signals, and the doors close on to their frames

    Benchmark: ADB says free-swing door closers to BS EN 1155 are appropriate on bedrooms where a self-closing device could be an obstacle to residents, and lets them be released by the fire detection and alarm system. The Fire Safety Order requires the responsible person to keep the premises and the safety devices in efficient working order.

    • GuidanceADB Vol 2, para C6(b)If a self-closing device would interfere with the normal approved use of the building, self-closing fire doors may be held open by an automatic release mechanism activated by an automatic fire detection and alarm system.
    • GuidanceADB Vol 2, para 2.45(a)If doors fitted with a self-closing device could present an obstacle to residents, free-swing door closers in accordance with BS EN 1155 are appropriate on bedrooms.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
Show in the 3D model

Bedroom and corridor walls

  • Means of escape
  • Compartmentation
Show in the 3D model

ADB asks for each bedroom in a care home to be enclosed in fire-resisting construction (at least REI 30) with fire-resisting doors (at least E 30).

  • ADB asks for every corridor serving bedrooms to be a protected corridor.
  • A bedroom should not hold more than one single or double bed.
  • The wall between a bedroom and a common escape route should have no uninsulated glazing.
  • Linings should meet Table 6.1: class B-s3, d2 on circulation spaces, C-s3, d2 in other rooms, and D-s3, d2 only in rooms of up to 4 m2 in residential accommodation.
  • Where a wall between bedrooms, or on a protected corridor, stops at a suspended ceiling, ADB asks for cavity barriers on the line of the wall or a fire-resisting ceiling (at least EI 30) over the whole area.

Here the walls round the bedrooms and the corridors that serve them are REI 30, and no glazing between a bedroom and the corridor is uninsulated, so any door vision panel is insulated fire glass.

  • Wall and ceiling linings in the corridors, as circulation spaces, should be class B-s3, d2 or better, and in the bedrooms, lounges and other rooms C-s3, d2.
  • Only rooms of up to 4 m2 in residential accommodation may be D-s3, d2 (ADB Vol 2 para 6.1 and Table 6.1).
  • Where the corridor walls or the walls between bedrooms stop at a suspended ceiling, the void above has cavity barriers on their line or a fire-resisting ceiling (EI 30) throughout (ADB Vol 2 paras 9.5 and 9.7).

REI 30Bedrooms and ancillary accommodation in a care home, and the corridors that serve them, take REI 30 (Table B1 items 13 and 15(d)).

  • GuidanceADB Vol 2, para 2.42“Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30). Every corridor serving bedrooms should be a protected corridor.”
  • GuidanceADB Vol 2, para 2.43“Bedrooms should not contain more than one single or double bed.”
  • GuidanceADB Vol 2, para 6.1The surface linings of walls and ceilings should meet the classifications in Table 6.1.
  • GuidanceADB Vol 2, para 9.5If the fire resisting construction of a protected escape route is not carried to full storey height, or at the top storey not to the underside of the roof covering, the cavity above or below it should be fitted with cavity barriers on the line of the enclosure or, above, enclosed on its lower side by a fire resisting ceiling (minimum EI 30) that extends throughout the building, compartment or separated part.
  • GuidanceADB Vol 2, para 9.7Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.
  • GuidanceADB Vol 2, Table B1, item 13Enclosure of a protected lobby or protected corridor: REI 30, tested from each side separately.
  • GuidanceADB Vol 2, Table B1, item 15(d)Construction that encloses bedrooms and ancillary accommodation in care homes: REI 30, tested from each side separately.
  • GuidanceADB Vol 2, Table B3, item 6Between residential or sleeping accommodation and a common escape route (corridor, lobby or stair), the permitted area of uninsulated glazed elements is nil.
  • GuidanceADB Vol 2, Table 6.1Classification of linings: small rooms of up to 4 m2 in residential accommodation, D-s3, d2; other rooms, C-s3, d2; other circulation spaces, B-s3, d2.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Corridor doors (dividing the corridor)

  • Means of escape
Show in the 3D model

A long corridor that gives access to alternative escape routes is divided by self-closing fire doors so one fire cannot cut both routes.

  • ADB asks for this where the corridor is more than 12 m long and connects two or more storey exits, with the doors about half way between the exits.
  • A dead end of more than 4.5 m should be separated by self-closing fire doors from any part of the corridor that gives two directions of escape or continues past a storey exit.
  • BS 9991 recommends the same split for corridors of more than 12 m between exits.
  • Where a corridor has a false ceiling, cavity barriers may be needed so smoke cannot pass over the doors.
  • For existing homes the 2006 guide asks for fire doors near the middle of corridors over 30 m, and says doors on electromagnetic hold-open devices should be closed at night.

Here the corridors are divided by self-closing doorsets about mid-way between storey exits, in the wing and on the service corridors, and the passages south of Stair 1 on the first and second floors have a dead-end door.

  • Each doorset stands where its held-open leaves lie flat against a wall, clear of every doorway and every door’s swing, so none blocks a bedroom door.
  • Cavity barriers may be needed so smoke cannot pass over the doors above a ceiling (ADB Vol 2 para 9.6; 2006 guide page 85).
In existing buildings

The 2006 guide, for existing homes, asks for corridors of more than 30 m to be divided near the middle, against 12 m in new design (2006 guide page 85; ADB Vol 2 para 2.26; BS 9991 clause 55.5).

E 30 SaDoors that divide a corridor between alternative exits, or cut off a dead end, take E 20 Sa at least (Table C1 items 7(a) and 7(b)); the model uses E 30 Sa, as the bedroom enclosure does.

  • GuidanceADB Vol 2, para 2.26A corridor giving access to alternative escape routes should be divided by self-closing fire doorsets (and associated screens) where it is more than 12 m long and connects two or more storey exits. The doorsets should be approximately mid-way between the two storey exits and safeguard the route from smoke, while considering the layout of the corridor and any adjacent fire risks.
  • GuidanceADB Vol 2, para 2.28Dead ends of corridors exceeding 4.5 m that give access to a point from which alternative escape routes are available should be separated by self-closing fire doorsets from any part of the corridor that provides two directions of escape or continues past one storey exit to another.
  • GuidanceADB Vol 2, para 9.6In divided corridors, cavity barriers may be needed to prevent alternative escape routes being affected by fire or smoke.
  • GuidanceADB Vol 2, Table C1, item 7(a)Doors sub-dividing corridors that connect alternative exits: E 20 Sa.
  • GuidanceADB Vol 2, Table C1, item 7(b)Doors separating the dead-end portions of corridors from the remainder of the corridor: E 20 Sa.
  • StandardBS 9991, clause 55.5 (opens in a new tab)Corridors serving bedrooms are protected corridors, with 30 minute construction and self-closing doors of at least E 30 Sa or FD 30 S. Corridors longer than 12 m between exits are subdivided by 30 minute construction and a self-closing door of that rating. The standard notes that self-closing doors can be fitted with hold-open devices to BS 7273-4.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • GuidanceFire safety risk assessment: residential care premises, page 85Corridors serving sleeping accommodation have 30 minutes fire resistance and self-closing devices. Corridors of more than 30 m are generally subdivided with fire doors as near the middle as possible, and a corridor serving two exits from a floor generally has fire doors separating them. Where electromagnetic hold-open devices are fitted, the doors should be closed at night, and false ceilings generally need barriers or smoke stopping over any fire doors.

What a fire risk assessor checks

  1. Hold-open devices on the corridor doors release when the fire alarm signals, and the doors close on to their frames

    Benchmark: ADB says hold-open devices to BS EN 1155 are appropriate on circulation spaces where a self-closing device could be an obstacle to residents, and lets them be released by the fire detection and alarm system. The Fire Safety Order requires the responsible person to keep the premises and the safety devices in efficient working order.

    • GuidanceADB Vol 2, para C6(b)If a self-closing device would interfere with the normal approved use of the building, self-closing fire doors may be held open by an automatic release mechanism activated by an automatic fire detection and alarm system.
    • GuidanceADB Vol 2, para 2.45(b)If doors fitted with a self-closing device could present an obstacle to residents, hold-open devices in accordance with BS EN 1155 are appropriate on circulation spaces.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
  2. The corridor doors are checked monthly to close fully, with their frames and seals intact, and the doors on hold-open devices release when they are tested

    Benchmark: The 2006 guide asks for a monthly check that fire doors close correctly with frames and seals intact, and its sample checklist asks whether a linked door holder releases when the alarm is tested. BS 9991 recommends that hold-open devices are tested monthly, by simulating a power failure or the alarm, and the result recorded.

    • GuidanceFire safety risk assessment: residential care premises, page 34Daily, doors on escape routes are checked to swing freely and close fully, and a routine closes all compartmentation corridor fire doors at night. Weekly, the fire detection and warning systems and manually operated devices are tested. Monthly, every fire door is checked to work and close correctly with its frame and seals intact, and the emergency lighting is tested. Every six months a competent person tests the emergency lighting and the detection and warning system.
    • GuidanceFire safety risk assessment: residential care premises, page 118The sample maintenance checklist asks, in its weekly checks, whether the alarm test made the linked fire protection systems operate, giving a magnetic door holder releasing as the example.
    • StandardBS 9991, Annex I, I.4.8The standard recommends that doors held open by hold-open devices are tested monthly, by simulating a power failure or a fire alarm, and that the results are recorded.
  3. Every week a fire alarm signal releases every hold-open door among the corridor doors and each is seen to close. The test is done at a quiet time, or with a warning first, because a door swinging shut can hurt a frail resident

    Benchmark: BS 7273-4 recommends a weekly release test of every door release mechanism, at about the same time each week, and its note says doors released in working hours can affect residents.

    • StandardBS 7273-4 Code of practice for the operation of fire protection measures. Actuation of release mechanisms for doors, clause 21.1.2The standard recommends that every week a fire alarm signal releases every door release mechanism and each door is seen to close, at about the same time each week. Doors released in working hours can affect residents, so people are warned first or the test is done at a quiet time.
  4. A competent person inspects the corridor doors and records it, as often as the fire risk assessment sets

    Benchmark: BS 8214 recommends regular inspection of fire doors at the interval the risk assessment sets, with a record, and like-for-like repair by a competent person.

    • StandardBS 8214 Fire resisting and smoke control doors. Code of practice, clause 15.1The standard recommends that fire doors are inspected regularly, as often as the risk assessment sets and the door’s use makes sensible, with the inspection recorded. A major failure is put right at once, parts are replaced like for like, and a competent person does the work and records what changed.
  5. A routine closes the corridor fire doors held on hold-open devices at night

    Benchmark: The 2006 guide asks for a routine for closing the compartmentation corridor fire doors at night, and says doors on electromagnetic hold-open devices should be closed at night.

    • GuidanceFire safety risk assessment: residential care premises, page 34Daily, doors on escape routes are checked to swing freely and close fully, and a routine closes all compartmentation corridor fire doors at night. Weekly, the fire detection and warning systems and manually operated devices are tested. Monthly, every fire door is checked to work and close correctly with its frame and seals intact, and the emergency lighting is tested. Every six months a competent person tests the emergency lighting and the detection and warning system.
    • GuidanceFire safety risk assessment: residential care premises, page 85Corridors of more than 30 m are generally subdivided with fire doors as close to the mid point as possible. Where electromagnetic hold-open devices are fitted, the doors should be closed at night.
Show in the 3D model

Stores, sluices, bathrooms and staff rooms

  • Compartmentation
Show in the 3D model

ADB asks for ancillary accommodation in a care home to be enclosed in fire-resisting construction (at least REI 30), with doors of at least E 30, and for escape routes not to pass through it.

  • The list covers chemical stores, cleaners’ rooms, clothes storage, day rooms, smoking rooms, disposal rooms, plant rooms, linen stores, kitchens, laundry rooms, staff changing and locker rooms and store rooms.
  • BS 9991 adds bathrooms with powered hoists to the rooms that take 30 minute construction and self-closing doors.
  • For wheelchairs and scooters it recommends no charging points in common corridors or protected stairways.
  • It recommends a store separated from the escape routes by 30 minutes where there are sprinklers (60 without), and sprinklers extended to the charging area.

Here the stores, sluices, assisted bathrooms, hoist stores and changing rooms are enclosed in 30 minute construction with E 30 Sa doors, and the bathrooms have powered hoists.

  • Mobile hoists, powered wheelchairs and scooters are charged in enclosed, sprinklered stores, never in corridors or stairs.
  • BS 9991 recommends that charging points are not in common corridors or protected stairways, and that a storage and charging area is separated by at least 30 minutes where the building has sprinklers, with the sprinklers extended into it (BS 9991:2024 clauses 55.5 and 7.5).
  • NHS guidance for hospitals adds: nothing combustible beside a charger, damaged batteries never charged or used, and timers so that equipment left on charge charges during waking hours.

REI 30Ancillary accommodation in a care home takes at least REI 30 (para 2.44), with doors of E 30 (Table C1 item 10(b)).

  • GuidanceADB Vol 2, para 2.38A fire in one protected area should not prevent occupants of other areas from reaching a final exit. Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.
  • GuidanceADB Vol 2, para 2.44Ancillary accommodation such as chemical stores, cleaners’ rooms, clothes storage, day rooms, smoking rooms, disposal rooms, plant rooms, linen stores, kitchens, laundry rooms, staff changing and locker rooms and store rooms should be enclosed by fire resisting construction (minimum REI 30).
  • GuidanceADB Vol 2, Table C1, item 10(b)A door forming part of the enclosure to ancillary accommodation in care homes: E 30.
  • StandardBS 9991, clause 55.5 (opens in a new tab)Storage rooms and cupboards, staff changing and locker rooms, kitchens and laundry rooms, disposal and refuse rooms and day rooms take fire-resisting construction to the standard’s Table 5 and self-closing doors of at least E 30 Sa or FD 30 S. Smoking rooms and bathrooms with electrically powered facilities such as hoists take 30 minute construction and self-closing doors of that rating.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • StandardBS 9991, clause 7.5 (opens in a new tab)Electric charging points should not be in common access corridors or protected stairways. A designated store for electric wheelchairs and mobility scooters should be separated from the means of escape by at least 30 minutes of fire-resisting construction where the building has sprinklers (60 minutes where it has none), and sprinklers should be extended to the charging area.Why it applies here: BS 9991 clause 55.5 sends care homes to this clause for storing and charging wheelchairs and scooters.
  • GuidanceHealth Technical Memorandum 05-03: Fire safety in the NHS, operational provisions, Part K, paragraphs 5.65 to 5.68NHS guidance for hospitals says batteries are charged to the maker’s instructions with nothing combustible near the charger in use, damaged batteries are never charged, and timers can limit charging to waking hours. It is written for NHS premises, so for a care home it is a comparison, not a requirement.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Medical oxygen is kept to a minimum and stored safely: the room where it is used is no smoking and signed, it is well ventilated, and the fire and rescue service is told oxygen is kept. Staff are trained in its safe use

    Benchmark: The 2006 guide asks for the number of cylinders to be the practical minimum, stored safely and ventilated, the room where oxygen is used to be a no smoking area with warnings, trained staff and the fire and rescue service told that oxygen is used.

    • GuidanceFire safety risk assessment: residential care premises, page 50Medical oxygen cylinders are kept to the minimum, stored safely and preferably outside. The room where oxygen is used is a no smoking area with clear signs and good ventilation, staff who operate the equipment are trained, and the fire and rescue service is told that oxygen is used and stored. Aerosols are a high hazard when stored under pressure and are disposed of safely.
    • GuidanceFire safety risk assessment: residential care premises, page 41Fire safety training for staff includes the safe use of, and risks from, storing or working with highly flammable and explosive substances and bottled or piped oxygen.
  2. Aerosols and flammable liquids are kept to a minimum in a locked store

    Benchmark: The 2006 guide asks for flammable liquids and gases in residents’ areas to be kept to a minimum, with spare supplies in dedicated, locked storerooms, and describes aerosols as a high hazard when stored under pressure.

    • GuidanceFire safety risk assessment: residential care premises, pages 19 and 48Flammable liquids and gases in residents’ areas are kept to a minimum, and spare supplies are stored in dedicated, locked storerooms where residents and visitors are not allowed to go, ideally fire-resisting and locked away.
    • GuidanceFire safety risk assessment: residential care premises, page 50Medical oxygen cylinders are kept to the minimum, stored safely and preferably outside. The room where oxygen is used is a no smoking area with clear signs and good ventilation, staff who operate the equipment are trained, and the fire and rescue service is told that oxygen is used and stored. Aerosols are a high hazard when stored under pressure and are disposed of safely.
Show in the 3D model

Day rooms (first and second floors)

  • Means of escape
  • Compartmentation
Show in the 3D model

A lounge or dining room in a care home is a day room, and ADB asks for it to be enclosed in fire-resisting construction (at least REI 30).

  • Where a storey has areas for eating or drinking and that is not the main use of the building, ADB asks for at least two escape routes from each area, leading to a storey exit without entering a kitchen.
  • Routes are alternatives when they are in directions at least 45 degrees apart, or separated by fire-resisting construction.
  • In a residential (institutional) building travel is limited to 9 m where it is possible in one direction only and 18 m where it is possible in more than one.
  • Where a room has a dead-end part, Diagram 2.1 limits the one-direction part, and the total to the nearer exit should still be within the 18 m.

If the layout of partitions and fittings is not known, direct distances are assessed and taken as two-thirds of the travel distance.

Here the lounges and dining rooms are enclosed in 30 minute construction with E 30 Sa doors.

  • The first floor lounge has a second door in its corridor wall, so the walk from each far corner is one direction until the two doors are 45 degrees apart and then two, and the totals to the doors are 8.4 and 8.8 m, under 9 m (the Travel panel works them).
  • Each dining room has two ways out that avoid the kitchen.

REI 30The lounges and dining rooms are enclosed in 30 minute construction with E 30 Sa doors.

  • GuidanceADB Vol 2, para 2.16If a storey contains areas for consuming food or drink, and that is not the main use of the building, a minimum of two escape routes should be provided from each area (except from inner rooms that meet the conditions in paragraph 2.11), and those routes should lead directly to a storey exit without entering a kitchen or similar area of high fire hazard.
  • GuidanceADB Vol 2, para 2.38Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.
  • GuidanceADB Vol 2, para 2.44Ancillary accommodation, which includes day rooms, should be enclosed by fire resisting construction (minimum REI 30).
  • GuidanceADB Vol 2, para 2.10Alternative escape routes should be in directions 45 degrees or more apart, or, if less than 45 degrees apart, separated from each other by fire resisting construction.
  • GuidanceADB Vol 2, Diagram 2.1Travel distance in a dead-end condition: the angle between the two exits as seen from the dead end is at least 45 degrees; the shorter distance to either exit is no more than the maximum for alternative routes; and the distance along the dead end is no more than the maximum where there is no alternative route.
  • GuidanceADB Vol 2, Table 2.1Maximum travel distance for a residential (institutional) building (purpose group 2(a)): 9 m where travel is possible in one direction only, 18 m where it is possible in more than one direction. Note 1: where the layout of partitions and fittings is not known, the direct distance is assumed to be two-thirds of the travel distance.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Compartment floors

  • Compartmentation
Show in the 3D model

ADB asks for every floor of a care home to be a compartment floor, so each storey is a compartment of its own.

  • A fire on one storey is held away from the next while residents are moved along it.
  • Table B1 gives compartment floors the same period as Table B2 sets by the height of the top floor: for a residential (institutional) building with its top floor more than 5 m and up to 11 m above ground, 60 minutes, tested from the underside.

Here the slab of the first floor and the slab of the second floor are the compartment floors between the three storeys, REI 60.

  • The space over the cafe is floored over and enclosed, so the first floor’s compartment floor is unbroken.

REI 60Compartment floors take the period Table B2 sets for the top floor’s height, 60 minutes at 6.3 m, tested from the underside (Table B1 item 3(c)).

  • GuidanceADB Vol 2, para 2.36“Each storey used for the care of residents should be divided by compartment walls into at least three protected areas. All floors should be compartment floors.”
  • GuidanceADB Vol 2, para 8.8“All floors should be constructed as compartment floors.”
  • GuidanceADB Vol 2, Table B1, item 3(c)Any other floor, including compartment floors: REI as set in Table B2, tested from the underside.
  • GuidanceADB Vol 2, Table B2Residential (institutional), height of top floor above ground: up to 5 m, 30 minutes; up to 11 m, 60 minutes; up to 18 m, 60 minutes; up to 30 m, 90 minutes; more than 30 m, 120 minutes.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Protected stairs

  • Means of escape
  • Compartmentation
Show in the 3D model

ADB asks for every internal escape stair in a care home to be a protected stairway, in a fire-resisting enclosure, leading to a final exit directly or through an exit passageway.

  • A single escape stair is allowed only in the cases ADB lists, for example a building with no storey more than 11 m above ground that is allowed one escape route on every storey, and BS 9991 recommends at least two independent escape routes from any floor of a care home.
  • A stair serving up to 150 people in a residential (institutional) building should be at least 1000 mm wide unless staff alone use it, and no narrower than the exits that lead to it or at any point on the way to a final exit.
  • Doors to the enclosure are half the wall’s fire resistance, at least 30 minutes, with the Sa smoke suffix.
  • A protected stairway may hold only the things ADB lists, such as washrooms, a lift well if it is not a firefighting stair, and cupboards enclosed in fire-resisting construction where it is not the only stair.

Here there are three protected stairs, and every floor is served by at least two: Stair 1 by the entrance, Stair 2 at the north end of the service wing and Stair 3 at the east end of the bedroom wing.

  • Each flight is 1.1 m wide, against the 1000 mm ADB asks for up to 150 people, and every stair leads to a final exit.
  • The stores that would have stood inside a stair are left out, because a protected stairway may hold only what ADB lists.

REI 60A protected stair is a protected shaft: its enclosure takes the period Table B2 sets, 60 minutes here (para 8.6, Table B1 item 8(c)), and its doors half that, at least 30 minutes, with Sa (Table C1 item 2(c)).

  • GuidanceADB Vol 2, para 3.3A single escape stair may serve a building in the situations listed, which include a building with no storey more than 11 m above ground level that is allowed only a single escape route in every storey in accordance with paragraph 2.6b and Table 2.1.
  • GuidanceADB Vol 2, para 3.10The width of escape stairs should be at least as wide as any exits giving access to the stairs, no less than the widths in Table 3.1, and should not reduce at any point on the way to a final exit.
  • GuidanceADB Vol 2, para 3.23Every internal escape stair should be a protected stairway (within a fire resisting enclosure). The exception is an unprotected stair forming part of an internal route where the travel distance and the number of people are very limited.
  • GuidanceADB Vol 2, para 3.36Every protected stairway should lead to a final exit, either directly or via an exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
  • GuidanceADB Vol 2, para 3.38A protected stairway may include only sanitary accommodation or washrooms, a lift well if the stair is not a firefighting stair, and, if it is not the only stair, a reception desk of up to 10 m2 and cupboards enclosed with fire resisting construction.
  • GuidanceADB Vol 2, Table 3.1Minimum width of escape stairs in a residential (institutional) building, unless the stair will be used only by staff: 1000 mm where it serves up to 150 people.Why it applies here: Each flight is 1.1 m wide, against the 1000 mm.
  • GuidanceADB Vol 2, Table C1, item 2(c)A door enclosing a protected shaft forming a stairway not described in 2(b): half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum and with suffix Sa(2).
  • StandardBS 9991, clause 55.2.1 (opens in a new tab)Whatever the evacuation strategy, the standard recommends that all care homes have at least two independent escape routes from any floor level, to provide means of escape and to give the fire and rescue service several ways in.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • GuidanceADB Vol 2, para 8.6Stairs and service shafts connecting compartments should be protected to restrict the spread of fire between the compartments. These are called protected shafts, and the walls or floors round them are considered compartment walls or compartment floors.
  • GuidanceADB Vol 2, Table B1, item 8(c)Protected shafts, other than the glazing and the parts between a shaft and a protected lobby or corridor that the table lists: REI as set in Table B2, tested from each side separately.
Show in the 3D model

Refuges with emergency voice communication

  • Means of escape
Show in the 3D model

A refuge is a place where someone who cannot use the stairs can wait for a short time, as part of the management plan.

  • ADB asks for a refuge on every storey of each protected stairway that gives an exit from it.
  • It need not be inside the stair enclosure, but it should give direct access to the stair, and one refuge can be used by more than one person.
  • A refuge is at least 900 mm by 1400 mm and reachable by a wheelchair user, and in a stair, lobby or protected corridor it should not narrow the escape route or get in the way of people escaping.
  • Each has an emergency voice communication outstation to BS 5839-9, linked to a master station by the control room or the fire alarm panel, and is marked; ADB asks for a blue “Refuge - keep clear” sign in protected lobbies and stairways.

Here there are six refuges, one at each stair on each upper floor, each with its emergency voice communication outstation and its blue sign.

  • On the first floor the Stair 2 and Stair 3 refuges stand in the corridor beside the stair door, and on the second floor the Stair 3 refuge does, because a refuge on those landings would obstruct the way to the flight.
  • A refuge gives direct access to the stair, as ADB asks of one outside the enclosure.
  • GuidanceADB Vol 2, para 3.4Refuges form part of the management plan and offer relatively safe areas for people to wait for a short period only. They should be provided on every storey (except ones consisting only of plant rooms) of each protected stairway providing an exit from that storey, need not be within the stair enclosure but should enable direct access to the stair, and a single refuge may be occupied by more than one person.Why it applies here: Six refuges, one at each stair on each upper floor, each giving direct access to its stair.
  • GuidanceADB Vol 2, para 3.5Satisfactory refuges include an enclosure such as a compartment, protected lobby, protected corridor or protected stairway, and an area in the open air that is protected or remote from any fire risk and has its own means of escape.
  • GuidanceADB Vol 2, para 3.6Refuges should be a minimum of 900 mm by 1400 mm and accessible by someone in a wheelchair. Where sited in a protected stairway, lobby or corridor, they should not reduce the width of the escape route or obstruct the flow of people escaping.Why it applies here: No refuge stands where a flight arrives, so none obstructs the way down.
  • GuidanceADB Vol 2, para 3.7Refuges should have an emergency voice communication system complying with BS 5839-9, consisting of Type B outstations communicating with a master station in the building control room, if there is one, or next to the fire detection and alarm panel.
  • GuidanceADB Vol 2, para 3.8Refuges and evacuation lifts should be clearly identified. In protected lobbies and protected stairways there should be a blue mandatory sign worded “Refuge - keep clear” in addition to fire safety signs.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Lift 2: the evacuation lift

  • Means of escape
Show in the 3D model

ADB says lifts should generally not be used in a fire unless their use is part of a management plan for evacuating people, with the lift sited and protected and built to stay usable. A lift meant for that is an evacuation lift.

  • BS 9991 recommends that a building with passenger lift access also has a means of using lifts for escape, with at least one evacuation lift for each escape stair, built to BS EN 81-20 and its own clause, and it expects BS EN 81-76 to be adopted when published.
  • The lift well should be inside a protected stairway or enclosed in at least REI 30 where it could prejudice escape, and a well that connects compartments forms a protected shaft.
  • ADB asks for refuges and evacuation lifts to be clearly identified.
  • BS 9991 recommends that the lift’s lobby has smoke protection in a care home: smoke ventilation to the areas adjoining the lobby, with natural ventilation by a smoke shaft, or a pressure differential system.

Here this is Lift 2, the only evacuation lift.

  • It is inside the Stair 2 enclosure on every floor, and on the first and second floors a smoke shaft from the corridor beside Stair 2, with a vent at the head of Stair 2, protects it.
  • In an evacuation staff use it to take residents down, as part of the evacuation plan.
  • The Stair 2 refuge beside it, with its emergency voice communication outstation, is where a resident can wait for a short time. The “Evacuation lift” sign is at Lift 2 only.
  • Lift 1 is an ordinary passenger lift, not an evacuation lift, with no smoke shaft.
  • BS 9991 recommends at least one evacuation lift for each escape stair where passenger lifts serve the upper floors: here only Stair 2 has one, Stair 1’s lift is not an evacuation lift and Stair 3 has no lift.

REI 60Assumed: Lift 2 stands inside the Stair 2 enclosure, and a well that connects compartments forms a protected shaft, so the model takes the protected stairs’ 60 minutes for its well, with E 30 landing doors, half that period. Its own text gives the lift no period.

  • GuidanceADB Vol 2, para 5.32“Generally, lifts should not be used when there is a fire in the building, unless their use forms part of a management plan for evacuating people” and the lifts are appropriately sited and protected and contain safety features to ensure they remain usable during a fire.Why it applies here: Lift 2 is used by staff under the evacuation plan; Lift 1 is not used in a fire.
  • GuidanceADB Vol 2, para 5.34Lift wells should be sited within the enclosures of a protected stairway, or enclosed with fire resisting construction (minimum REI 30) when in a position that might prejudice the means of escape.Why it applies here: Lift 2 is inside the Stair 2 enclosure on every floor.
  • GuidanceADB Vol 2, para 5.35A lift well connecting different compartments should form a protected shaft.
  • GuidanceADB Vol 2, para 3.4Refuges should be provided on every storey of each protected stairway providing an exit from that storey, and a single refuge may be occupied by more than one person.
  • GuidanceADB Vol 2, para 3.8Refuges and evacuation lifts should be clearly identified, with a blue mandatory sign worded “Refuge - keep clear” in protected lobbies and stairways.
  • GuidanceADB Vol 2, para 3.38(b)A protected stairway may include a lift well if the stair is not a firefighting stair.
  • StandardBS 9991, clause 7.4.1 (opens in a new tab)A building with passenger lift access to an upper or lower level should also have a means of using lifts for escape. A lift provided for escape is designed and programmed as an evacuation lift, with at least one evacuation lift for each escape stair, or more if a capacity assessment calls for it.Why it applies here: Only Stair 2 has an evacuation lift. Lift 1, an ordinary passenger lift, is not an evacuation lift, and Stair 3 has no lift.
  • StandardBS 9991, clause 7.4.2 (opens in a new tab)Evacuation lifts are designed and operated to BS EN 81-20 and the subclause’s own recommendations. The standard expects users to adopt BS EN 81-76 for evacuation lifts when it is published, and says the lift enclosure is built as a protected shaft.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • StandardBS 9991, clause 56.2 (opens in a new tab)In the lobbies of evacuation lifts in care homes the standard recommends smoke protection by smoke ventilation in the areas next to the lobbies, natural per clause 20.2.2.2 or mechanical, or by a pressure differential system to the lobby.Why it applies here: Lift 2’s waiting area is protected by the smoke shaft from the corridor beside Stair 2 and the vent at the head of Stair 2.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The evacuation lift’s switches are tested weekly and the lift is tested by a competent person every six months

    Benchmark: BS 9991 recommends a weekly test of the evacuation lift switches and a six-monthly inspection and test of lifts used for evacuation by a competent person, and the 2006 guide’s sample checklist has the same six-monthly check.

    • StandardBS 9991, Annex I, I.3.6 and I.6.2(e)The standard recommends that the operation of the evacuation lift switches is tested once a week, and that lifts used for evacuation are inspected and tested every six months by a competent person.
    • GuidanceFire safety risk assessment: residential care premises, page 119The sample checklist asks, among its six-monthly checks, whether any firefighting or emergency evacuation lift, any sprinkler system and the release and closing mechanisms of fire-resisting compartment doors have been tested by a competent person, and whether the fire warning system has been checked by a competent person.
Show in the 3D model

Lift 1: an ordinary passenger lift

  • Means of escape
Show in the 3D model

An ordinary passenger lift is not an evacuation lift and is not used in a fire.

  • ADB says lifts should generally not be used when there is a fire unless their use is part of a management plan, with the lift sited and protected and built to stay usable.
  • Where a care home is planned for progressive horizontal evacuation and the lift well is not inside a protected stairway, ADB asks for its entrance to be separated at every storey by a protected lobby of at least REI 30, and for the lift well to be enclosed in at least REI 30 where it could prejudice escape.
  • Because lifts are generally not used in a fire, a person who cannot use the stairs waits at a refuge.
  • BS 9991 recommends at least one evacuation lift for each escape stair, so a home with more escape stairs than evacuation lifts is a gap against that recommendation, which its fire strategy has to deal with.

Here this is Lift 1, an ordinary passenger lift, not an evacuation lift.

  • On the ground and first floors it is outside a protected stair, so its entrance is behind a protected lobby; on the second floor it is inside the Stair 1 enclosure.
  • It has no smoke shaft and no vent at the head of Stair 1, and it is not used in a fire.
  • The Stair 1 refuges beside it serve the stair, not the lift.
  • BS 9991 recommends at least one evacuation lift for each escape stair: Lift 1, which is not an evacuation lift, leaves its stair without one.

An “In case of fire do not use lift” sign is drawn beside its landing door. None of the guidance read for this page says such a sign is wanted, so the page claims no source for it.

REI 60Guidance allows 30 or 60 minutes.Assumed: ADB asks for a lift well to be enclosed in at least REI 30 where it could prejudice escape, and says a well that connects compartments forms a protected shaft. Lift 1 serves all three floors, each a compartment, so the model takes the protected shaft’s 60 minutes, as the protected stairs have, with E 30 landing doors, half that period.

  • GuidanceADB Vol 2, para 5.32“Generally, lifts should not be used when there is a fire in the building, unless their use forms part of a management plan for evacuating people” and the conditions on siting, protection and safety features are met.Why it applies here: Lift 1 is not used in a fire.
  • GuidanceADB Vol 2, para 5.34Lift wells should be sited within the enclosures of a protected stairway, or enclosed with fire resisting construction (minimum REI 30) when in a position that might prejudice the means of escape.
  • GuidanceADB Vol 2, para 5.35A lift well connecting different compartments should form a protected shaft.
  • GuidanceADB Vol 2, para 5.37“In buildings designed for phased evacuation or progressive horizontal evacuation, if the lift well is not within the enclosures of a protected stairway, its entrance should be separated at every storey by a protected lobby (minimum REI 30).”Why it applies here: On the ground and first floors Lift 1’s well is outside a protected stair, so its entrance has a protected lobby.
  • GuidanceADB Vol 2, para 3.4Refuges are the relatively safe areas where people wait for a short period, provided on every storey of each protected stairway that gives an exit from that storey.
  • StandardBS 9991, clause 7.4.1 (opens in a new tab)A building with passenger lift access to an upper or lower level should also have a means of using lifts for escape. A lift provided for escape should be designed and programmed to work as an evacuation lift, with at least one for each escape stair.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Stair and Lift 1 lobby (first floor)

  • Means of escape
  • Compartmentation
Show in the 3D model

In a building planned for progressive horizontal evacuation, ADB asks for the entrance to a lift well that is not inside a protected stairway to be separated at every storey by a protected lobby, built to at least REI 30.

  • The doors to a protected lobby approach to a lift shaft are E 30 Sa.
  • The lift well itself is enclosed in at least REI 30 where it could prejudice the way out.

Here Lift 1 and Stair 1 share a lobby on the first floor.

  • Lift 1 is a passenger lift all the same, so ADB asks for the lobby, and it also takes the approach to the stair out of the social space, since escape routes should not pass through a day room.

REI 30The protected lobby at Lift 1’s entrance is built to at least REI 30, with E 30 Sa doors.

  • GuidanceADB Vol 2, para 5.37“In buildings designed for phased evacuation or progressive horizontal evacuation, if the lift well is not within the enclosures of a protected stairway, its entrance should be separated at every storey by a protected lobby (minimum REI 30).”
  • GuidanceADB Vol 2, Table C1, item 5(c)A door forming part of the enclosure of a protected lobby approach to a lift shaft: E 30 Sa.
  • GuidanceADB Vol 2, para 2.38Escape routes should not pass through ancillary accommodation listed in paragraph 2.44, which includes day rooms.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Smoke shaft beside Lift 2

BS 9991 recommends smoke protection for the lobbies of evacuation lifts in care homes: smoke ventilation to the areas adjoining them, natural or mechanical, or a pressure differential system to the lobby.

  • The natural form in clause 20.2.2.2(b) is a smoke shaft in the lobby or corridor, with a smoke control damper of at least 1 m2 at the top of the stairway.
  • The vents are set to open on smoke detection in the lobby or corridor next to the stair.
  • Only the vent where smoke is detected opens, so one floor’s smoke is not drawn along the others.

Here one shaft serves the corridor heads beside Stair 2 on the first and second floors, the form with a shaft because those spaces have no outside wall.

  • It protects Lift 2’s waiting area only: Lift 1 has no smoke shaft.
  • Its vents open only where smoke is detected.

REI 60Assumed: the shaft links the first and second floors, which are separate compartments, so the model builds it as a protected shaft, whose enclosure takes the period Table B2 sets, 60 minutes here, as the protected stairs do. Its own text gives it no period.

  • StandardBS 9991, clause 56.2 (opens in a new tab)In the lobbies of evacuation lifts in care homes the standard recommends smoke ventilation in the adjacent areas, to help people waiting and to keep smoke out of the lift shaft, natural per 20.2.2.2 or mechanical per 20.2.2.3 b), or a pressure differential system to the lobby per 20.2.2.3 a).Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • StandardBS 9991, clause 20.2.2.1 (opens in a new tab)Vents that open automatically from the top storey of the stairs should operate on smoke detection in the protected lobbies or protected corridors next to the stair enclosure. Only the vent from the lobby or corridor where smoke has been detected opens, to outside air or into a smoke shaft, and later detections or manual overrides do not open more than one at a time.Why it applies here: Clause 56.2 sends the smoke protection of evacuation lift lobbies to the ventilation this clause describes.
  • StandardBS 9991, clause 20.2.2.2 (opens in a new tab)A natural ventilation system has either vents to outside of at least 0.9 m2 aerodynamic free area in the corridor or lobby next to the stair and at least 0.7 m2 at the top of the stairway, or a smoke shaft to the standard’s Annex F in the lobby or corridor with a smoke control damper of at least 1 m2 at the top storey of the stairway.Why it applies here: Clause 56.2 sends the smoke protection of evacuation lift lobbies to the ventilation this clause describes.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Sprinklers (category 3)

ADB asks for a care home to be fitted with a sprinkler system throughout the building, whatever its height, in accordance with Appendix E, which sends residential buildings to BS 9251.

  • A system installed to meet Part B is treated as a life safety system.
  • BS 9251 puts residential care premises with more than 10 residents in category 3: a design density of 2.80 mm/min over 2 to 4 sprinklers with 30 minutes of water.
  • Heads are recommended in all parts, but the standard lets some be left out unless the fire strategy or risk assessment asks for them: bathrooms, shower rooms and WCs under 5 m2 with lining classes it lists and not prepared for white goods such as washing machines, dryers, electric showers or water heaters, enclosed stairs, ceiling voids, enclosed shafts, small cupboards and roof voids nobody uses.
  • A zone should not cover more than one floor, with a lockable full-bore stop valve and a quarter turn drain valve, and no more than 500 sprinklers.

A higher density, set by Table 2 note C, is a choice a designer can make where residents are vulnerable.

Here the system is category 3, with one zone for each floor.

  • The model chooses the higher density of note C for the residential areas: it is a choice a designer can make where residents are vulnerable, and BS 9251 does not require it for every care home.
  • The en-suites of 4.0 to 4.8 m2 have no head, as clause 5.4 allows.
  • The one on the second floor measures 5.1 m2, so clause 5.4 does not let it be left out, and the model shows a head there.
In existing buildings

Homes designed under the earlier text (notified before 2 March 2025, with work started soon after) may have no sprinklers.

  • The old para 2.46 let a sprinklered home drop the closers on bedroom doors, put more than 10 beds in a protected area and put more than one bed in a room, and all three went in 2025 (ADB 2019 edition para 2.46; the 2025 amendments).
  • GuidanceADB Vol 2, para 2.46“Care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E.”
  • GuidanceADB Vol 2, Appendix E, para E3Where sprinklers are called for, they should be provided throughout the building. For residential buildings they should follow BS 9251. Any system installed to satisfy Part B should be given additional measures to improve reliability and availability and is regarded as a life safety system.
  • StandardBS 9251, Table 1 (opens in a new tab)Residential care premises with more than 10 residents are category 3.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, Table 2, note C (opens in a new tab)Category 3: a minimum design density of 2.80 mm/min, 2 to 4 design sprinklers and 30 minutes of supply. Note C raises the density where a higher fire safety risk applies, to 4 mm/min for a single head or 2.8 mm/min for up to four heads operating.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, clause 4.2.3.1 (opens in a new tab)Aspects of additional risk, such as a higher fire safety risk or vulnerable occupants, can call for enhancements: a higher category, a higher design density or a more resilient system, recorded on the compliance certificate.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, clause 5.1 (opens in a new tab)A system divided into zones has zones of no more than one floor, each with a lockable full-bore stop valve and a quarter turn drain valve, and no more than 500 sprinklers. Parts needing service are placed where they can be reached.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, clause 5.4 (opens in a new tab)Sprinkler protection should be provided in all parts of the premises, but may be omitted from the listed areas unless a fire strategy or risk assessment asks for it: bathrooms, shower rooms and WCs under 5 m2 with the listed linings and not prepared for white goods such as washing machines, dryers, electric showers or water heaters; enclosed staircases and shafts of the listed materials; ceiling voids; cupboards under 2 m2 or with a least dimension of 1 m or less; and uninhabited roof voids.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.

What a fire risk assessor checks

  1. Each zone’s stop valve is the lockable, monitored type, with its flow alarm switch

    Benchmark: BS 9251 recommends zones of no more than one floor, each with a lockable full-bore stop valve, and parts that need service placed where they can be reached.

    • StandardBS 9251, clause 5.1A system divided into zones has zones of no more than one floor, each with a lockable full-bore stop valve and a quarter turn drain valve, and no more than 500 sprinklers. Parts needing service are placed where they can be reached.
  2. The system is inspected and tested at least once a year by a competent person, who signs the logbook

    Benchmark: BS 9251 recommends an annual inspection and test by a competent person, who signs the logbook.

    • StandardBS 9251, clause 7.1.1The system is inspected and tested at least once a year by a competent person, who signs the logbook.
  3. When the system is shut down there are set arrangements: restore it quickly, shut down at low-risk times, no hot work, extra patrols, and tell the fire and rescue service

    Benchmark: The 2006 guide asks that where sprinklers are part of the fire strategy the emergency plan covers the times they are out of action, with the measures it lists.

    • GuidanceFire safety risk assessment: residential care premises, page 66If a sprinkler system is part of the fire strategy, management procedures cover the times it is out of action: restore it quickly, limit planned shutdowns to low-risk periods, avoid hot work, train staff in extra duties and patrols, revise the evacuation strategy where needed, and inform the fire and rescue service.
Show in the 3D model

Fire detection (Category L1)

  • Detection and alarm
Show in the 3D model

ADB asks for a fire detection and alarm system to L1 standard, in accordance with BS 5839-1.

  • BS 5839-1:2025 lists residential care premises as category L1, which covers every room and area, with exceptions for low-risk toilets, shower rooms and bathrooms, toilet lobbies, small cupboards and some shallow voids.
  • Where people sleep, the standard recommends smoke, carbon monoxide fire or multi-sensor detectors, not heat detectors.
  • Where residents are likely to need staff help to get out and more than ten people sleep, it recommends an addressable system, and it names residential care premises.

Here the system is L1 and addressable, with smoke detectors in the bedrooms, as BS 5839-1:2025 recommends where people sleep, and heat detectors in the kitchen, laundry and plant room.

In existing buildings

The 2006 guide, written for existing homes, asks for the L1 system of BS 5839-1 where more than ten residents are above the ground floor or many depend on staff to escape.

  • It describes a lower category, which covers the escape routes, the rooms opening on to them and high-risk areas, for larger premises where every resident can evacuate without help (page 60).
  • GuidanceADB Vol 2, para 2.41“A fire detection and alarm system should be provided to L1 standard in accordance with BS 5839-1.”
  • StandardBS 5839-1, clause 7.9 (opens in a new tab)An L1 system covers every room and area. The exceptions are low-risk toilets, shower rooms and bathrooms, toilet lobbies, cupboards under about 1 m2 and some shallow voids.Why it applies here: ADB asks for an L1 system in a care home, and this clause says what L1 covers. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 7.10 (opens in a new tab)Where people sleep, in an L1 room whose occupants need warning of a fire in that room, the standard recommends smoke detectors, combustion gas fire detectors or multi-sensor detectors, not heat detectors.Why it applies here: People sleep in a care home’s bedrooms, which is where this clause applies. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 7.12 (opens in a new tab)Where occupants are likely to need staff help to escape and more than ten people sleep, the system should be addressable. Residential care premises are named.Why it applies here: A care home with more than ten residents is the case this clause names. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, Table A.1 (opens in a new tab)Annex A (informative) lists residential care premises as category L1.Why it applies here: ADB asks for L1 in a care home, and the standard’s own table lists residential care premises under it. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • GuidanceFire safety risk assessment: residential care premises, page 60In larger premises where all the residents can evacuate themselves without staff help, the system should include detectors in all the escape routes, in any room opening on to one and in other high-risk areas, which is a lower category of BS 5839-1 than L1. In other larger premises, particularly those with more than ten residents above the ground floor or a significant proportion dependent on staff to escape, a more comprehensive system covering all areas, the category L1, is appropriate.
Show in the 3D model

Call points, sounders and beacons

  • Detection and alarm
Show in the 3D model

BS 5839-1:2025 recommends an alarm of at least 65 dB(A) throughout, 60 dB(A) in stairways and in enclosures of up to about 60 m2, and no more than 120 dB(A).

  • In care home bedrooms its note says levels well above the minimum might distress residents.
  • It recommends 75 dB(A) at the bedhead only where the system is meant to wake people, and its note says this does not apply where it is not, giving residential care as the example.
  • Residential care premises follow the sound level clause.
  • For people with hearing difficulties the 2006 guide says visual beacons and vibrating devices linked to the alarm are among the popular systems.

Here a call point stands beside every stair door and final exit, and there are sounders in the corridors, day rooms and bedrooms.

  • They sound at the general 65 dB(A) level in the bedrooms because the strategy is staff-led and the alarm is not meant to wake residents.
  • StandardBS 5839-1, clause 15.1.1 a) and b) (opens in a new tab)The alarm should reach at least 65 dB(A) throughout, with 60 dB(A) in stairways and in enclosures up to about 60 m2, and no more than 120 dB(A). Note 1 says that in care home bedrooms levels well above these minima might distress residents. 75 dB(A) at the bedhead is recommended only where the system is meant to wake people, and Note 3 says it does not apply where it is not, giving residential care as the example.Why it applies here: The bedrooms have sounders at the general level, not the 75 dB(A) at the bedhead, since the alarm is not meant to wake residents. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 15.3.2 (opens in a new tab)Residential care premises follow clause 15.1.1.Why it applies here: This clause names residential care premises. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • GuidanceFire safety risk assessment: residential care premises, page 59Where people have hearing difficulties and are likely to be alone, other means of raising the alarm should be considered. Among the most popular systems are visual beacons and vibrating devices or pagers linked to the fire alarm.
Show in the 3D model

Emergency lighting

  • Means of escape
Show in the 3D model

ADB Table 5.1 asks for escape lighting on all common escape routes in residential buildings, and in any building in toilets of at least 8 m2, electricity and generator rooms, the switch or battery room for the emergency lighting and emergency control rooms.

  • The lighting to an escape stair is on its own circuit, and escape lighting follows BS 5266-1.
  • BS 9991 recommends emergency lighting in every area of a care home, including residential, escape, ancillary and non-residential accommodation.
  • BS 5266-1:2025 recommends 3 hours of emergency lighting in sleeping accommodation and names care homes.
  • It recommends a function check at least monthly, a full rated-duration test of every luminaire at least once a year at a time of least risk or on alternate luminaires 24 hours apart, results kept in the logbook, and notes the system is not fully working until the batteries have recharged.

Here emergency lighting covers every area, bedrooms included, and lasts 3 hours.

  • GuidanceADB Vol 2, Table 5.1Provisions for escape lighting: in residential buildings, all common escape routes (except in two storey blocks of flats); in any purpose group, toilet accommodation of at least 8 m2, electricity and generator rooms, switch and battery rooms for the emergency lighting system, and emergency control rooms.
  • GuidanceADB Vol 2, para 5.26Escape stair lighting should be on a separate circuit from the electricity supply to any other part of the escape route.
  • GuidanceADB Vol 2, para 5.27Escape lighting should conform to BS 5266-1.
  • StandardBS 9991, clause 56.4 (opens in a new tab)Emergency lighting to BS 5266-1 is recommended in all areas of a care home, including residential, common escape routes, ancillary and non-residential accommodation.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
  • StandardBS 5266-1, clause 9.2 (opens in a new tab)Sleeping accommodation has 3-hour emergency lighting, and Note 1 names care homes. The commentary allows for the building being reoccupied, or evacuation delayed, once normal lighting is back.Why it applies here: Every bedroom has emergency lighting for 3 hours. ADB names the 2016 edition; this page uses the current edition, BS 5266-1:2025.
  • StandardBS 5266-1, clause 12 (opens in a new tab)Routine inspections and tests follow BS EN 50172: a function check at least monthly, a full rated-duration test of every luminaire at least once a year at a time of least risk or on alternate luminaires 24 hours apart, a visual inspection each year, a photometric check at least every 5 years, and results in the logbook. The system is not fully working until the batteries recharge.Why it applies here: ADB asks for escape lighting to follow BS 5266-1, and this clause says how it is kept working. ADB names the 2016 edition; this page uses the current edition, BS 5266-1:2025.

What a fire risk assessor checks

  1. There is a monthly function test of every luminaire and an annual full-duration test. After a full discharge the building is not relied on until the batteries have recharged, or other arrangements are made, because people sleep here

    Benchmark: The 2006 guide asks for a monthly function test and an annual full discharge test, and says the premises should not be occupied until the system is fully working unless alternative arrangements are made. BS 9991 recommends a daily check that every lamp of a maintained system is lit and a monthly simulated failure.

    • GuidanceFire safety risk assessment: residential care premises, page 105Emergency escape lighting is tested monthly by operating the test facility and annually by a full discharge test. Batteries typically take 24 hours to recharge and the premises should not be occupied until the system is fully working unless alternative arrangements have been made, which matters most in premises where people sleep every night.
    • StandardBS 9991, Annex I, I.2.4 and I.4.3The standard recommends a daily check that every lamp of a maintained system is lit, and a monthly test in which a failure of the normal lighting is simulated and every luminaire and exit sign is inspected.
  2. The annual full-duration test is done at a time of least risk, or on alternate lights a day apart, so the building is never left without charged lights

    Benchmark: BS 5266-1 recommends a full rated-duration test every year at a time of least risk, or on alternate luminaires 24 hours apart, and says the system is not fully working until the batteries recharge.

    • StandardBS 5266-1, clause 12Routine inspections and tests follow BS EN 50172: a function check at least monthly, a full rated-duration test of every luminaire at least once a year at a time of least risk or on alternate luminaires 24 hours apart, a visual inspection each year, a photometric check at least every 5 years, and results in the logbook. The system is not fully working until the batteries recharge.
Show in the 3D model

Fire safety signs

  • Means of escape
Show in the 3D model

ADB asks for every doorway or exit that gives access to a means of escape, other than exits in ordinary use such as main entrances, to carry an exit sign.

  • Refuges and evacuation lifts are clearly identified, with a blue mandatory sign worded “Refuge - keep clear” in protected lobbies and stairways.
  • Fire doors are marked on both sides with a sign to BS 5499-5: “Fire door keep shut”, “Fire door keep locked shut”, or “Automatic fire door keep clear” where a door is held open by an automatic release mechanism or free swing device.
  • Cupboards and service ducts are marked on the outside only, and bedroom doors are exempt only in residential (other) premises.

Here there are exit signs at every exit not in ordinary use.

  • “Refuge - keep clear” is at the six refuges, and the “Evacuation lift” sign at Lift 2 only.
  • “Automatic fire door keep clear” is on doors held open or free-swing, including the bedroom doors, and “Fire door keep locked shut” on the outside of the riser doors.
  • GuidanceADB Vol 2, para 5.28Every doorway or other exit providing access to a means of escape, other than exits in ordinary use such as main entrances, should be distinctively and conspicuously marked by an exit sign in accordance with BS ISO 3864-1 and BS 5499-4.
  • GuidanceADB Vol 2, para 3.8Refuges and evacuation lifts should be clearly identified. In protected lobbies and protected stairways there should be a blue mandatory sign worded “Refuge - keep clear” in addition to fire safety signs.
  • GuidanceADB Vol 2, para C11All fire doorsets other than those listed in C12 should be marked on both sides, except those to cupboards and service ducts, which are marked on the outside, with “Fire door keep shut”, “Fire door keep locked shut” or, where held open by an automatic release mechanism or free swing device, “Automatic fire door keep clear”.
  • GuidanceADB Vol 2, para C12Doors to and within flats and dwellinghouses, bedroom doors in ‘residential (other)’ premises and lift entrance and landing doors need not carry the signs.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Service risers

  • Compartmentation
Show in the 3D model

A riser or service shaft that links compartments is a protected shaft, and its doors take half the fire resistance of the wall they are in, at least 30 minutes.

  • ADB asks for every fire door to have a self-closing device, except doors to cupboards and to service ducts that are normally locked shut.
  • Those doors are marked “Fire door keep locked shut”, on the outside only, and kept locked.
  • Parts of a sprinkler system that need servicing, such as zone valves, are placed where they can be reached, in communal locations for example, as BS 9251 recommends.

Here the risers are protected shafts, their doors E 30, kept locked shut and marked “Fire door keep locked shut” on the outside only.

REI 60The risers are protected shafts, which take the period Table B2 sets, 60 minutes here, with E 30 doors kept locked shut.

  • GuidanceADB Vol 2, Table C1, item 2(d)A door enclosing a protected shaft forming a lift or service shaft: half the period of fire resistance of the wall in which it is fitted, but 30 minutes minimum.
  • GuidanceADB Vol 2, para C5All fire doorsets should be fitted with a self-closing device, except fire doorsets to cupboards, fire doorsets to service ducts normally locked shut, and fire doorsets within flats and dwellinghouses.
  • GuidanceADB Vol 2, para C11Fire doorsets are marked on both sides, except those to cupboards and service ducts, which are marked on the outside, and a door kept locked is marked “Fire door keep locked shut”.
  • StandardBS 9251, clause 5.1 (opens in a new tab)The system is designed to be easy to maintain, with parts needing service or adjustment, such as zone valves, in accessible locations, for example communal ones.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.

What a fire risk assessor checks

  1. No combustible storage in electrical cupboards and risers, and the fixed wiring is inspected by a competent electrician at regular intervals

    Benchmark: The 2006 guide asks for combustible material not to be piled against electrical equipment and for all electrical installations to be inspected regularly by a competent electrician.

    • GuidanceFire safety risk assessment: residential care premises, pages 48, 51 and 52Combustible material is not piled against electrical equipment, and all electrical installations are inspected at regular intervals by a competent electrician.
  2. The fire dampers are closed by a simulated alarm every week, and a competent person inspects and tests them every year

    Benchmark: BS 9991 recommends simulating actuation of the smoke control systems and fire damper control panels every week, with the dampers seen to close, and an annual inspection and performance test of the fire dampers by a competent person.

    • StandardBS 9991, Annex I, I.3.5 and I.7The standard recommends that the actuation of the smoke control systems and fire damper control panels is simulated every week, with the fire dampers seen to close, and that fire dampers and their controls are inspected and performance tested every year by a competent person.
Show in the 3D model

Nurse station and evacuation aids

  • Means of escape
Show in the 3D model

How many residents a protected area can hold depends on the staff likely to be available and the help residents need.

  • ADB asks for that assessment to be handed over with the building’s fire safety information, along with any provision for evacuating disabled people that can be used in personal emergency evacuation plans.
  • The Fire Safety Order requires the responsible person to nominate enough competent people to carry out the evacuation.
  • The 2006 guide, written for existing homes, says it should be possible to evacuate a protected area within 2½ minutes of the alarm using the staff present, as a starting point for the assessment, tested by a simulated evacuation at the lowest staffing, as at night.
  • NFCC guidance says night staffing can be as low as two or three nursing staff in smaller homes, that hoists, evacuation chairs, blankets and mats are tiring to use, and that research has shown two staff take about 2.5 minutes for each resident with impaired mobility.
  • The 2006 guide says stairlifts should not be used for emergency evacuation.

Here each upper floor’s nurse station holds the alarm repeater, two evacuation mats, and an evacuation chair stands at each upper floor stair.

  • Seven waking staff at night is an INFIRISK teaching assumption: against NFCC’s figure of about 2.5 minutes for two staff to move each resident with impaired mobility, and the 2006 guide’s 2½ minutes for a protected area, that is the tension the assessment of beds in para 2.39 has to settle.
  • Personal emergency evacuation plans for residents who need help are supported by the fire safety information handed over (para 19.5(c)).
  • A competent person helping with the assessment should be matched to the premises: PAS 79-1 says a two-storey care home is likely to put its occupants at more risk than a 20-storey office.
  • GuidanceADB Vol 2, para 2.39The number of residents’ beds in protected areas should be based on an assessment of the number of staff likely to be available and the level of assistance residents may need. The maximum number of beds in one protected area should not exceed 10.
  • GuidanceADB Vol 2, para 19.5(c)Fire safety information should include any provision enabling the evacuation of disabled people, which can be used when designing personal emergency evacuation plans.
  • GuidanceADB Vol 2, para 19.5(d)“Information for care homes should include the assessment for the number of beds in a compartment, as this should set out the expected number of staff and level of assistance of residents (see paragraph 2.39).”
  • Ongoing dutyFire Safety Order 2005, Article 15(1)(b)The responsible person must nominate a sufficient number of competent people to carry out the procedures for serious and imminent danger, so far as they concern getting people out of the premises.
  • GuidanceFire safety risk assessment: residential care premises, pages 68 to 70It should be possible, in normal operating conditions, to evacuate any protected area in 2½ minutes using the staff present. The time is checked by a simulated evacuation assuming the lowest staffing, as at night, and the 2½ minutes is a starting point for the assessment. If the movement times are excessive the options include a smaller protected area, more staff, fewer residents in the area or a sprinkler system.
  • GuidanceFire safety risk assessment: residential care premises, page 75Where an escape plan moves people with mobility impairments down stairs by hand, staff need to be trained, available and able, the process regularly practised, and equipment such as evacuation chairs considered. Stairlifts should not be used for emergency evacuation.
  • GuidanceCare and nursing homes: short term staffing shortages and implications for evacuation strategies and operational response, section 5.5At night nursing staff can be as few as two or three in smaller homes. Using hoists, evacuation chairs, blankets and evacuation mats can be very tiring and stressful for staff and can slow them down.
  • GuidanceCare and nursing homes: short term staffing shortages and implications for evacuation strategies and operational response, section 5.6Research has shown that it can take two staff about 2.5 minutes to evacuate each resident with impaired mobility, so moving every resident into an adjacent protected area could take more than twenty minutes. The guidance cites no study.
  • StandardPAS 79 Fire risk assessment. Code of practice (parts 1 and 2), PAS 79-1:2020, clause 7 (opens in a new tab)The specification’s commentary says only competent people carry out an assessment and its reviews, and that competence should rise with risk and complexity. Risk is not simply a matter of height: it says a two-storey residential care home is likely to put its occupants at more risk than a 20-storey office.Why it applies here: The person who helps with a care home’s assessment is chosen to match its risk, and PAS 79-1 is the code of practice for how an assessment is made.

What a fire risk assessor checks

  1. Evacuation aids are provided, and evacuation chairs where stairs are used, with stairlifts never used to evacuate

    Benchmark: NFCC guidance names hoists, evacuation chairs, blankets and evacuation mats as the aids care homes use, and the 2006 guide asks for evacuation chairs to be considered where stairs are used and says stairlifts should not be used.

    • GuidanceCare and nursing homes: short term staffing shortages and implications for evacuation strategies and operational response, section 5.5At night nursing staff can be as few as two or three in smaller homes. Using hoists, evacuation chairs, blankets and evacuation mats can be very tiring and stressful for staff and can slow them down.
    • GuidanceFire safety risk assessment: residential care premises, page 75Where an escape plan moves people with mobility impairments down stairs by hand, staff need to be trained, available and able, the process regularly practised, and equipment such as evacuation chairs considered. Stairlifts should not be used for emergency evacuation.
  2. A designated person in charge is on the premises whenever residents are, and agency and temporary staff are trained in the evacuation procedure before their first shift

    Benchmark: The 2006 guide asks for a manager or designated person in charge on the premises while residents are there, and for training of new, agency and temporary staff before they start.

    • GuidanceFire safety risk assessment: residential care premises, page 45The manager, or a designated manager, should be in charge of the premises and present on them for the whole time that residents occupy them, and kept free from work that would stop them being available at once if the alarm sounds.
    • GuidanceFire safety risk assessment: residential care premises, page 26The evacuation of residents will in almost all cases rely entirely on the action of staff, so all staff, including agency and temporary staff, should be fully trained in the evacuation procedures for the premises.
    • GuidanceFire safety risk assessment: residential care premises, page 40Fire safety training should be provided to new, agency and temporary staff before they start their duties, repeated periodically where appropriate, and tested by fire drills.
  3. Staff are trained to use the evacuation aids quickly and with as little distress to the resident as possible

    Benchmark: The 2006 guide asks for staff who physically move residents with evacuation aids to be trained to deploy them as quickly and efficiently as possible, with as little distress to the resident as possible.

    • GuidanceFire safety risk assessment: residential care premises, page 114Where residents of poor mobility are physically moved by staff and evacuation aids are provided, staff should be trained to deploy and use them as quickly and efficiently as possible and with as little distress to the resident as possible.
Show in the 3D model

External walls and windows

The surface of an external wall is held to a class of reaction to fire that depends on the building’s height and its distance from the boundary.

  • For a residential building (purpose groups 1 and 2) 11 m high or less, ADB Table 12.1 asks for class B-s3, d2 or better within 1000 mm of the relevant boundary and sets no provisions beyond that distance.
  • Above 11 m the class is A2-s1, d0 or better.
  • If a building is fitted throughout with sprinklers to Appendix E, ADB allows the boundary distance to be halved, to a minimum of 1 m, or the unprotected area to be doubled.

Here the building is under 11 m high, so Table 12.1 asks for class B-s3, d2 or better within 1000 mm of the relevant boundary and nothing beyond.

  • The building is sprinklered throughout, which is what lets ADB halve the boundary distance (para 13.22).
  • GuidanceADB Vol 2, Table 12.1Reaction to fire of the external surface of walls, all residential purpose groups (1 and 2): more than 11 m high, class A2-s1, d0 or better; 11 m or less, class B-s3, d2 or better less than 1000 mm from the relevant boundary and no provisions at 1000 mm or more.
  • GuidanceADB Vol 2, para 13.22If a building is fitted throughout with a sprinkler system in accordance with Appendix E, either the boundary distance can be halved, to a minimum of 1 m, or the amount of unprotected area can be doubled.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Wheeled bins are kept in a secure compound away from the building, never against it, and skips are at least 6 m away

    Benchmark: The 2006 guide asks for wheeled bins to be secured in a compound so they cannot be moved against the building, and for skips to be at least 6 m from the premises.

    • GuidanceFire safety risk assessment: residential care premises, pages 46 and 57Wheeled bins used outside are secured in a compound so they cannot be moved against the building and set on fire, and skips should normally be at least 6 m from the premises.
Show in the 3D model

The ground floor and the grounds

Fire appliance access

ADB sets how much of a building’s perimeter a fire engine should reach by the building’s total floor area and the height of its top storey.

  • For 2000 m2 to 8000 m2 with a top storey up to 11 m, vehicle access for a pump is provided to 15 per cent of the perimeter, along the building.
  • A small building of up to 2000 m2 follows the less demanding of 15 per cent of the perimeter or 45 m from every point of the footprint.
  • Every elevation with access has a door at least 750 mm wide, and no more than 60 m from a door to the next door or the end of the elevation.
  • A dead-end access route longer than 20 m needs a turning facility.
  • For a pump, ADB’s typical route is 3.7 m between kerbs, gateways of 3.1 m, a turning circle of 16.8 m between kerbs or 19.2 m between walls, 3.7 m clear height and 12.5 tonnes.

Here the outer walls measure about 220 m round, so 15 per cent is 33 m, and the hardstanding along the west frontage is 36 m long.

  • The floor area is between 2000 m2 and 8000 m2 and the top storey is under 11 m, so the 15 per cent for a pump appliance applies.
  • The main entrance is the door on that frontage that ADB asks for where a fire engine has access.
  • The turning head in front of it is the turning facility a dead-end route of more than 20 m needs.
  • GuidanceADB Vol 2, para 15.2For buildings other than small ones, provide vehicle access in accordance with Table 15.1.
  • GuidanceADB Vol 2, para 15.3Every elevation to which vehicle access is provided should have a door, a minimum of 750 mm wide, with a maximum of 60 m between doors, or between a door and the end of the elevation.Why it applies here: The main entrance is the door on the west frontage, where the hardstanding is.
  • GuidanceADB Vol 2, para 15.8Where access is provided in accordance with Table 15.1 for a building up to 11 m high (other than a small building), pump appliance access should be adjacent to the building for the specified percentage of the total perimeter.
  • GuidanceADB Vol 2, para 15.10Dead-end access routes longer than 20 m require turning facilities, as in Diagram 15.3, complying with Table 15.2.Why it applies here: The way in from the access drive is a dead end of more than 20 m, so the turning head in front of the entrance is the turning facility.
  • GuidanceADB Vol 2, Table 15.1Vehicle access to buildings not fitted with fire mains: total floor area 2000 m2 to 8000 m2 and top storey up to 11 m, 15% of the perimeter for a pump; over 11 m, 50% for a high reach appliance. Up to 2000 m2 with a top storey up to 11 m, paragraph 15.1 gives the less onerous of 15% of the perimeter or within 45 m of every point of the footprint.Why it applies here: The floor area is in the 2000 m2 to 8000 m2 band and the top storey is 6.3 m, so 15 per cent of the perimeter, about 33 m of about 220 m, for a pump appliance.
  • GuidanceADB Vol 2, Table 15.2Typical vehicle access route for a pump: 3.7 m between kerbs, 3.1 m gateways, turning circle 16.8 m between kerbs and 19.2 m between walls, 3.7 m clearance, 12.5 tonnes.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The access road and hardstanding are kept clear for fire engines, and the fire and rescue service is told if building work blocks them

    Benchmark: The 2006 guide asks for daily checks that fire engines have clear access, for access roads and hardstanding to be maintained and available at all times, and for the fire and rescue service to be told when access roads become unusable.

    • GuidanceFire safety risk assessment: residential care premises, pages 24, 66 and 113Staff check daily that fire engines have clear access. Facilities such as access roads and hardstanding are properly maintained and available at all times, and if the access roads become unusable, for example because of building work, the fire and rescue service is told.
Show in the 3D model

Private fire hydrant

ADB asks for additional fire hydrants where both of these apply: the building has a compartment of more than 280 m2, and it is erected more than 100 m from an existing hydrant.

  • For a building without fire mains the hydrants should be within 90 m of an entrance to the building and no more than 90 m apart.
  • Each hydrant is marked by a plate fixed nearby in a conspicuous position, to BS 3251, and BS 9990 gives guidance on private hydrants.

Where the position of the public hydrant is not known, a designer cannot tell whether the second condition applies.

Here the day rooms and entrance area on the ground floor is a compartment of more than 280 m2 (about 380 m2 with the walls inside it), so the first of the two conditions is met.

  • The public hydrant’s position is not known, so the second cannot be checked.
  • The model shows a private pillar hydrant beside the turning head, 12.0 m from the main entrance and inside the 90 m ADB asks for.
  • GuidanceADB Vol 2, para 16.8A building needs additional fire hydrants if it has a compartment with an area more than 280 m2 and is being erected more than 100 m from an existing fire hydrant.Why it applies here: The first condition is met, a compartment of more than 280 m2. The public hydrant’s position is not known, so the model shows a private hydrant.
  • GuidanceADB Vol 2, para 16.9Where additional hydrants are needed, for buildings not provided with fire mains they should be within 90 m of an entrance to the building and a maximum of 90 m apart.Why it applies here: The hydrant is 12.0 m from the main entrance, inside the 90 m.
  • GuidanceADB Vol 2, para 16.10Each fire hydrant should be clearly indicated by a plate, fixed nearby in a conspicuous position, in accordance with BS 3251.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The hydrant is kept clear and its indicator plate is in place

    Benchmark: BS 9991 recommends a weekly inspection that nothing obstructs a hydrant, its indicator plate is in position and its isolating valves are locked open, and the 2006 guide’s sample checklist asks whether vehicles block a hydrant or the way to it.

    • StandardBS 9991, Annex I, I.3.7The standard recommends that every fire hydrant is inspected once a week: nothing obstructs access, the indicator plate is in position and the isolating valves are locked open.
    • GuidanceFire safety risk assessment: residential care premises, page 118The sample checklist asks, daily and every three months, whether vehicles are blocking fire hydrants or access to them.
Show in the 3D model

Fire and rescue service sprinkler inlet

  • Sprinklers
  • Firefighting
Show in the 3D model

On a sprinkler system fed from its own tank and pumps, BS 9251 lists a fire and rescue service inlet among the ways to add to the water supply.

  • The inlet connection is labelled, and the system’s maximum working pressure is shown at the inlet.
  • It usually sits downstream of the pumps, after the check valve.
  • Where that is not possible it can be used to refill the tanks, taking care not to contaminate the public water supply.

Here the inlet is a cabinet on the outside of the service wing’s west wall, between the laundry and servery windows, with its sign, facing the hardstanding where a pump appliance parks, so a fire engine can add to the tank’s supply.

  • BS 9251 lists the inlet among the measures that make a system more resilient where occupants are vulnerable, as residents of a care home are.
  • StandardBS 9251, clause 4.2.4 (opens in a new tab)On dedicated pump and tank fed installations, a fire and rescue service inlet can supplement the water supply. Sprinkler inlet connections are labelled and the system’s maximum working pressure is shown at the inlet. Inlets usually sit downstream of the pumps after the check valve; where that is not possible, the inlet can refill the tanks without contaminating the public water supply.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, clause 4.2.3.1 (opens in a new tab)Aspects of additional risk, such as a higher fire safety risk or vulnerable occupants, can call for enhancements: a higher category, a higher design density or a more resilient system, recorded on the compliance certificate.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
Show in the 3D model

Top floor 6.3 m: 60 minutes

  • Compartmentation
Show in the 3D model

The height of the top floor above ground sets the fire resistance of the structure.

  • ADB measures it as Diagram D6 shows, and Table B2 gives a residential (institutional) building 30 minutes where the top floor is up to 5 m, 60 minutes up to 18 m, 90 minutes up to 30 m and 120 minutes above that.
  • A care home whose top floor is more than 5 m and up to 11 m above ground therefore takes 60 minutes, and that is the figure used for its compartment walls and floors.
  • A higher-risk building in England is one at least 18 m high or with at least 7 storeys that is of a description in regulations, and the regulations name care homes.
  • A care home under 18 m with fewer than 7 storeys is not a higher-risk building, a point the coroner raised in Regulation 28 report 2022-0043.

Here the top floor, the second floor in the roof, is 6.3 m above the ground: more than 5 m, so Table B2 gives 60 minutes, and under 11 m.

  • The building has three storeys and is under 18 m high, so it is not a higher-risk building: the law’s height test is at least 18 m or at least 7 storeys.
  • GuidanceADB Vol 2, Table B2Residential (institutional), height of top floor above ground in a building or separated part: up to 5 m, 30 minutes; up to 11 m, 60 minutes; up to 18 m, 60 minutes; up to 30 m, 90 minutes; more than 30 m, 120 minutes.Why it applies here: The top floor is 6.3 m above the ground, more than 5 m and under 11 m, so the 60 minute figure.
  • GuidanceADB Vol 2, Diagram D6The height of the floor of the top storey above ground level is measured as Diagram D6 in Appendix D shows (Appendix A, definitions).
  • LawBuilding Safety Act 2022, Section 31 (Building Act 1984, section 120D(2)(a))A higher-risk building in England is a building that is at least 18 metres in height or has at least 7 storeys, and is of a description set out in regulations.Why it applies here: The building has three storeys and is under 18 m high, so it is under both limits.
  • LawHigher-Risk Buildings (Descriptions and Supplementary Provisions) Regulations 2023, Regulation 2The descriptions of building that can be a higher-risk building are a building with at least two residential units, a care home and a hospital. The height and storey test of section 120D still applies to each.
  • GuidanceRegulation 28 report to prevent future deaths 2022-0043, section 5The coroner’s concerns were that sprinkler systems were not mandatory for care homes whose residents have limited or no independent mobility, and that such homes were not higher-risk buildings unless they were at least 18 metres high or had at least 7 storeys.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Main entrance and final exits

  • Means of escape
  • Firefighting
Show in the 3D model

ADB asks for doors on escape routes to have no lock, latch or bolt, or only simple fastenings that are easy to operate, work from the side people approach from, need no key and need only one action.

  • A door secured by a code, card or biometric should have an override from the escape side, and an electrically powered lock should return to unlocked if the alarm operates, if power or the system fails and when the override is used, the override being a Type A call point.
  • Every protected stairway should lead to a final exit, directly or through an exit passageway.
  • Where fire engines have access, each elevation with access should have a door at least 750 mm wide, and no more than 60 m between doors or from a door to the end of the elevation.
  • Where elderly people may wander, the 2006 guide accepts security latches on final exits if procedures keep the doors available in an emergency, staff are trained and the emergency plan covers it.
  • It says any device that impedes escape, or that is hard to operate, is not acceptable.

Here the main entrance, the stairs’ external doors and the south passage door are the final exits.

  • Their electric locks release when the alarm operates, when the power or the system fails and on a Type A call point override on the escape side, as ADB asks.
  • A call point stands beside every stair door and final exit.
  • The main entrance is also the door that ADB asks for on the west frontage, where the fire engine has access.
  • GuidanceADB Vol 2, para 5.7Doors on escape routes should not be fitted with a lock, latch or bolt fastenings, or only with simple fastenings that are easy to operate, operable from the side approached by people escaping, operable without a key and without manipulating more than one mechanism. A secure door operated by code, card, proximity or biometric data should have a security mechanism override from the side approached by people escaping.
  • GuidanceADB Vol 2, para 5.8Electrically powered locks should return to the unlocked position if the fire detection and alarm system operates, if there is loss of power or system error and if the security mechanism override is activated. The override should be a Type A call point as described in BS 7273-4, on the side approached by people escaping.Why it applies here: The entrance and the stairs’ external doors have electric locks that release in all three cases.
  • GuidanceADB Vol 2, para 3.36Every protected stairway should lead to a final exit, either directly or via an exit passageway.
  • GuidanceADB Vol 2, para 15.3Every elevation to which vehicle access is provided should have a door, a minimum of 750 mm wide, giving access into the building, with a maximum of 60 m between doors, or between a door and the end of the elevation.Why it applies here: The main entrance is the door on the west frontage where the fire engine has access.
  • GuidanceFire safety risk assessment: residential care premises, pages 29 to 30Exit doors on escape routes and final exit doors should normally open in the direction of travel and be quickly and easily openable without a key. Where elderly people may wander out, final exit doors may have security latches if procedures ensure all such doors are always available in an emergency, staff are trained and the emergency plan includes them.
  • GuidanceFire safety risk assessment: residential care premises, pages 127 to 129Appendix B3 starts from the position that doors on escape routes should not be fitted with locking devices, accepts devices that stop unlimited access but let people open the door easily in a fire, and treats any device that impedes escape as not acceptable. Electrical locks should be linked to the alarm with a bypass for immediate release and a means of manual override.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Fire alarm panel and staff alarm

  • Detection and alarm
Show in the 3D model

The alarm panel shows where the alarm is, and BS 5839-1:2025 recommends a diagram at the panel showing the entrances, main circulation and zones.

  • The standard lists two departures that are never acceptable variations: no zone plan where a storey has more than one zone, and no way of sending alarm signals to an alarm receiving centre in a residential care home.
  • The link does not replace the call: the standard recommends that staff still call 999 or 112.
  • NFCC guidance records the principle that care homes may expect a fire and rescue service response without call filtering, as a matter of general fire service practice.
  • A staff alarm can give staff time to investigate before the full alarm, but in residential care premises the standard recommends no delay in summoning the fire and rescue service.
  • A staff alarm should normally come only from automatic detectors, not call points, heat detectors or sprinklers, and if a call point is to give one, the person using it should not be left in doubt.
  • It turns into the full alarm after a preset time of normally no more than 6 minutes, and a second detector before reset gives the full alarm.

Here the main panel is at reception, with the zone plan beside it and the master station that the refuges’ emergency voice communication outstations talk to, and a repeater panel stands at the nurse station on each upper floor.

  • The first automatic detector gives the staff alarm, and the alarm receiving centre is called at once.
  • After a set time, normally no more than 6 minutes, it becomes the full alarm, and a second detector, a call point, a heat detector or a sprinkler flow switch gives the full alarm straight away.
  • The first fire signal also releases every hold-open and free-swing door in the building and unlocks the electrically locked escape doors.
  • BS 5839-1 recommends no delay in residential care premises, so here the call goes at once.
  • StandardBS 5839-1, clause 6.6 (opens in a new tab)Two departures are never acceptable variations: no zone plan where a storey has more than one zone, particularly where people sleep, and no way of sending alarm signals to an alarm receiving centre in a residential care home.Why it applies here: A care home is the premises both departures are listed for. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 14.2 (opens in a new tab)In an occupied building, summoning the fire and rescue service should always include a 999 or 112 call by the occupants, even where there is an alarm receiving centre link.Why it applies here: The call is recommended in every occupied building, a care home included. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 14.7 (opens in a new tab)Residential care premises have a means of automatic transmission of alarm signals to an alarm receiving centre.Why it applies here: This clause names residential care premises. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 18.2.2 (opens in a new tab)In residential care premises there should be no delay in summoning the fire and rescue service.Why it applies here: This clause names residential care premises. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 18.2.4 (opens in a new tab)Staff alarms should normally be generated only by automatic fire detectors, not by call points, heat detectors or sprinklers; if a call point is to give a staff alarm, the person using it should not be left in doubt.Why it applies here: A staff alarm is the arrangement a care home can use to give staff time, and this clause sets what can start it. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 18.2.7 (opens in a new tab)The staff alarm turns into the full alarm automatically after a preset time, normally no more than 6 minutes.Why it applies here: A staff alarm is the arrangement a care home can use to give staff time, and this clause sets how long it lasts. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 18.2.8 (opens in a new tab)A second detector operating before the alarm is reset gives the full alarm. The note repeats that a delay in calling the fire and rescue service is not appropriate in residential care homes.Why it applies here: This clause names residential care homes. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • StandardBS 5839-1, clause 22.2.5 (opens in a new tab)A diagram on or beside the panel shows the entrances, the main circulation and the zones, as a mimic, a display with back-up or a printed zone plan the right way round. Each repeat panel gets one for its part.Why it applies here: A care home has more than one zone on a storey, so the diagram is what lets staff and the fire service find a fire. ADB names the 2017 edition; this page uses the current edition, BS 5839-1:2025.
  • GuidanceCare and nursing homes: short term staffing shortages and implications for evacuation strategies and operational response, section 2.3NFCC guidance records the principle, from older fire and rescue service guidance on reducing false alarms, that care homes may expect a fire and rescue service response without call filtering, because filtering could delay the critical actions in the first minutes.
  • GuidanceADB Vol 2, para 3.7Refuges should have an emergency voice communication system complying with BS 5839-9, consisting of Type B outstations communicating with a master station in the building control room, if there is one, or next to the fire detection and alarm panel.Why it applies here: The master station is beside the main alarm panel at reception.

What a fire risk assessor checks

  1. There is no call-challenge delay before the fire and rescue service is summoned

    Benchmark: BS 5839-1 recommends no delay in summoning the fire and rescue service in residential care premises.

    • StandardBS 5839-1, clause 18.2.2In residential care premises there should be no delay in summoning the fire and rescue service.
  2. Staff dial 999 on every fire alarm. The automatic link to the alarm receiving centre does not replace the call

    Benchmark: BS 5839-1 recommends that in an occupied building summoning the fire and rescue service always includes a 999 or 112 call by the occupants, even where there is an alarm receiving centre link.

    • StandardBS 5839-1, clause 14.2In an occupied building, summoning the fire and rescue service should always include a 999 or 112 call by the occupants, even where there is an alarm receiving centre link.
  3. After any fire alarm, including a false alarm that is reset, staff check every resident and every fire exit and secured door before standing down

    Benchmark: A coroner’s report after a death following a reset false alarm raised the lack of resident checks and fire exit checks, and the need for clear processes for responding to alarms and for training carers to check residents and fire exits (Regulation 28 report 2024-0481).

    • GuidanceRegulation 28 report to prevent future deaths 2024-0481, sections 4 and 5After a false alarm at night was reset, either no resident checks or inadequate ones were made and some or all fire exits were not checked, and a resident who had got through a door that should have been locked fell down an unheated stairwell leading to an external fire exit, and died. The coroner’s concerns were about training senior staff, clear processes for responding to alarms, and training carers to check residents and fire exits.
  4. A manual call point is operated every week, a different one each time, and the result is recorded in the logbook. A competent person services the system at least every six months

    Benchmark: The 2006 guide asks for a weekly test with a different call point each time and six-monthly servicing by a competent person, and BS 5839-1 recommends the same routine with a logbook.

    • GuidanceFire safety risk assessment: residential care premises, pages 34, 61 and 62The fire detection and warning system is tested once a week, a manual call point being operated each time with a different one in turn, usually with a test key, and a competent person services it every six months. It is good practice to record all tests, false alarms and maintenance.
    • StandardBS 5839-1, clauses 42.1, 43.2 and 48The standard recommends a weekly test through a call point, a different one each week, with the result recorded against the call point’s identity, an inspection and service by a competent person about every six months, and a logbook that records the tests, faults and false alarms.
  5. There is a procedure for meeting the fire and rescue service on arrival and telling them where any residents remain, with up-to-date details of every resident present, including medication and needs, kept ready to hand over

    Benchmark: The 2006 guide asks for procedures for meeting the fire and rescue service on arrival and telling them where any residents remain, and suggests keeping up-to-date details of the residents present, with their medication and special needs.

    • GuidanceFire safety risk assessment: residential care premises, pages 112 and 113The emergency plan includes procedures for meeting the fire and rescue service on arrival and telling them where any residents remain and of any special risks. It can help to keep up to date information on all the residents present, including their medication, special needs and next of kin, and to hand it to the emergency services.
  6. Every false alarm is investigated and recorded, and its cause put right

    Benchmark: The 2006 guide warns that frequent false alarms make people complacent, and asks that false alarms are recorded, and BS 5839-1 keeps the record in the system’s logbook.

    • GuidanceFire safety risk assessment: residential care premises, page 60False alarms from automatic detection are a major problem and, if frequent, people may become complacent and not respond correctly to a real fire.
    • StandardBS 5839-1, clause 48The system’s logbook records tests, faults, false alarms and the action taken, and its commentary points to the Fire Safety Order.
Show in the 3D model

Sprinkler tank and pumps

A sprinkler system needs a reliable water supply: BS 9251 lists mains water, with or without a pump, and a stored supply, with pumps from a tank.

  • A stored supply is sized so that its effective capacity covers the duration for the category, 30 minutes for category 3, allowing for the air gap and unusable water, and the tank is sited so it can be inspected and maintained, with a low-level alarm.
  • In a category 3 system the pumps should be in an area the sprinklers protect or in a fire compartment holding only the sprinkler plant and its electrical equipment, with fire resistance at least equal to the system’s duration, kept above freezing.
  • The standard lists ways to make the system more resilient, such as a back-up power supply to the pumps.
  • ADB asks for the cables to equipment that has to keep working in a fire, such as the pumps, to be protected circuits: PH 30 cable on its own circuit, routed only through areas with negligible fire risk.

Here the pumps and the tank have a room of their own at the north end of the plant room, built to resist fire for 60 minutes, which is more than the 30 minutes of the system’s duration that BS 9251 recommends the room to match.

  • That is a choice, not a minimum.
  • The tank is 4.0 m by 1.9 m and 2.0 m high, 15.2 m3, with 0.6 m left along its south side to inspect it, and there are duty and standby pumps.
  • The cables to the pumps are a protected circuit: PH 30 cable, on its own circuit, routed through areas of negligible fire risk.

REI 60The pumps and the tank have a room of their own, built to resist fire for 60 minutes, with an E 60 door.

  • GuidanceADB Vol 2, para 5.29To limit damage to cables in protected circuits, the cables should be sufficiently robust, their routes carefully chosen or physically protected, and their supports class A1 and as strong as the cable.
  • GuidanceADB Vol 2, para 5.30A protected circuit to operate equipment during a fire should use cable that achieves PH 30, should pass only through parts of the building in which the fire risk is negligible, and should be separate from any circuit provided for another purpose.Why it applies here: The pumps are equipment that has to keep working in a fire, so their cables are a protected circuit of PH 30 cable on their own circuit.
  • StandardBS 9251, clause 5.11.2 (opens in a new tab)Sprinkler systems are connected to a reliable supply, such as the mains, mains boosted by a pump, or a stored supply with pumps from a tank or a pressurised vessel.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, clause 5.11.4.1 (opens in a new tab)A stop valve is placed close to the tank outlet, a low water level alarm is provided for a stored supply, and storage tanks are sited so they can be inspected and maintained.Why it applies here: The 0.6 m along the south side of the tank is its inspection space.
  • StandardBS 9251, clause 5.11.4.2 (opens in a new tab)The effective capacity of a stored supply should cover the duration for the category in Table 2, allowing for the air gap at the top and the unusable water at the base, and the tank has a cover.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, clause 5.12.1 (opens in a new tab)Pump sets for categories 2, 3 and 4 are located in an area protected by the sprinklers or in a fire compartment holding only plant and electrical equipment for the sprinkler system, with fire resistance at least equal to the duration of the system’s operation, where the temperature stays above freezing. Pumps start automatically on demand and are continuously rated.Why it applies here: The room is built to 60 minutes against the 30 minutes of the system’s duration, so it is more than the clause recommends.
  • StandardBS 9251, clause 4.2.4 (opens in a new tab)Ways to improve the system’s resilience include a longer water supply, a back-up power supply to the pumps, additional pumps, remote monitoring of critical components and a fire and rescue service inlet.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
Show in the 3D model

Kitchen

  • Compartmentation
  • Sprinklers
Show in the 3D model

A care home kitchen is ancillary accommodation, so ADB asks for it to be enclosed in fire-resisting construction (at least REI 30).

  • BS 9251 treats a kitchen of 50 m2 or less like the rest of the sprinklered building, and sends a kitchen over 50 m2 to its ordinary-hazard design, with an area of operation of 72 m2.
  • For a kitchen with deep oil cookers, BS 9251 recommends a local application system as well.
  • Residents are not expected to use manual firefighting equipment, so BS 9991 recommends it only in higher-risk rooms such as communal kitchens, and the 2006 guide says that in a care home the emphasis is on the residents’ safety, not fighting the fire.
  • A fire blanket and a suitable extinguisher are kept near the hazard, for staff who know how to use them.
  • The guide asks for a thermostat on deep fat equipment, never leaving it unattended, extract ducting, grease traps and filters cleaned regularly, and the gas, electricity and extract isolation switches near an exit.

In the Home Office incident-level data for care homes in England, 46.1 per cent of fires in the five years to 2025/26 started in a kitchen, by INFIRISK’s count of that file.

Here the kitchen is about 60 m2, over 50 m2, so BS 9251 treats it as an ordinary hazard room.

  • A fryer under the extract canopy has its own suppression system, with a manual release and the gas, electricity and extract isolation switches by the kitchen’s corridor exit.
  • A fire blanket and a Class F extinguisher hang by the kitchen exit, for staff trained to use them.
  • In a care home the emphasis is on the residents’ safety rather than fighting the fire.

Across England, nearly half of fires in care homes start in a kitchen, and cookers, microwaves, hobs, grills and toasters are the source of about four in ten (INFIRISK’s count of the Home Office’s incident-level data, 2021/22 to 2025/26).

REI 30A care home kitchen is ancillary accommodation, enclosed in fire-resisting construction of at least REI 30.

  • GuidanceADB Vol 2, para 2.44Ancillary accommodation, which includes kitchens, should be enclosed by fire resisting construction (minimum REI 30).
  • StandardBS 9251, Table 3, note D (opens in a new tab)A kitchen in residential care premises of 50 m2 or less takes the standard residential density of 2.80 mm/min, and one over 50 m2 is designed to Table 4. Note D says a kitchen with deep oil cookers should have a local application system as well as the sprinklers.Why it applies here: The kitchen is over 50 m2, so it follows Table 4, and its fryer has a local application system as well as the sprinklers.
  • StandardBS 9251, Table 4 (opens in a new tab)Care home kitchens, with ordinary-hazard heads, have an area of operation of 72 m2, and where the compartment is under 50 m2 at most four heads are needed.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9991, clause 56.1 (opens in a new tab)Because residents might not be expected to use manual firefighting equipment, the standard recommends providing it only in higher fire risk areas such as communal lounges, communal kitchens and wardens’ accommodation. Where it is provided, people on the premises should be familiar with it.Why it applies here: The blanket and the extinguisher are by the kitchen exit, for staff who know how to use them.
  • GuidanceFire safety risk assessment: residential care premises, page 23In residential care homes the emphasis should be on the safety of residents rather than on fighting the fire. Extinguishers are used mainly to protect life and help escape, and are otherwise used only if they can be used safely and without risk of trapping the user.
  • GuidanceFire safety risk assessment: residential care premises, page 47In larger premises the cooking range should have an automatic fire suppression system, and in smaller ones a suitable extinguisher and fire blanket. All deep fat cooking equipment should have a thermostat and never be left unattended. Extractor ducting, grease traps and filters should be cleaned regularly, and isolation switches for gas, electricity and extractor fans should be near an exit.
  • GuidanceFire safety risk assessment: residential care premises, page 64Extinguishers are sited close to the hazard, on a stand or hung on a wall at about 1 m to the handle for larger ones and 1.5 m for smaller ones. A foam extinguisher is not suitable for deep-fat fryers or chip pans. In some care homes the risk assessment may need to consider an extinguisher being used as a weapon or vandalised.
  • GuidanceFire safety risk assessment: residential care premises, page 65Fire blankets should be near the hazard and in a position that can be reached safely. They are particularly suitable for kitchens, and light-duty blankets suit small fires in residential care premises involving cooking oils, fat and clothing.
  • GuidanceFire statistics: incident level datasets, Other building fires dataset, 2021/22 to 2025/26INFIRISK’s count of the Home Office incident-level data for fires in nursing homes and retirement care homes in England, 2021/22 to 2025/26: of 2,475 fires, 46.1 per cent started in a kitchen. Cookers, microwave ovens, hot plates and grills together were 39.6 per cent of the ignition sources. The Home Office publishes no table that separates care homes, so these are our counts of its file.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The fryer has a thermostatic control and is never left unattended, and the extract ducting, grease traps and filters are cleaned regularly. The gas, electricity and extract isolation switches are near an exit

    Benchmark: The 2006 guide asks for a thermostat on deep fat equipment, never leaving it unattended, regular cleaning of extractor ducting, grease traps and filters, and isolation switches for gas, electricity and extractor fans near an exit.

    • GuidanceFire safety risk assessment: residential care premises, page 47All deep fat cooking equipment should have a thermostat and never be left unattended. Extractor ducting, grease traps and filters should be cleaned and maintained regularly, and the isolation switches for gas, electricity and extractor fans should be near an exit. Laundry machines should not be overloaded, exhaust filters should be cleaned, cloths and mop heads with chemical residue can spontaneously combust in a dryer, and the laundry should not store other combustible material.
  2. Extinguishers are fixed firmly in their brackets, because one that falls can injure a frail resident, and the Class F extinguisher is within 10 m of the fryer

    Benchmark: BS 5306-8 warns that in care homes an extinguisher knocked off its mounting can injure vulnerable people, and recommends a Class F extinguisher within 10 m of cooking oil.

    • StandardBS 5306, BS 5306-8:2023, clause 8.3 and clause 8.4The standard warns that in care homes an extinguisher that is knocked off its mounting can injure vulnerable people, and recommends recessed housings or cabinets where one could be dislodged. It recommends a Class F extinguisher within 10 m of cooking oil, less 5 m for each door that has to be opened.
Show in the 3D model

Laundry

  • Compartmentation
  • Sprinklers
Show in the 3D model

ADB asks for a laundry room in a care home to be enclosed in fire-resisting construction (at least REI 30), and its travel distances follow Table 2.1 like any other room.

  • BS 9251 sends a care home laundry that stores and processes linen to its ordinary-hazard design, with an area of operation of 100 m2.
  • The 2006 guide calls laundries a high-risk area.
  • It asks that machines are not overloaded, that exhaust filters are cleaned, that cloths and mop heads with chemical residue are kept out of dryers because they can ignite on their own, and that the laundry is not used to store other combustible material.
  • It lists clogged ventilation and poorly cleaned equipment such as tumble driers among the common causes of fire in equipment.

Here the laundry is about 42 m2, with its double door set towards the middle of its east wall so that both far corners are about 8.2 m from it, under the 9 m ADB asks for where travel is possible in one direction only.

  • It has heat detection and ordinary hazard sprinkler heads.

REI 30A laundry room in a care home is enclosed in fire-resisting construction of at least REI 30.

  • GuidanceADB Vol 2, para 2.44Ancillary accommodation, which includes laundry rooms, should be enclosed by fire resisting construction (minimum REI 30).
  • GuidanceADB Vol 2, Table 2.1Maximum travel distance in a residential (institutional) building: 9 m where travel is possible in one direction only, 18 m where it is possible in more than one.Why it applies here: Both far corners of the laundry are about 8.2 m from its door, under the 9 m.
  • StandardBS 9251, Table 3 (opens in a new tab)A laundry with storage and processing of linen, such as an institutional or care home laundry, is designed to Table 4 rather than the standard residential density.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • StandardBS 9251, Table 4 (opens in a new tab)Laundries that store and process linen, with ordinary-hazard heads, have an area of operation of 100 m2.Why it applies here: ADB Appendix E sends sprinkler systems in residential buildings, which includes care homes, to BS 9251.
  • GuidanceFire safety risk assessment: residential care premises, page 47Laundries remain a high-risk area. Washing and drying machines should not be overloaded, exhaust filters should be cleaned and maintenance carried out regularly. Cleaning cloths and mop heads put in dryers can spontaneously combust if any chemical residue is left on them, and the laundry should not be used to store miscellaneous combustible material.
  • GuidanceFire safety risk assessment: residential care premises, page 51Common causes of fire in equipment include blocked ventilation points and inadequate cleaning of equipment such as tumble driers. A competent person should maintain machinery and equipment adequately and regularly.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Drier lint is cleaned and the machines’ ventilation is kept clear

    Benchmark: The 2006 guide lists blocked ventilation points and inadequate cleaning of equipment such as tumble driers among the common causes of fire in equipment, and asks for a competent person to maintain machinery regularly.

    • GuidanceFire safety risk assessment: residential care premises, page 51Common causes of fire in equipment include blocked ventilation points and inadequate cleaning of equipment such as tumble driers. A competent person should maintain machinery and equipment adequately and regularly. Residents, visitors and staff should be discouraged from bringing their own portable heaters.
  2. Machines are not overloaded and exhaust filters are cleaned. Cloths and mop heads with chemical residue are kept out of the dryers, because they can ignite on their own. Nothing combustible is stored in the laundry

    Benchmark: The 2006 guide asks that washing and drying machines are not overloaded, exhaust filters are cleaned, cloths and mop heads with chemical residue are not put in dryers because they can ignite spontaneously, and the laundry is not used to store combustible material.

    • GuidanceFire safety risk assessment: residential care premises, page 47All deep fat cooking equipment should have a thermostat and never be left unattended. Extractor ducting, grease traps and filters should be cleaned and maintained regularly, and the isolation switches for gas, electricity and extractor fans should be near an exit. Laundry machines should not be overloaded, exhaust filters should be cleaned, cloths and mop heads with chemical residue can spontaneously combust in a dryer, and the laundry should not store other combustible material.
  3. Drying is never started near the end of the day or left running out of hours. Each load finishes its cooling cycle and is taken out and shaken out, and only fully cooled laundry is stacked, because oily laundry, can heat up and catch fire on its own after drying

    Benchmark: The insurers’ briefing note on laundries recommends not tumble drying near the end of the working day or leaving cycles to run out of hours, letting the cooling cycle finish, shaking laundry out and storing only fully cooled stock.

    • GuidanceRisk control briefing note 4: Fire safety for laundries with a focus on tumble dryers, section 4, page 3The insurers’ briefing note recommends not tumble drying near the end of the working day or letting cycles run on out of hours, letting the cooling cycle finish before laundry is taken out and shaken out, storing only fully cooled stock, washing oil-contaminated laundry hot enough, and keeping filters and lint clear.
Show in the 3D model

Day rooms (ground floor)

  • Means of escape
  • Compartmentation
Show in the 3D model

A lounge or dining room in a care home is a day room, and ADB asks for it to be enclosed in fire-resisting construction (at least REI 30).

  • Where a storey has areas for eating or drinking and that is not the main use of the building, ADB asks for at least two escape routes from each area, leading to a storey exit without entering a kitchen.
  • Routes are alternatives when they are in directions at least 45 degrees apart, or separated by fire-resisting construction.
  • In a residential (institutional) building travel is limited to 9 m where it is possible in one direction only and 18 m where it is possible in more than one.
  • Where a room has a dead-end part, Diagram 2.1 limits the one-direction part, and the total to the nearer exit should still be within the 18 m.

If the layout of partitions and fittings is not known, direct distances are assessed and taken as two-thirds of the travel distance.

Here the cafe is enclosed in 30 minute construction, as ADB asks of day rooms.

  • The dining room has two ways out that avoid the kitchen: its corridor double door and its servery door into the corridor alcove.
  • The lounge at the east end has a garden door in its south wall as well as its corridor door, so from every corner there are two directions, more than 45 degrees apart.

REI 30A day room in a care home is enclosed in fire-resisting construction of at least REI 30; here the cafe is enclosed in 30 minute construction.

  • GuidanceADB Vol 2, para 2.16If a storey contains areas for consuming food or drink, and that is not the main use of the building, a minimum of two escape routes should be provided from each area (except from inner rooms that meet the conditions in paragraph 2.11), and those routes should lead directly to a storey exit without entering a kitchen or similar area of high fire hazard.Why it applies here: The dining room’s two ways out are its corridor double door and its servery door, and neither passes through the kitchen.
  • GuidanceADB Vol 2, para 2.38Escape routes should not pass through ancillary accommodation listed in paragraph 2.44.
  • GuidanceADB Vol 2, para 2.44Ancillary accommodation, which includes day rooms, should be enclosed by fire resisting construction (minimum REI 30).
  • GuidanceADB Vol 2, para 2.10Alternative escape routes should be in directions 45 degrees or more apart, or, if less than 45 degrees apart, separated from each other by fire resisting construction.Why it applies here: The lounge’s corridor door and its garden door are more than 45 degrees apart from every corner.
  • GuidanceADB Vol 2, Diagram 2.1Travel distance in a dead-end condition: the angle between the two exits as seen from the dead end is at least 45 degrees; the shorter distance to either exit is no more than the maximum for alternative routes; and the distance along the dead end is no more than the maximum where there is no alternative route.
  • GuidanceADB Vol 2, Table 2.1Maximum travel distance for a residential (institutional) building (purpose group 2(a)): 9 m where travel is possible in one direction only, 18 m where it is possible in more than one direction. Note 1: where the layout of partitions and fittings is not known, the direct distance is assumed to be two-thirds of the travel distance.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Lift 1’s protected lobby (ground floor)

  • Means of escape
  • Compartmentation
Show in the 3D model

In a building planned for progressive horizontal evacuation, ADB asks for the entrance to a lift well that is not inside a protected stairway to be separated at every storey by a protected lobby, built to at least REI 30.

  • The doors to a protected lobby approach to a lift shaft are E 30 Sa.
  • The lift well itself is enclosed in at least REI 30 where it could prejudice the way out.

Here Lift 1 is not inside a stair on the ground floor, so ADB asks for a protected lobby at its entrance, built to at least REI 30 with E 30 Sa doors.

  • Lift 1 is an ordinary passenger lift, not an evacuation lift, and the lobby is asked for all the same.

REI 30The protected lobby at Lift 1’s entrance is built to at least REI 30, with E 30 Sa doors.

  • GuidanceADB Vol 2, para 5.37“In buildings designed for phased evacuation or progressive horizontal evacuation, if the lift well is not within the enclosures of a protected stairway, its entrance should be separated at every storey by a protected lobby (minimum REI 30).”Why it applies here: Lift 1’s well is outside a protected stair on this floor, so its entrance has a protected lobby.
  • GuidanceADB Vol 2, Table C1, item 5(c)A door forming part of the enclosure of a protected lobby approach to a lift shaft: E 30 Sa.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Bedroom garden doors

  • Means of escape
Show in the 3D model

A door from a bedroom or day room to a garden can be an exit, and the same rules apply as for any door on an escape route.

  • ADB asks for no lock, latch or bolt, or only simple fastenings that need no key and one action, and for an override from the escape side where a code, card or biometric secures it.
  • An electrically powered lock should return to unlocked if the alarm operates, if power or the system fails and when the override is used.
  • Where residents may wander out unaware of the danger, the 2006 guide accepts security latches only if procedures keep the doors available in an emergency, staff are trained and the emergency plan covers them.

Here every bedroom on the ground floor has a door of its own to the garden, and so does the lounge.

Where residents may walk out unaware of the danger, final exit doors may be secured.

  • Locks on escape doors should open without a key from the escape side, and electric locks should release on the fire alarm, on power loss and from a call point on the escape side (ADB Vol 2 paras 5.7, 5.8).
  • The guide asks for procedures and trained staff so that secured exits are always available in an emergency, set out in the emergency plan (2006 guide pages 29 to 30; Appendix B3, pages 127 to 129).
  • GuidanceADB Vol 2, para 5.7Doors on escape routes should have no lock, latch or bolt, or only simple fastenings that are easy to operate, operable from the escape side without a key and with one mechanism. A secure door operated by code, card or biometric data should have a security mechanism override from the escape side.
  • GuidanceADB Vol 2, para 5.8Electrically powered locks should return to the unlocked position if the fire detection and alarm system operates, on loss of power or system error and when the override is activated, which should be a Type A call point on the escape side.
  • GuidanceFire safety risk assessment: residential care premises, pages 29 to 30Where elderly people may wander out, final exit doors may have security latches if procedures ensure all such doors are always available in an emergency, staff are trained and the emergency plan includes them.
  • GuidanceFire safety risk assessment: residential care premises, pages 127 to 129Doors on escape routes start from the position of having no locking devices, devices that stop unlimited access but open easily in a fire are accepted, and electrical locks should be linked to the alarm with a bypass and a manual override.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Bedrooms (ground floor)

  • Means of escape
  • Compartmentation
Show in the 3D model

ADB asks for each bedroom in a care home to be enclosed in fire-resisting construction (at least REI 30) with fire-resisting doors (at least E 30).

  • ADB asks for every corridor serving bedrooms to be a protected corridor.
  • A bedroom should not hold more than one single or double bed.
  • The wall between a bedroom and a common escape route should have no uninsulated glazing.
  • Linings should meet Table 6.1: class B-s3, d2 on circulation spaces, C-s3, d2 in other rooms, and D-s3, d2 only in rooms of up to 4 m2 in residential accommodation.
  • Where a wall between bedrooms, or on a protected corridor, stops at a suspended ceiling, ADB asks for cavity barriers on the line of the wall or a fire-resisting ceiling (at least EI 30) over the whole area.

Here there are 21 bedrooms on the ground floor, each with its en-suite and a door of its own to the garden.

  • They are enclosed, doored and lined as the bedrooms above are (see Bedrooms and en-suites).

REI 30Each bedroom is enclosed in fire-resisting construction of at least REI 30, with E 30 Sa doors as upstairs.

  • GuidanceADB Vol 2, para 2.42“Each bedroom in a care home should be enclosed in fire resisting construction (minimum REI 30) with fire resisting doors (minimum E 30). Every corridor serving bedrooms should be a protected corridor.”
  • GuidanceADB Vol 2, para 2.43“Bedrooms should not contain more than one single or double bed.”
  • GuidanceADB Vol 2, para 6.1The surface linings of walls and ceilings should meet the classifications in Table 6.1.
  • GuidanceADB Vol 2, para 9.5If the fire resisting construction of a protected escape route is not carried to full storey height, or at the top storey not to the underside of the roof covering, the cavity above or below it should be fitted with cavity barriers on the line of the enclosure or, above, enclosed on its lower side by a fire resisting ceiling (minimum EI 30) that extends throughout the building, compartment or separated part.
  • GuidanceADB Vol 2, para 9.7Where a cavity exists above or below a partition between bedrooms because the enclosure is not carried to full storey height or to the underside of the roof covering, the guidance in paragraph 9.5 should be followed.
  • GuidanceADB Vol 2, Table B1, item 13Enclosure of a protected lobby or protected corridor: REI 30, tested from each side separately.
  • GuidanceADB Vol 2, Table B1, item 15(d)Construction that encloses bedrooms and ancillary accommodation in care homes: REI 30, tested from each side separately.
  • GuidanceADB Vol 2, Table B3, item 6Between residential or sleeping accommodation and a common escape route (corridor, lobby or stair), the permitted area of uninsulated glazed elements is nil.
  • GuidanceADB Vol 2, Table 6.1Classification of linings: small rooms of up to 4 m2 in residential accommodation, D-s3, d2; other rooms, C-s3, d2; other circulation spaces, B-s3, d2.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Doors between protected areas (ground floor)

  • Means of escape
  • Compartmentation
Show in the 3D model

The doors in the walls between protected areas are the doors residents and staff cross in a fire.

  • So ADB counts a door in a compartment wall as a storey exit when the building is planned for progressive horizontal evacuation.
  • ADB Table C1 asks for such a door to match the wall it is in, with the Sa smoke suffix added when it is used for evacuation, so a 60 minute compartment wall takes an E 60 Sa door.
  • Where a closer on a corridor door could be an obstacle to residents, ADB says a hold-open device to BS EN 1155 is appropriate, released by the fire detection and alarm system.
  • Door openings should take up no more than 25 per cent of the length of a compartment wall unless the doors give insulation as well as integrity.
  • BS 9991’s clause for communal facilities recommends corridors used for evacuation at least 1 200 mm wide and door openings at least 850 mm clear, so wheelchairs get through.

Here the ground floor has five protected areas: the service wing and the day rooms and entrance, which hold no beds, and wing west, wing middle and wing east with 10, 8 and 3 beds.

  • Four corridor doorsets, and the dining room’s servery door, are E 60 Sa and held open on the alarm.

REI 60The compartment walls between the ground floor’s protected areas resist fire for 60 minutes, and their doors are E 60 Sa, held open on the alarm.

  • GuidanceADB Vol 2, Table C1, item 2(e)A door in a compartment wall that is not one of the other kinds listed should be the “same as for the wall in which it is fitted, but add Sa(2) if the door is used for progressive horizontal evacuation under the guidance to requirement B1”.
  • GuidanceADB Vol 2, para 2.45(b)If doors fitted with a self-closing device could present an obstacle to residents, hold-open devices in accordance with BS EN 1155 are appropriate on circulation spaces.
  • GuidanceADB Vol 2, para C6(b)If a self-closing device would interfere with the normal approved use of the building, self-closing fire doors may be held open by an automatic release mechanism activated by an automatic fire detection and alarm system.
  • GuidanceADB Vol 2, para C8Fire doorsets often give no significant insulation. Unless they give both integrity and insulation, a maximum of 25% of the length of a compartment wall should consist of door openings. Where a clear space can be kept on both sides of the doorway, the percentage may be greater.
  • GuidanceADB Vol 2, Appendix AStorey exit: “If an institutional building is planned to enable progressive horizontal evacuation, a door in a compartment wall is considered a storey exit for the purposes of requirement B1.”
  • StandardBS 9991, clause 55.3.3 (opens in a new tab)The standard recommends that corridors used for evacuation are at least 1 200 mm wide and that doors have an effective clear opening of at least 850 mm, so wheelchairs can use them. Where double doors are fitted, one of them gives the 850 mm.Why it applies here: BS 9991 has a section for care homes, and ADB’s guidance for them follows the same ideas.
Show in the 3D model

In existing care homes

  • Means of escape
Show in the 3D model

Many care homes were built under older guidance and stay as they are.

  • The 2019 edition of ADB let a home with sprinklers leave self-closing devices off bedroom doors, put more than 10 beds in a protected area and more than one bed in a bedroom.
  • From 2 March 2025 ADB asks for sprinklers throughout every new care home, whatever its height, and those allowances are gone.
  • The 2019 text continues to apply only where the work was notified before that date and was sufficiently progressed, with foundation concrete or piling started, by then or within six months.
  • Older homes were often divided with fire doors across a corridor, not full compartment walls: the 2006 guide says reducing a protected area may be no more than dividing a wing with a set of self-closing fire doors across a corridor, and asks for fire doors near the middle of corridors over 30 m, against 12 m in new design.
  • Two coroners’ reports show what failures look like. Regulation 28 report 2022-0043 raised the lack of a sprinkler requirement. Regulation 28 report 2024-0481 followed a night-time alarm that was reset without adequate checks of residents or fire exits, and raised training for senior staff, clear processes for responding to alarms, and training carers to check residents and fire exits.
  • Fire and rescue services in England carried out 6,004 audits of care homes in 2025/26 (34,077 are known to them), and 39.5 per cent of those audits were unsatisfactory.

This part is about older homes, not this one: it stands at the ruler’s 11 m mark, above this building’s 6.3 m top storey.

  • GuidanceADB Vol 2, para 2.46The 2019 text said that when a sprinkler system is provided in accordance with Appendix E, three variations were acceptable: fire doorsets to bedrooms need not have self-closing devices, protected areas may contain more than 10 beds, and bedrooms may contain more than one bed. If any were made, management procedures should take account of the larger number of residents who may need assistance and the need to close bedroom doors by hand during sleeping hours.
  • GuidanceADB Vol 2, para 2.46“Care homes should be fitted with a sprinkler system throughout the building in accordance with Appendix E.” Taking effect on 2 March 2025, replacing the 2019 text.
  • GuidanceADB Vol 2, IntroductionThe 2025 changes take effect on 2 March 2025. The earlier text continues to apply where a building notice or initial notice was given, or a full plans application made, before that date and the work had started and was sufficiently progressed before it, or does so within six months of it. For a new building, sufficiently progressed means the pouring of foundation concrete, or the placing of piling, has started.
  • GuidanceFire safety risk assessment: residential care premises, page 70If movement times to an adjoining protected area are excessive, the options include reducing the size of the protected area, which may be no more than dividing the wing of a building by positioning a set of fire-resisting self-closing doors across a corridor, more staff, fewer residents in the area, or an appropriately designed sprinkler system.
  • GuidanceFire safety risk assessment: residential care premises, page 85Corridors of more than 30 m are generally subdivided with fire doors as close to the mid point as possible. Where electromagnetic hold-open devices are fitted, the doors should be closed at night.
  • GuidanceRegulation 28 report to prevent future deaths 2022-0043, section 5The coroner’s concerns were that sprinkler systems were not mandatory for care homes whose residents have limited or no independent mobility, and that such homes were not higher-risk buildings unless they were at least 18 metres high or had at least 7 storeys.
  • GuidanceRegulation 28 report to prevent future deaths 2024-0481, sections 4 and 5After a false alarm at night was reset, either no resident checks or inadequate ones were made and some or all fire exits were not checked, and a resident who had got through a door that should have been locked fell down an unheated stairwell leading to an external fire exit, and died. The coroner’s concerns were about training senior staff, clear processes for responding to alarms, and training carers to check residents and fire exits.
  • GuidanceFire statistics data tables, FIRE1202, 2025/26In England in 2025/26 fire and rescue services knew of 34,077 care homes and carried out 6,004 audits of them: 3,634 were satisfactory and 2,370 (39.5 per cent) were not. Services choose which premises to audit by risk, so this is the share of the audits, not of all care homes.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model
  • This is guidance on what an assessor looks at, not an assessment of any real building.
  • Every check is a management check made in use, in a new care home and in an existing one alike.
  • A fire risk assessment is made by a competent person, matched to the risk of the premises (PAS 79-1:2020, clause 7).
  • The 2006 guide for residential care premises was written for existing homes. Where a check cites it, the check is what the guide asks for, not a rule in law: the law’s duties are in the list of ongoing duties.

Ongoing duties once people live here

Fire safety does not stop when the building is finished. These are the duties the law puts on whoever runs this building once people live and work in it: what must be done, by whom, when, and the law it comes from. Some apply only from a certain height; each says where it applies in this building.

  1. Fire risk assessment

    Who
    The responsible person for the care home
    What
    Make a suitable and sufficient assessment of the fire risks to the people in and around the care home, record it with the measures taken or to be taken and any group of people it finds especially at risk, and review it regularly and after any significant change. The law sets no fixed review period: it asks for a review “regularly”, and when there has been a significant change. Appoint one or more competent people to help carry out the preventive and protective measures: a person is competent if they have enough training and experience, or knowledge and other qualities, to do it properly.
    When
    Any workplace to which the Fire Safety Order applies, from the day the care home is occupied: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 9(1), (3), (6) and (7)The responsible person must make a suitable and sufficient risk assessment and review it regularly; as soon as practicable after it is made or reviewed, they must record it, the record including its findings, with the measures taken or to be taken, and any group of persons it identifies as especially at risk.
    • Ongoing dutyFire Safety Order 2005, Article 18(1) and (5)The responsible person must appoint one or more competent people to help them carry out the preventive and protective measures. A person is competent for this if they have enough training and experience or knowledge and other qualities to carry the measures out properly.

    In the model: Protected areas on every floor, Nurse station and evacuation aids

  2. Arrangements, equipment and the emergency services

    Who
    The responsible person for the care home
    What
    Make and give effect to arrangements for planning, organising, controlling, monitoring and reviewing the preventive and protective measures, and record them. Where necessary to keep people safe, provide appropriate fire-fighting equipment and detectors and alarms, with equipment people operate by hand easy to reach, simple to use and signed. Nominate competent people to carry out the fire-fighting measures, with enough training and equipment, and arrange the contacts needed with the emergency services. The fire and rescue authority is the enforcing authority for premises of this kind.
    When
    Any workplace to which the Fire Safety Order applies: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 11The responsible person must make and give effect to arrangements for the effective planning, organisation, control, monitoring and review of the preventive and protective measures, and must record those arrangements.
    • Ongoing dutyFire Safety Order 2005, Article 13(1), (3)(b) and (3)(c)Where necessary to keep people safe, the responsible person must make sure the premises have appropriate fire-fighting equipment, fire detectors and alarms, and that equipment people operate by hand is easy to reach, simple to use and signed. They must nominate competent people to carry out the fire-fighting measures, with enough training and equipment, and arrange the contacts needed with the emergency services.
    • Ongoing dutyFire Safety Order 2005, Article 25(1)(a)For the purposes of the Order, the enforcing authority is the fire and rescue authority for the area in which premises are situated, except for the premises the article gives to others, such as the Health and Safety Executive for a construction site or a ship under construction.

    In the model: Fire alarm panel and staff alarm, Call points, sounders and beacons, Nurse station and evacuation aids

  3. Evacuation procedures and enough competent people

    Who
    The responsible person for the care home
    What
    Nominate a sufficient number of competent people to carry out the procedures for serious and imminent danger, so far as they concern getting people out of the premises.
    When
    Any workplace to which the Fire Safety Order applies: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 15(1)(b)The responsible person must nominate a sufficient number of competent people to carry out the procedures for serious and imminent danger, so far as they concern getting people out of the premises.

    In the model: Nurse station and evacuation aids, Protected areas on every floor

  4. Fire safety training for staff

    Who
    The responsible person for the care home
    What
    Make sure employees are given adequate safety training when they start and when they take on new or increased risks. The training must include suitable instruction on the precautions and actions to take, be repeated periodically where appropriate, be adapted to new or changed risks, suit the risk the assessment finds, and take place during working hours.
    When
    Any workplace to which the Fire Safety Order applies: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 21(1) and (2)The responsible person must make sure their employees are given adequate safety training when they start and when they take on new or increased risks. The training must include suitable instruction on the precautions and actions to take, be repeated periodically where appropriate, be adapted to new or changed risks, suit the risk the assessment finds, and take place during working hours.

    In the model: Nurse station and evacuation aids, Protected areas on every floor

  5. Maintaining the doors, alarm, sprinklers and lighting

    Who
    The responsible person for the care home
    What
    Where necessary to safeguard people in and around the care home, make sure the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and kept in efficient working order and in good repair. That takes in the hold-open and free-swing devices on the doors, the fire alarm, the sprinklers and the emergency lighting.
    When
    Any workplace to which the Fire Safety Order applies: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)Where necessary to safeguard the people in and around the premises, the responsible person must ensure that the premises, and the facilities, equipment and devices provided for their safety, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.

    In the model: Doors between protected areas (first and second floors), Bedroom doors (free-swing closers), Corridor doors (dividing the corridor), Fire detection (Category L1), Sprinklers (category 3), Emergency lighting

  6. Facilities for firefighters

    Who
    The responsible person for the care home
    What
    Where necessary to safeguard firefighters in a fire, make sure the facilities, equipment and devices provided for their use or protection are subject to a suitable system of maintenance and kept in efficient working order and in good repair. At this care home they are the fire appliance hardstanding, the private hydrant and the sprinkler inlet.
    When
    Any workplace to which the Fire Safety Order applies: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 38(1)Where necessary to safeguard firefighters in a fire, the responsible person must ensure that the facilities, equipment and devices provided for their use or protection are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.

    In the model: Fire appliance access, Private fire hydrant, Fire and rescue service sprinkler inlet

  7. Keeping the escape routes clear

    Who
    The responsible person for the care home
    What
    Where necessary, keep the routes to emergency exits, and the exits themselves, clear at all times. In a care home that includes the corridors that hold residents moved into a protected area, the stairs and the refuges.
    When
    Any workplace to which the Fire Safety Order applies: a care home at any height.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.

    In the model: Protected areas on every floor, Protected stairs, Refuges with emergency voice communication, Main entrance and final exits

  8. Fire safety information at handover

    Who
    The person carrying out the building work, to the responsible person for the care home
    What
    When building work erects a care home, give the responsible person fire safety information about its design and construction and its services, fittings and equipment, that will help them operate and maintain it with reasonable safety, no later than completion or occupation. ADB asks for the information for a care home to include the assessment of how many beds each protected area holds, with the expected number of staff and the help residents need (Vol 2 para 19.5(d)).
    When
    Building work that erects a building to which the Fire Safety Order will apply.
    In this building
    Applies here at every height.
    • LawBuilding Regulations 2010, Regulation 38(1) to (3)Where building work erects or extends a building to which the Fire Safety Order will apply, or goes with a change of use that brings the Order to it, and Part B applies to the work, the person carrying out the work must give the responsible person fire safety information, about the design and construction of the building and its services, fittings and equipment, that will help them operate and maintain it with reasonable safety, no later than completion or occupation; the responsible person acknowledges receiving it.

    In the model: Protected areas on every floor, Nurse station and evacuation aids

  9. Safe care and safe premises: the Health and Social Care regulations

    Who
    The registered provider
    What
    Provide care in a safe way, which includes assessing and reducing the risks to the people in the provider’s care and making sure the premises are safe for their intended purpose and used in a safe way. Keep the premises and equipment clean, secure, suitable, properly used and maintained. Run systems that assess, monitor and reduce the risks to residents’ health, safety and welfare, and keep the records needed. Deploy enough suitably qualified, competent, skilled and experienced people, with the support, training and supervision they need.
    When
    While the care service is registered under the Health and Social Care Act 2008.
    In this building
    Applies here at every height.
    • Ongoing dutyThe Health and Social Care Act 2008 (Regulated Activities) Regulations 2014, Regulations 12 and 15A registered care provider must provide care in a safe way, which includes assessing and reducing the risks to the people in its care and making sure its premises are safe for their intended purpose and used in a safe way (regulation 12). Its premises and equipment must be clean, secure, suitable for their purpose, properly used and maintained and appropriately located (regulation 15).
    • Ongoing dutyThe Health and Social Care Act 2008 (Regulated Activities) Regulations 2014, Regulation 17(1), (2)(b) and (d)A registered care provider must run systems that assess, monitor and reduce the risks to the health, safety and welfare of the people in its care, and must keep the records needed about its staff and the running of the service.
    • Ongoing dutyThe Health and Social Care Act 2008 (Regulated Activities) Regulations 2014, Regulation 18(1) and (2)(a)A registered care provider must deploy enough suitably qualified, competent, skilled and experienced people, and its staff must receive the support, training and supervision they need to do their jobs.

    In the model: Nurse station and evacuation aids, Bedrooms and en-suites, Protected areas on every floor

Guides behind this model

Read more on the topics this building shows.

See all 8 guides linked from this model

What this model assumes

  • Illustrative, not a real address: the layout follows a consented scheme, and the fire design is INFIRISK’s, to Approved Document B Volume 2, which the scheme did not carry.
  • The model’s north is the plan’s: the building’s real rotation from true north is not drawn.
  • Night staffing of seven waking staff is an INFIRISK teaching assumption.
  • The site is designed, not surveyed, and drawn level: the real ground falls about 3.2 m over the 30 m west of the building.
  • Stair geometry to Approved Document K.
  • The size of the lifts is not known, so the text about them claims none. The real scheme’s drawings show two lifts with no evacuation lift designation, no lift lobbies and no smoke shafts, so the lift design, Lift 2 the evacuation lift and Lift 1 an ordinary passenger lift, is INFIRISK’s.
  • Where neither a part’s own text nor the guidance it cites settles a fire resistance period, the model assumes one from Approved Document B Volume 2, taking the more onerous value where the guidance leaves the choice to the fire risk assessment: the two lift wells and the smoke shaft are taken as protected shafts of 60 minutes, with E 30 lift landing doors. Each such value is marked as assumed where it is shown.

Approved Document B Volume 2 is the 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments, read on 15 and 16 November 2026. BS 9991:2024, BS 9251:2021, BS 5839-1:2025 and BS 5266-1:2025 are the current editions, paraphrased (ADB names the 2017 edition of BS 5839-1 and the 2016 edition of BS 5266-1). BS 7273-4:2015+A2:2023, BS 8214:2026, BS 5306-8:2023, BS 7177:2008+A1:2011 and PAS 79-1:2020 are paraphrased too. The 2006 guide for residential care premises and the NFCC guidance of 18 November 2021 are cited by page or section, and legislation is as revised on legislation.gov.uk.

Technical review by INFIRISK editorial: 16 November 2026 · Next review: 16 February 2027