INFIRISK 3D buildings · Existing house converted into flats

Converted flats

A Victorian house in a terrace, converted into four flats long ago and judged as it is lived in today. Step through every floor, from the common hall and its timber stair to the loft, see what a fire risk assessor checks, and what a conversion done today would need instead.

See the same house let as a shared house

This building is illustrative. It is drawn to show how the guidance fits together, and it is not a fire strategy or a design for any real building. For your own building, speak to a competent fire engineer or fire risk assessor.

Every part of the building

The roof

Roof over the party walls

  • Compartmentation
  • External wall
Show in the 3D model

Where a party wall meets a pitched roof, it is built up to the underside of the slates and fire-stopped there, and carried across the eaves, so fire cannot pass over the top of it through the roof space.

  • The roof covering either side is chosen so fire does not spread across it from one house to the next.
  • BS 9792 notes that in old blocks of flats the walls between flats may not go up through the roof void, and the government’s 2026 hazard rating guidance expects fire separation in the roof space between terraced houses too.
  • So an assessor tries to look into the roof void, and records it when that is not practicable.

60 minutesAssumed: where the party wall is carried up to the roof it takes the 60 minutes of the party wall below, which LACORS’s 2008 guidance for existing housing lists for walls separating buildings; the roof’s own text says the wall is fire-stopped there and gives no period.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
  • GuidanceADB Vol 1, paras 7.15 and 7.16In a block of flats the junction of a compartment wall with the roof follows the provisions for houses (paras 5.11 and 5.12). In residential buildings no more than 15 m high, a combustible substrate and timber battens fully bedded in mortar over the width of the wall may extend over it.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary (opens in a new tab)Fire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.Why it applies here: The party walls run up through the pitched roof void.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Reasonable fire separation is expected within any roof space, for example between terraced houses, and the lines of compartmentation between top-floor flats in buildings with a stay put policy should extend through the roof void in a continuous vertical plane to the underside of the roof.Why it applies here: The party walls run up through the pitched roof void.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The party wall through the roof void: continuous to the underside of the roof, fire-stopped, and the void reachable

    Benchmark: For new work: the wall continued to the underside of the roof covering, fire-stopped, and across the eaves.

    • GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentaryFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Reasonable fire separation is expected within any roof space, for example between terraced houses, and the lines of compartmentation between top-floor flats in buildings with a stay put policy should extend through the roof void in a continuous vertical plane to the underside of the roof.

    A defect the source namesFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire; access is recorded when it was not practicable.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentaryFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.
Show in the 3D model

The first floor, second floor and loft

Common stair and landings

  • Means of escape
  • Compartmentation
Show in the 3D model

For a house converted into flats to a standard below the 1991 Building Regulations, LACORS’s 2008 guidance for existing housing asks for a 30-minute protected route.

  • The route is the hall, the stair and the landings enclosed in 30-minute fire-resisting construction, with FD30S self-closing doors to the flats.
  • Existing partitions of adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes, though the exact construction of an existing partition is difficult to tell without opening it up.
  • 9 mm board or original lath and plaster in sound condition may be accepted only within the fire risk assessment, which in a building like this is likely to call for something to make up for it, such as better detection.
  • Everyone leaves when the alarm sounds: for these houses the guidance’s approach is early warning to every flat and total evacuation, while blocks built or converted to the 1991 standard may adopt stay put.
  • BS 9792 treats it as a matter for each building: it expects a fire alarm in the common parts of converted houses whose construction cannot support stay put.

It is guidance for existing housing, used by the council under the Housing Act 2004; the Fire Safety Order reaches the same common parts and flat entrance doors.

Here it is the house’s original timber stair, against the party wall, rising from the hall to a landing at the front of each floor; it ends at the second floor landing.

  • If fewer than two thirds of the flats are owner-occupied, as the model takes it, the house is also a house in multiple occupation under section 257 of the Housing Act 2004.
  • As a whole it does not need a mandatory HMO licence, but a council can include such buildings in an additional licensing scheme.
  • Its manager must keep the means of escape clear and in good repair, keep the fire alarm in good working order, display notices showing the way out and have the wiring tested at least every five years.

30 minutesLACORS’s 2008 guidance for existing housing asks for a 30-minute protected route: the hall, the stair and the landings in 30-minute fire-resisting construction.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, section 37 and para 2.3Houses or buildings converted into self-contained flats where the conversion did not, and does not, meet the building standards of the Building Regulations 1991. Buildings converted to that standard and still meeting it are not included: they will not need additional fire safety measures unless occupied in a way other than intended, or a new risk has been introduced since.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and para 21.5For a three- or four-storey building converted into self-contained flats to a standard below the 1991 Building Regulations: a 30-minute protected route, FD30S flat entrance doors with self-closers, and no fire doors needed inside the flats, though their doors should be sound and close fitting.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.5 and 19.6Existing partitions of adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes. Lesser constructions such as 9 mm plasterboard or original lath and plaster, in sound condition and good repair, may be accepted in lower-risk premises, which it describes as shared houses of no more than two storeys; in higher-risk premises only within the overall fire risk assessment, which is likely to call for compensating measures such as enhanced detection, a domestic water suppression system or a second way out.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 7.6For the properties this guidance covers, the approach is to give early warning of a fire to all occupiers and make sure they can evacuate the building to a place of permanent safety (total evacuation). Blocks of flats constructed or converted in compliance with the Building Regulations 1991 may adopt a different approach, such as stay put, because their compartmentation makes spread beyond the flat where a fire starts unlikely.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.2, commentary (opens in a new tab)Whether to stay put is a matter for each building; a fire alarm is expected in the common parts of converted houses whose construction cannot support stay put.Why it applies here: The converted house is an older conversion whose construction is not taken to support stay put.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 3.2 and 33.2The case studies must not be used as off-the-peg solutions, and there is no obligation to adopt their exact solutions: each building is judged on its own risk assessment.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.
  • Ongoing dutyFire Safety Order 2005, Article 6(1A)Where a building contains two or more sets of domestic premises, the Order applies to the building’s structure and external walls and any common parts, and to all doors between the domestic premises and the common parts.
  • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Sections 254(1)(e) and 257(1) to (5)A converted block of flats, a building converted into and consisting of self-contained flats, is a house in multiple occupation where the building work done for the conversion did not comply with the appropriate building standards and still does not, and less than two thirds of the flats are owner-occupied. For a conversion completed before 1 June 1992 the standards are those of the Building Regulations 1991; a flat is owner-occupied if lived in by someone with a lease of more than 21 years or the freehold, or their household.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Appendix 1, note on converted blocks (section 257)Certain converted blocks of flats fall within the HMO definition: those converted to a standard that does not comply with the Building Regulations 1991, and still does not, where less than two thirds of the flats are owner-occupied. They are not subject to mandatory licensing, but may fall within a council’s additional licensing scheme.

What a fire risk assessor checks

  1. The route’s enclosure: the walls and ceilings of the hall, stair and landings, and anything passing through them

    Benchmark: LACORS (2008), for a conversion below the 1991 Building Regulations standard: a 30-minute protected route, enclosed at all points, with gaps round pipes, cables and ducts fire stopped; adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes; 9 mm board or original lath and plaster only within the risk assessment.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and para 21.5For a three- or four-storey building converted into self-contained flats to a standard below the 1991 Building Regulations: a 30-minute protected route, FD30S flat entrance doors with self-closers, and no fire doors needed inside the flats, though their doors should be sound and close fitting.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.5 and 19.6Existing partitions of adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes. Lesser constructions such as 9 mm plasterboard or original lath and plaster, in sound condition and good repair, may be accepted in lower-risk premises, which it describes as shared houses of no more than two storeys; in higher-risk premises only within the overall fire risk assessment, which is likely to call for compensating measures such as enhanced detection, a domestic water suppression system or a second way out.

    A defect the source namesCeilings not in sound condition, particularly lath and plaster ones, cannot be relied on for 30 minutes and should be replaced or upgraded.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.4Ceilings not in sound condition, particularly lath and plaster ones, should be replaced or upgraded to give 30 minutes of fire resistance.
  2. What is kept on the route: heaters, cooking, furniture, storage, post, bicycles and anything else that would burn or block it

    Benchmark: LACORS (2008): the route kept free of obstructions and fire risks, with no portable heaters, cooking, furniture or storage on the stair. The Fire Safety Order: the responsible person keeps the routes to the exits, and the exits, clear.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 15.3 and 15.4The protected route is kept free of obstructions and fire risks: the stairway holds no portable or bottled-gas heaters, no cooking facilities, and no furniture or storage. Storage cupboards are not located in protected routes unless they are fire resisting, kept locked shut and have smoke detection inside as appropriate (single households and shared houses of up to two storeys excepted).
    • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.

    A defect the source namesFree storage, trailing leads and worn carpets on the route, and fire doors kept from closing onto their latches, for instance by a catching carpet.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 32.4Escape routes are kept free from obstruction at all times, with no free storage on them and no trip hazards such as trailing leads or worn carpets; fire doors close themselves onto their latches with nothing such as a catching carpet in the way, and a flat’s entrance door always needs its closer.
Show in the 3D model

Flat entrance doors

  • Compartmentation
  • Means of escape
Show in the 3D model

Each flat’s front door opens off the hall or a landing, and stands between that flat and everyone else’s way out.

  • In a conversion of this kind LACORS’s 2008 guidance for existing housing asks for an FD30S fire door with a self-closer to every flat, and does not require fire doors inside the flats, though their doors should be sound and close fitting.
  • It asks for the route to be enclosed at all points by 30-minute construction, which takes in any glazed light over or beside a flat’s door, like the one over the raised ground floor flat’s door here.
  • Older doors may have no intumescent strips or smoke seals, though a door that met the requirements when it was fitted may still be adequate.
  • Here the flats’ doors open straight onto the hall or the stair, with no lobby between, which the 2026 hazard rating guidance says is likely to be more critical than a door onto a protected lobby.
  • The responsible person must tell residents to keep fire doors shut, not to tamper with the closers and to report faults.

The top storey, the loft, is more than 11 m up, so the responsible person must also:

  • use best endeavours to check these doors at least once a year
  • check the fire doors in the common parts at least every three months

That duty applies to existing buildings too.

FD30SLACORS’s 2008 guidance for existing housing asks for an FD30S fire door with a self-closer to every flat.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and para 21.5For a three- or four-storey building converted into self-contained flats to a standard below the 1991 Building Regulations: a 30-minute protected route, FD30S flat entrance doors with self-closers, and no fire doors needed inside the flats, though their doors should be sound and close fitting.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.1Where fire-resisting partitions are needed, any doorway in them has a fire-resisting door assembly at least to the partition’s standard: FD30 in a 30-minute partition, an S after the figure meaning smoke seals.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3 (opens in a new tab)Older flat entrance doors might have no intumescent strips, and so might not achieve 30 minutes of fire resistance, or no smoke seals; a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.Why it applies here: The flat entrance doors are part of the common parts’ protection.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.35Original flat entrance doors may lack intumescent strips and smoke seals but may be acceptable, depending on the building and where the door is: one that opens directly onto a staircase enclosure is likely to be more critical than one that opens onto a protected lobby leading to the stair.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.33Depending on design and the height of the highest floor, fire protection to escape routes within individual dwellings may be required, generally above 4.5 m except in very small flats; in multi-occupied buildings fire protection to escape routes is generally required, and the fire-resisting construction protecting them includes any glazing.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(1) to (3)The responsible person must give residents information that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported.

What a fire risk assessor checks

  1. Flat entrance doors: rating, self-closer, intumescent strips and smoke seals, fit and gaps, and damage, on at least a sample

    Benchmark: LACORS (2008), for a conversion below the 1991 Building Regulations standard: an FD30S door with a self-closer to every flat. A door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and para 21.5For a three- or four-storey building converted into self-contained flats to a standard below the 1991 Building Regulations: a 30-minute protected route, FD30S flat entrance doors with self-closers, and no fire doors needed inside the flats, though their doors should be sound and close fitting.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3Older flat entrance doors might have no intumescent strips, and so might not achieve 30 minutes of fire resistance, or no smoke seals; a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 5An assessment of housing is one of four types. Type 1 covers the common parts without opening up, and is generally enough where there is evidence of the building’s integrity; it includes at least a sample of flat entrance doors. Type 3 also looks inside a sample of the dwellings.

    A defect the source namesOlder doors may have no intumescent strips, and so may not resist fire for 30 minutes, or no smoke seals. Even in lower-risk premises LACORS’s 2008 guidance for existing housing does not accept non-fire-resisting glazed doors, flimsy doors or hollow infill (egg-box) doors.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.3Older flat entrance doors might have no intumescent strips, and so might not achieve 30 minutes of fire resistance, or no smoke seals; a door that met the requirements when it was fitted may still be adequate, and is not replaced without weighing the risk.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.6In lower risk premises, existing well fitted and well made solid doors may be acceptable; non-fire-resisting glazed doors, flimsy doors and hollow infill doors (known as egg-box doors) are not.
  2. Glazing over or beside a flat entrance door: a fanlight or side light

    Benchmark: LACORS (2008): the protected route enclosed at all points by construction of at least 30 minutes, which takes in any glazing in the walls round it, and doorways in fire-resisting walls fitted with fire-resisting doorsets.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.1Where fire-resisting partitions are needed, any doorway in them has a fire-resisting door assembly at least to the partition’s standard: FD30 in a 30-minute partition, an S after the figure meaning smoke seals.

    A defect the source namesGlazing in or round a fire door that is not fire resisting. Georgian wired glass is the commonest fire-resisting glass, and non-wired fire-resisting glass is always marked in a corner with its maker’s name and fire performance, so unmarked plain glass can be taken not to be fire resisting and needs replacing or protecting with fire-resisting glass. The glazing is part of the enclosure round the route, which as a whole is to give 30 minutes.

    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Appendix B, p.59Check that any glazing within, or surrounding, a fire door is fire resisting. The commonest fire-resisting glazing is Georgian wired glass; non-wired fire-resisting glass is always marked in a corner with the maker’s name and its fire performance, and unmarked non-wired glass can be assumed not to be fire resisting and needs replacing or protecting with fire-resisting glass.
  3. Fire door information for residents, and the door checks the height brings

    Benchmark: Residents told to keep fire doors shut, not to tamper with the closers and to report faults. With the top storey more than 11 m up, the fire doors in the common parts checked at least every 3 months, and the flat entrance doors, with best endeavours, at least every 12 months.

    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(1) to (3)The responsible person must give residents information that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.
Show in the 3D model

Emergency lighting

  • Means of escape
Show in the 3D model

Lights in the hall and on the landings that come on by themselves if the power to the ordinary lighting fails.

  • For a house of three or four storeys converted into flats, LACORS’s 2008 guidance for existing housing asks for ordinary artificial lighting on the route, and emergency escape lighting where the route is long or complex or has no effective borrowed light.
  • The stair here has no window of its own, so it is drawn.
  • The government’s 2026 hazard rating guidance expects emergency escape lighting in the common escape routes of most buildings of flats anyway.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11Conventional artificial lighting is required on the escape route; emergency escape lighting is required if the route is long or complex or where there is no effective borrowed light.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Emergency escape lighting should be provided in all common escape routes in most flats.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Escape lighting in the hall and on the landings: there, covering the route, and tested

    Benchmark: LACORS (2008), for a house of three or four storeys converted into flats: ordinary lighting on the route, and emergency escape lighting where the route is long or complex or has no effective borrowed light. An annual full discharge test by a competent person, recorded (LACORS 32.8). The 2026 hazard rating guidance expects emergency escape lighting in the common escape routes of most flats.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11Conventional artificial lighting is required on the escape route; emergency escape lighting is required if the route is long or complex or where there is no effective borrowed light.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 32.5 and 32.8A Grade A fire alarm is tested weekly at a detector or call point, serviced every six months by a competent person and kept with a log book; emergency escape lighting has an annual discharge test.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Emergency escape lighting should be provided in all common escape routes in most flats.
Show in the 3D model

Inside the flats

  • Means of escape
Show in the 3D model

Inside each flat the partitions and doors are ordinary ones.

  • LACORS’s 2008 guidance for existing housing, in its case study of a conversion of this kind, does not require fire doors within the flats, though its figure says ideally, and asks for sound, well made, close-fitting doors.
  • The government’s 2026 hazard rating guidance says the escape route inside a flat is generally protected where a floor is more than 4.5 m up, except in very small flats, so an assessor who gets into the flats looks at this too.
  • Each flat’s hall leads from its front door to its rooms, and every habitable room opens off it.

Measured inside their walls:

  • the raised ground floor flat has 52.1 m2, its living room in the bay and its bedroom in the outrigger
  • the first floor flat has 56.3 m2, its bedroom across the front of the house
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and para 21.5For a three- or four-storey building converted into self-contained flats to a standard below the 1991 Building Regulations: a 30-minute protected route, FD30S flat entrance doors with self-closers, and no fire doors needed inside the flats, though their doors should be sound and close fitting.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.33Depending on design and the height of the highest floor, fire protection to escape routes within individual dwellings may be required, generally above 4.5 m except in very small flats; in multi-occupied buildings fire protection to escape routes is generally required, and the fire-resisting construction protecting them includes any glazing.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Top flat’s own stair

  • Means of escape
Show in the 3D model

The common stair ends at the second floor landing.

  • The top flat’s front door is there, and behind it the flat has its own stair up to its loft rooms: the only way out of the loft is down that stair and out through that door, so a fire on the stair or the second floor could cut it off.
  • The model draws the stair with ordinary walls and doors, like the rest of the flat.
  • LACORS’s 2008 guidance for existing housing, in its case study, does not require fire doors within flats and relies on the flat’s own alarms to wake the people sleeping in it; but it also asks for a long route inside a flat to be considered, which may call for the route to be protected, an alternative exit, or extra measures such as better detection or water suppression (para 9.14).
  • The 2026 hazard rating guidance says the route inside a flat with a floor more than 4.5 m up is generally protected.

Which of these this flat needs is for an assessment that looks inside the flat. Here the top flat has smoke alarms in every room and circulation space, with a heat alarm in its kitchen.

The top flat has 90.0 m2:

  • 56.3 m2 on the second floor
  • 33.7 m2 in the loft, counted where the headroom is 1.5 m or more
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and para 21.5For a three- or four-storey building converted into self-contained flats to a standard below the 1991 Building Regulations: a 30-minute protected route, FD30S flat entrance doors with self-closers, and no fire doors needed inside the flats, though their doors should be sound and close fitting.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and figure D11A mixed system: Grade A, LD2 coverage in the common areas and a heat alarm in each flat in the room or lobby opening onto the escape route, interlinked; and Grade D, LD3 coverage in each flat, a smoke alarm in that room or lobby, not interlinked, to protect the sleeping occupants. The figure shows the fire alarm control panel inside the front door.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 9.14A long internal hallway inside a flat may need protecting, or enhanced detection.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.33Depending on design and the height of the highest floor, fire protection to escape routes within individual dwellings may be required, generally above 4.5 m except in very small flats; in multi-occupied buildings fire protection to escape routes is generally required, and the fire-resisting construction protecting them includes any glazing.
Show in the 3D model

Loft rooms

  • Means of escape
Show in the 3D model

A loft converted into rooms is a storey: its floor is the top storey’s floor, which is what the 11 m line in Approved Document B and the fire door checks in the law are measured to, from the lowest ground beside the building.

Here the loft floor is taken as 11.5 m above the garden, the lowest ground beside the house, and the front lightwell is at the same level.

  • That puts the converted house over the 11 m line; the same house let as a shared house, with no loft, has its top storey at 8.7 m.
  • Under the slope the ceiling is taken 0.15 m inside the roof; behind the low wall at the front, the eaves are storage.
  • GuidanceADB Vol 1, Appendix A and Diagrams D4 and D6The height of a building is measured as Diagram D4 shows, from the mean ground level to the mean roof level. The height of the top storey is measured as Diagram D6 shows, from ground level on the lowest side of the building to the upper surface of the top floor. They are different heights: a block whose top storey is under 11 m can be more than 11 m high.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.
Show in the 3D model

Alarms in the flats

  • Detection and alarm
Show in the 3D model

Each flat has its own mains-powered alarms with a backup supply, separate from the common parts’ system: smoke alarms in its hall and living room, and a heat alarm in its kitchen.

  • Kept separate, they wake the people in that flat without one flat’s false alarm sending the whole house out.
  • LACORS’s 2008 guidance for existing housing asks at least for a smoke alarm in the hall or room by each flat’s door (Grade D, LD3).
  • BS 5839-6 Table 1 recommends Grade D1, Category LD2 in each flat of the older converted houses it treats as HMOs, which is what is drawn.
  • The immediate landlord of a rented flat must make sure there is a smoke alarm on each storey with living accommodation, working on the day each new tenancy begins, unless the house must be licensed as an HMO, when the licence’s conditions apply instead.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and figure D11A mixed system: Grade A, LD2 coverage in the common areas and a heat alarm in each flat in the room or lobby opening onto the escape route, interlinked; and Grade D, LD3 coverage in each flat, a smoke alarm in that room or lobby, not interlinked, to protect the sleeping occupants. The figure shows the fire alarm control panel inside the front door.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 22.10Where more than one alarm system serves a building, it is a mixed system: the systems meet different life safety objectives and may be of different grades, having regard to the need to avoid a false alarm in one dwelling unit affecting all the occupiers.
  • StandardBS 5839-6, Table 1, the HMO rows and note L (opens in a new tab)In England and Wales certain houses converted into blocks of flats before the Building Regulations 1991 came into force are treated as HMOs under the Housing Act 2004 (note L). For HMOs other than shared houses and those of one or two storeys with no floor over 200 m2, Table 1 recommends Grade A, Category LD2 in the communal areas, with detectors sited as BS 5839-1 sites them for a Category L2 system, and Grade D1, Category LD2 in each dwelling unit of two or more rooms, in new and existing premises alike.Why it applies here: The converted house is an older conversion of four storeys above its lower ground floor, of the kind note L describes.
  • LawSmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)The immediate landlord of a home in England let on a tenancy the regulations cover must ensure that, while it is occupied under that tenancy, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker; that each alarm is checked and in proper working order on the day a new tenancy begins; and that, when a tenant reports an alarm, it is checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Alarms in the flats, where access is given: there, mains powered, working, and checked at each new tenancy

    Benchmark: BS 5839-6 Table 1: Grade D1, Category LD2 in each flat of two or more rooms in an HMO, and Grade D1, Category LD1 in a maisonette with a floor more than 4.5 m up and no alternative means of escape, as the top flat is; LACORS (2008) asks at least for a smoke alarm in each flat’s hall (Grade D, LD3). In a rented flat, a smoke alarm on each storey with living accommodation, working on the day each tenancy begins.

    • StandardBS 5839-6, Table 1, the HMO rows and note LIn England and Wales certain houses converted into blocks of flats before the Building Regulations 1991 came into force are treated as HMOs under the Housing Act 2004 (note L). For HMOs other than shared houses and those of one or two storeys with no floor over 200 m2, Table 1 recommends Grade A, Category LD2 in the communal areas, with detectors sited as BS 5839-1 sites them for a Category L2 system, and Grade D1, Category LD2 in each dwelling unit of two or more rooms, in new and existing premises alike.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and figure D11A mixed system: Grade A, LD2 coverage in the common areas and a heat alarm in each flat in the room or lobby opening onto the escape route, interlinked; and Grade D, LD3 coverage in each flat, a smoke alarm in that room or lobby, not interlinked, to protect the sleeping occupants. The figure shows the fire alarm control panel inside the front door.
    • LawSmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)The immediate landlord of a home in England let on a tenancy the regulations cover must ensure that, while it is occupied under that tenancy, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker; that each alarm is checked and in proper working order on the day a new tenancy begins; and that, when a tenant reports an alarm, it is checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.
Show in the 3D model

Alarms in the top flat

  • Detection and alarm
Show in the 3D model

The top flat is on two storeys, its loft 11.5 m above the garden, with no way out but its own stair.

  • It has smoke alarms in every room and circulation space (its halls, its stair, the loft passage and each room where a fire might start), with a heat alarm in its kitchen.
  • BS 5839-6 Table 1’s row for flats of two or more rooms in an HMO recommends at least Grade D1, Category LD2.
  • Its row for any maisonette with a floor more than 4.5 m up and no alternative means of escape recommends Grade D1, Category LD1, which is what is drawn here.
  • A heat detector with a sounder just inside its front door is linked to the common parts’ alarm, as on the floors below.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and figure D11A mixed system: Grade A, LD2 coverage in the common areas and a heat alarm in each flat in the room or lobby opening onto the escape route, interlinked; and Grade D, LD3 coverage in each flat, a smoke alarm in that room or lobby, not interlinked, to protect the sleeping occupants. The figure shows the fire alarm control panel inside the front door.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 22.10Where more than one alarm system serves a building, it is a mixed system: the systems meet different life safety objectives and may be of different grades, having regard to the need to avoid a false alarm in one dwelling unit affecting all the occupiers.
  • StandardBS 5839-6, Table 1, the HMO rows and note L (opens in a new tab)In England and Wales certain houses converted into blocks of flats before the Building Regulations 1991 came into force are treated as HMOs under the Housing Act 2004 (note L). For HMOs other than shared houses and those of one or two storeys with no floor over 200 m2, Table 1 recommends Grade A, Category LD2 in the communal areas, with detectors sited as BS 5839-1 sites them for a Category L2 system, and Grade D1, Category LD2 in each dwelling unit of two or more rooms, in new and existing premises alike.Why it applies here: The converted house is an older conversion of four storeys above its lower ground floor, of the kind note L describes.
  • LawSmoke and Carbon Monoxide Alarm Regulations 2015, Regulation 4(1) and (3A)The immediate landlord of a home in England let on a tenancy the regulations cover must ensure that, while it is occupied under that tenancy, a smoke alarm is equipped on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker; that each alarm is checked and in proper working order on the day a new tenancy begins; and that, when a tenant reports an alarm, it is checked as soon as reasonably practicable and, if it is not in proper working order, repaired or replaced as soon as reasonably practicable.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.
  • StandardBS 5839-6, clause 9.2 a) and Table 1, note D (opens in a new tab)For a rented flat whose occupants are not known, Table 1 recommends Grade D1, Category LD2: mains alarms with a tamper-proof standby supply, in the circulation spaces, the principal habitable room and (heat only) the kitchen. A maisonette with a floor more than 4.5 m up and no alternative means of escape is in the Grade D1, Category LD1 row.Why it applies here: The top flat is let, on two storeys, its loft more than 4.5 m up, with no way out but its own stair.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Floors between the flats

  • Compartmentation
Show in the 3D model

The floors between the flats are the house’s original timber floors, with ceilings under them.

  • LACORS’s 2008 guidance for existing housing asks for 30 minutes of fire resistance between units of accommodation.
  • For this kind of conversion 30 minutes between flats throughout is the ideal, but on risk assessment sound, traditional construction may be accepted where extra detection makes up for it.
  • Lath and plaster ceilings in sound condition give less, and ceilings that are not sound, especially lath and plaster ones, should be replaced or upgraded to give 30 minutes.

30 minutesLACORS’s 2008 guidance for existing housing asks for 30 minutes of fire resistance between units of accommodation.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.1Floors and ceilings between units of accommodation should generally give 30 minutes of fire resistance. Between a basement or cellar and the ground floor escape route they should give 60 minutes, which may be reduced to 30 minutes where the basement has automatic fire detection to the guidance’s standard.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11, fire separation30 minutes of fire resistance between flats throughout is the ideal, but on risk assessment there may be no need for more fire-resisting separation between the flats, provided the walls and floors are of sound, traditional construction and additional compensatory detection is fitted.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.3Ceilings of 9 mm plasterboard or lath and plaster in sound condition give a lower standard of fire resistance: acceptable within the fire risk assessment in single households and shared houses of no more than three storeys, and in premises of higher risk only with compensating measures such as enhanced detection.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.4Ceilings not in sound condition, particularly lath and plaster ones, should be replaced or upgraded to give 30 minutes of fire resistance.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Floors and ceilings between the flats: their construction and condition, and any breaches for pipes and cables

    Benchmark: LACORS (2008): 30 minutes between units of accommodation; for this kind of conversion 30 minutes between flats is the ideal, and sound, traditional construction may be accepted with compensating detection.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.1Floors and ceilings between units of accommodation should generally give 30 minutes of fire resistance. Between a basement or cellar and the ground floor escape route they should give 60 minutes, which may be reduced to 30 minutes where the basement has automatic fire detection to the guidance’s standard.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11, fire separation30 minutes of fire resistance between flats throughout is the ideal, but on risk assessment there may be no need for more fire-resisting separation between the flats, provided the walls and floors are of sound, traditional construction and additional compensatory detection is fitted.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.

    A defect the source namesCeilings not in sound condition, particularly lath and plaster ones, cannot be relied on for 30 minutes and should be replaced or upgraded.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.4Ceilings not in sound condition, particularly lath and plaster ones, should be replaced or upgraded to give 30 minutes of fire resistance.
Show in the 3D model

Walls round the common parts

  • Compartmentation
Show in the 3D model

The walls between the hall, stair and landings and the flats are part of the protected route.

  • LACORS’s 2008 guidance for existing housing asks for the route to be enclosed at all points by construction of at least 30 minutes, with any gap round pipes, cables or ducts passing through it fire stopped.
  • Existing partitions of adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes, though the exact construction of an existing partition is difficult to tell without opening it up, and where its soundness is in doubt replacing it may be appropriate.
  • 9 mm board or original lath and plaster in sound condition may be accepted in lower-risk premises such as a shared house of two storeys, and in a building like this one only within the fire risk assessment, with compensating measures.

30 minutesLACORS’s 2008 guidance for existing housing asks for the route to be enclosed at all points by construction of at least 30 minutes.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.5 and 19.6Existing partitions of adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes. Lesser constructions such as 9 mm plasterboard or original lath and plaster, in sound condition and good repair, may be accepted in lower-risk premises, which it describes as shared houses of no more than two storeys; in higher-risk premises only within the overall fire risk assessment, which is likely to call for compensating measures such as enhanced detection, a domestic water suppression system or a second way out.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The walls round the hall, stair and landings: their construction, and gaps round pipes and cables

    Benchmark: LACORS (2008): the route enclosed at all points by construction of at least 30 minutes, with penetrations fire stopped; adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes; 9 mm board or lath and plaster only within the risk assessment, with compensating measures.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.5 and 19.6Existing partitions of adequately fixed 12.5 mm plasterboard with a skim coat, on correctly sized and spaced timbers and in good condition, can be expected to give a nominal 30 minutes. Lesser constructions such as 9 mm plasterboard or original lath and plaster, in sound condition and good repair, may be accepted in lower-risk premises, which it describes as shared houses of no more than two storeys; in higher-risk premises only within the overall fire risk assessment, which is likely to call for compensating measures such as enhanced detection, a domestic water suppression system or a second way out.
Show in the 3D model

Party walls

  • Compartmentation
Show in the 3D model

The wall between two houses in a terrace separates two buildings.

  • For new work it should resist fire for at least 60 minutes, run the full height of the building, and carry on up through the roof space to the underside of the roof.
  • LACORS’s 2008 guidance for existing housing also lists walls separating buildings for 60 minutes.

The model takes these party walls to be sound and continuous; in a real building that is not known until they are looked at, where services pass through them and where they meet the roof.

60 minutesA wall separating two buildings resists fire for at least 60 minutes in new work (ADB Table B2), and LACORS’s 2008 guidance lists such walls for 60 minutes too.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, Table B2 note †For compartment walls that separate buildings, the period of fire resistance is increased to a minimum of 60 minutes.
  • GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 15.2Walls separating one building from another are listed among the elements needing 60 minutes of protection.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Outside walls

Brick and stucco on solid Victorian walls.

  • From the mean ground level to the mean roof level the building is 12.4 m high, more than 11 m, so any new outer surface on these walls is to be class A2-s1, d0 or better.
  • Its top storey is 11 m or more up, so any insulation added to the walls is to be too.
In existing buildings

Many existing blocks were built with combustible cladding or insulation, and a large programme of remediation is under way in England.

  • LawBuilding Regulations 2010, Schedule 1, B4External fire spread.
  • GuidanceADB Vol 1, Table 10.1For residential buildings (purpose groups 1 and 2) more than 11 m high, the outermost surface of an external wall should be class A2-s1, d0 or better wherever it is. At 11 m or less: class B-s3, d2 or better less than 1000 mm from the relevant boundary, and no provision 1000 mm or more from it. Timber cladding at least 9 mm thick is accepted only where the table asks for class C-s3, d2 (note 3).
  • GuidanceADB Vol 1, para 10.7In buildings that include a residential purpose with a storey 11 m or more in height (Diagram D6), any insulation product or filler material used in the construction of an external wall should be class A2-s1, d0 or better. This does not apply to masonry cavity walls that comply with Diagram 8.2.
  • GuidanceADB Vol 1, Appendix A and Diagrams D4 and D6The height of a building is measured as Diagram D4 shows, from the mean ground level to the mean roof level. The height of the top storey is measured as Diagram D6 shows, from ground level on the lowest side of the building to the upper surface of the top floor. They are different heights: a block whose top storey is under 11 m can be more than 11 m high.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

The street, the gardens and the raised ground floor

Common entrance hall and front door

  • Means of escape
Show in the 3D model

The converted house has one front door, up the steps at the raised ground floor, into a small common hall.

  • The raised ground floor flat’s door opens off the hall, and the stair rises from it through an arch, so the hall, the stair and its landings are the one way out for every flat above.
  • LACORS’s 2008 guidance for existing housing says a final exit door should open from inside without a removable key, with an internal thumb turn on any security lock, and strongly recommends the same for each flat’s own door.
  • The hall is kept free of obstructions and fire risks: post left to pile up by the door, or anything stored in the hall, is fuel on the only way out.

Above the raised ground floor flat’s door is a glazed light, part of the hall’s wall: one of the things a fire risk assessor checks.

30 minutesThe hall is part of the protected route, which LACORS’s 2008 guidance for existing housing asks to be enclosed in 30-minute fire-resisting construction.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 16.1Final exit doors should open from inside without a removable key, which should always be so in an HMO, including a shared house; security locks should have an internal thumb-turn.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 16.2It is strongly recommended that the exit door of each flat or bedsit also opens from inside without a removable key.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 15.3 and 15.4The protected route is kept free of obstructions and fire risks: the stairway holds no portable or bottled-gas heaters, no cooking facilities, and no furniture or storage. Storage cupboards are not located in protected routes unless they are fire resisting, kept locked shut and have smoke detection inside as appropriate (single households and shared houses of up to two storeys excepted).
  • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The front door: opens from inside without a key, by a thumb turn on any security lock

    Benchmark: LACORS (2008), for existing housing: final exit doors open from inside without a removable key, which should always be so in an HMO; security locks have an internal thumb turn.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 16.1Final exit doors should open from inside without a removable key, which should always be so in an HMO, including a shared house; security locks should have an internal thumb-turn.
Show in the 3D model

Electrical intake and gas meters

  • Means of escape
  • Compartmentation
Show in the 3D model

The electricity intake and meters are in a cupboard under the stair, its door on the route, and the gas meters are outside, in boxes on the front wall in the lightwell.

  • LACORS’s 2008 guidance for existing housing says meters are ideally not in escape routes, though this may be relaxed where they are installed to the gas and electrical regulations, and that enclosing them in fire-resisting construction is best practice.
  • LACORS also says a storage cupboard on a protected route should be fire resisting, kept locked shut and, where appropriate, have a smoke detector inside.
  • The 2026 hazard rating guidance says a meter cupboard on the route is likely to need a fire-resisting door, kept locked shut and marked Fire door keep locked shut, as the door is drawn here.

30 minutesAssumed: LACORS’s 2008 guidance for existing housing asks for a cupboard on the protected route to be fire resisting and kept locked shut, and for the route to be enclosed at all points by at least 30 minutes, but gives the cupboard no period of its own; the model takes the route’s 30 minutes, with an FD30 door kept locked shut.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 15.5Gas and electricity meters should ideally not be sited in escape routes; this may be relaxed where they are installed to the gas and electrical regulations, and enclosing them in fire-resisting construction is best practice.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 15.3 and 15.4The protected route is kept free of obstructions and fire risks: the stairway holds no portable or bottled-gas heaters, no cooking facilities, and no furniture or storage. Storage cupboards are not located in protected routes unless they are fire resisting, kept locked shut and have smoke detection inside as appropriate (single households and shared houses of up to two storeys excepted).
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, pp.17, 34 and 35Fire-resisting doors are likely to be necessary on doors to meter cupboards, storage areas and plant rooms (p.34); doors to plant and store areas are generally kept locked shut, though a self-closer may be a suitable alternative (p.35); ‘fire door keep locked shut’ signs are generally provided on electrical equipment cupboards (p.17).

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The electrical intake and meters: enclosed, the cupboard locked shut and not used as a store, and the gaps round its cables sealed

    Benchmark: LACORS (2008): meters ideally not in the route; where they are, installed to the gas and electrical regulations and best enclosed in fire-resisting construction. A cupboard on a protected route is fire resisting, kept locked shut and has smoke detection inside as appropriate; openings round services through fire-resisting construction are fire stopped. The 2026 hazard rating guidance expects a fire-resisting door, kept locked shut and marked Fire door keep locked shut.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 15.5Gas and electricity meters should ideally not be sited in escape routes; this may be relaxed where they are installed to the gas and electrical regulations, and enclosing them in fire-resisting construction is best practice.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 15.3 and 15.4The protected route is kept free of obstructions and fire risks: the stairway holds no portable or bottled-gas heaters, no cooking facilities, and no furniture or storage. Storage cupboards are not located in protected routes unless they are fire resisting, kept locked shut and have smoke detection inside as appropriate (single households and shared houses of up to two storeys excepted).
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 19.4 and 19.7In general, walls and ceilings separating units of accommodation give at least 30 minutes of fire resistance, and protected routes are fully enclosed at all points by construction of at least 30 minutes. Openings round pipes, services or ducts passing through fire-resisting construction are fire stopped to the same level of fire resistance.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, pp.17, 34 and 35Fire-resisting doors are likely to be necessary on doors to meter cupboards, storage areas and plant rooms (p.34); doors to plant and store areas are generally kept locked shut, though a self-closer may be a suitable alternative (p.35); ‘fire door keep locked shut’ signs are generally provided on electrical equipment cupboards (p.17).
Show in the 3D model

Fire alarm in the common parts

  • Detection and alarm
Show in the 3D model

A fire alarm in the common parts: a control panel inside the front door, manual call points by the front door and on each landing, smoke detectors in the hall and on each landing, and a heat detector with a sounder just inside each flat’s door, the lower ground flat’s included, so that a fire in a flat sets off the alarm through the whole house.

  • BS 5839-6 explains that a detector just inside a flat’s door is there to warn the rest of the house before a fire breaks out through that door, not to give early warning to the people in the flat where it starts, and that heat detectors respond far more slowly to fire than smoke detectors (commentary, 9.1.6 and 10.1.3); so smoke may reach the hall and stair before the common alarm sounds.
  • The detectors just inside the flats’ doors are heat detectors, drawn as the same small round fittings as the smoke detectors.
  • This is the arrangement LACORS’s 2008 guidance for existing housing gives for a three- or four-storey house converted into flats below the 1991 standard: Grade A, LD2 in the common parts, with a panel, and a linked heat alarm in each flat’s hall.
  • BS 5839-6 Table 1 notes that the Housing Act 2004 treats certain houses converted into flats before the 1991 Building Regulations as HMOs, and for the communal areas of an HMO of more than two storeys it too recommends Grade A, Category LD2, with detectors sited as BS 5839-1 sites them for a Category L2 system, and manual call points (clause 18.2).
  • For a two-storey conversion LACORS gives a simpler Grade D system: mains smoke detectors in the common parts, with no panel, linked to a heat detector inside each flat’s door.
  • Neither source recommends that for a house of this size, where a fire risk assessment would have to justify it.

The government’s 2026 hazard rating guidance says some of LACORS is out of date, particularly on fire detection.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and figure D11A mixed system: Grade A, LD2 coverage in the common areas and a heat alarm in each flat in the room or lobby opening onto the escape route, interlinked; and Grade D, LD3 coverage in each flat, a smoke alarm in that room or lobby, not interlinked, to protect the sleeping occupants. The figure shows the fire alarm control panel inside the front door.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 22.9 and Table C2A Grade A system is designed and installed to BS 5839-1, as Part 6 modifies it: smoke or heat detectors linked to a control panel, with manual call points next to final exits and, in larger multi-storey properties, on each landing, and an alarm of at least 65 dB(A) throughout and 75 dB(A) at every bedhead with the doors shut. A Grade D system is one or more mains-powered smoke or heat alarms, each with a standby battery, and no control panel.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D10For a two-storey building converted into self-contained flats: a mixed system of Grade D, LD2 coverage in the common areas and a heat detector in each flat in the room or lobby opening onto the escape route, interlinked, and Grade D, LD3 coverage in each flat.
  • StandardBS 5839-6, Table 1, the HMO rows and note L (opens in a new tab)In England and Wales certain houses converted into blocks of flats before the Building Regulations 1991 came into force are treated as HMOs under the Housing Act 2004 (note L). For HMOs other than shared houses and those of one or two storeys with no floor over 200 m2, Table 1 recommends Grade A, Category LD2 in the communal areas, with detectors sited as BS 5839-1 sites them for a Category L2 system, and Grade D1, Category LD2 in each dwelling unit of two or more rooms, in new and existing premises alike.Why it applies here: The converted house is an older conversion of four storeys above its lower ground floor, of the kind note L describes.
  • StandardBS 5839-6, clause 18.2 b), f) and h) (opens in a new tab)Manual call points are recommended in all HMOs other than houses with lodgers, shared houses of up to six and houses of one or two storeys with no floor over 200 m2; they go on the escape routes, in an HMO the common parts, at every storey exit and principal exit to open air, those at storey exits close to the door onto the protected stair or on its landing, 1.2 m above the floor.Why it applies here: The converted house is an HMO of more than two storeys under section 257.
  • StandardBS 5839-6, clauses 9.1.6 and 10.1.3 (commentary) (opens in a new tab)Heat detectors respond far more slowly to fire than smoke detectors, though they are much less likely to give false alarms. In a mixed system in an HMO of three or more storeys, detectors in each dwelling close to its entrance door are there only to warn the occupants of other dwellings before a fire breaks through that dwelling’s door; the occupants of the dwelling where the fire starts may need smoke alarms in its own circulation areas.Why it applies here: The converted house’s heat detectors with sounders just inside each flat’s door.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.

What a fire risk assessor checks

  1. The common parts’ alarm: its grade and coverage, the call points, the heat detectors with sounders inside the flats’ doors, the panel, whether it can be heard in the flats’ bedrooms with the doors shut, and its testing and records

    Benchmark: LACORS (2008), for a three- or four-storey conversion below the 1991 standard: Grade A, LD2 in the common parts with a linked heat detector in each flat’s hall. BS 5839-6 Table 1: Grade A, Category LD2 in the communal areas of an HMO of more than two storeys, which it says the Housing Act treats certain older converted houses as, with manual call points by the front door and on the landings. LACORS (2008): at least 75 dB(A) at every bedhead with the doors shut (para 22.9). LACORS (2008): a Grade A system tested weekly at a detector or call point and serviced every six months by a competent person, with a log book. The Fire Safety Order: maintained in efficient working order. The 2026 hazard rating guidance says some of LACORS is out of date, particularly on fire detection.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11 and figure D11A mixed system: Grade A, LD2 coverage in the common areas and a heat alarm in each flat in the room or lobby opening onto the escape route, interlinked; and Grade D, LD3 coverage in each flat, a smoke alarm in that room or lobby, not interlinked, to protect the sleeping occupants. The figure shows the fire alarm control panel inside the front door.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 22.9 and Table C2A Grade A system is designed and installed to BS 5839-1, as Part 6 modifies it: smoke or heat detectors linked to a control panel, with manual call points next to final exits and, in larger multi-storey properties, on each landing, and an alarm of at least 65 dB(A) throughout and 75 dB(A) at every bedhead with the doors shut. A Grade D system is one or more mains-powered smoke or heat alarms, each with a standby battery, and no control panel.
    • StandardBS 5839-6, Table 1, the HMO rows and note LIn England and Wales certain houses converted into blocks of flats before the Building Regulations 1991 came into force are treated as HMOs under the Housing Act 2004 (note L). For HMOs other than shared houses and those of one or two storeys with no floor over 200 m2, Table 1 recommends Grade A, Category LD2 in the communal areas, with detectors sited as BS 5839-1 sites them for a Category L2 system, and Grade D1, Category LD2 in each dwelling unit of two or more rooms, in new and existing premises alike.
    • StandardBS 5839-6, clause 18.2 b), f) and h)Manual call points are recommended in all HMOs other than houses with lodgers, shared houses of up to six and houses of one or two storeys with no floor over 200 m2; they go on the escape routes, in an HMO the common parts, at every storey exit and principal exit to open air, those at storey exits close to the door onto the protected stair or on its landing, 1.2 m above the floor.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 32.5 and 32.8A Grade A fire alarm is tested weekly at a detector or call point, serviced every six months by a competent person and kept with a log book; emergency escape lighting has an annual discharge test.
    • Ongoing dutyFire Safety Order 2005, Article 17(1)The responsible person must make sure that the premises, and any facilities, equipment and devices provided in respect of the safety of relevant persons, are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.

    A defect the source namesA panel-less Grade D system of interlinked mains alarms in the common parts, which LACORS (2008) and BS 5839-6 Table 1 keep for conversions of one or two storeys, unless the fire risk assessment justifies it.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D10For a two-storey building converted into self-contained flats: a mixed system of Grade D, LD2 coverage in the common areas and a heat detector in each flat in the room or lobby opening onto the escape route, interlinked, and Grade D, LD3 coverage in each flat.
    • StandardBS 5839-6, Table 1, the HMO rows and note LIn England and Wales certain houses converted into blocks of flats before the Building Regulations 1991 came into force are treated as HMOs under the Housing Act 2004 (note L). For HMOs other than shared houses and those of one or two storeys with no floor over 200 m2, Table 1 recommends Grade A, Category LD2 in the communal areas, with detectors sited as BS 5839-1 sites them for a Category L2 system, and Grade D1, Category LD2 in each dwelling unit of two or more rooms, in new and existing premises alike.
Show in the 3D model

Fire exit sign and fire action notice

  • Means of escape
Show in the 3D model

A fire exit sign over the front door, and a fire action notice by it saying what to do in a fire.

  • The sign is drawn as LACORS’s case study shows one; in a real building whether it is needed is for the fire risk assessment, which looks at how plain the way out is.
  • For a house of three or four storeys converted into flats, LACORS’s 2008 guidance for existing housing asks for a final exit sign, and signs along the route if it is complex.
  • The government’s 2026 hazard rating guidance and BS 9792 say a building with one stair does not usually need fire exit signs, but a fire action notice is generally needed in the common parts.
  • The fire safety instructions are a legal duty in any building with two or more flats and common parts residents would escape through, whatever its height: the responsible person displays them where they will be seen, covering the evacuation strategy, how to report a fire and what residents must do, and gives them to residents.

Here everyone leaves when the alarm sounds, so the fire action notice says so.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11, fire safety signsA final exit sign, and signage along the escape route if the escape route is complex.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, pp.17 and 18Buildings with only one staircase would not usually require any fire exit signage regardless of the number of floors. Fire action notices are generally required in the common areas.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.1, commentary (opens in a new tab)Fire exit signs are usually unnecessary where there is a single escape route.Why it applies here: The converted house has one way out, by its one stair and front door.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9The responsible person must display fire safety instructions in a conspicuous part of any building which contains two or more sets of domestic premises and common parts through which residents would need to evacuate, covering the evacuation strategy, how to report a fire and what residents must do, and give them to residents.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Signs and notices: the fire exit sign, the fire action notice, and the fire safety instructions given to residents

    Benchmark: LACORS (2008): a final exit sign, and signs along the route if it is complex. The law: fire safety instructions displayed and given to residents in any building with two or more flats and common parts residents would escape through. The 2026 hazard rating guidance and BS 9792 say a building with one stair does not usually need fire exit signs, but a fire action notice is generally needed in the common parts.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11, fire safety signsA final exit sign, and signage along the escape route if the escape route is complex.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, pp.17 and 18Buildings with only one staircase would not usually require any fire exit signage regardless of the number of floors. Fire action notices are generally required in the common areas.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.1, commentaryFire exit signs are usually unnecessary where there is a single escape route.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9The responsible person must display fire safety instructions in a conspicuous part of any building which contains two or more sets of domestic premises and common parts through which residents would need to evacuate, covering the evacuation strategy, how to report a fire and what residents must do, and give them to residents.
Show in the 3D model

Floor over the lower ground flat

  • Compartmentation
Show in the 3D model

The floor over the lower ground flat carries the common hall and the raised ground floor flat.

  • LACORS’s 2008 guidance for existing housing asks for 30 minutes of fire resistance in floors between units of accommodation.
  • It asks for 60 minutes between a basement or cellar and the ground floor escape route, which may be reduced to 30 minutes where the basement has an automatic fire detection and warning system to the standard the guidance recommends.
  • Here the lower ground flat has a heat detector with a sounder, in the room under the hall, linked to the house’s alarm.

Whether that, with the flat’s own alarms, is enough for the lower figure is for the fire risk assessment.

60 minutesGuidance allows 30 or 60 minutes.Assumed: LACORS’s 2008 guidance for existing housing asks for 60 minutes between a basement and the ground floor escape route, or 30 minutes where the basement has the detection it recommends, and leaves which applies here to the fire risk assessment, so the model takes the more onerous 60 minutes.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.1Floors and ceilings between units of accommodation should generally give 30 minutes of fire resistance. Between a basement or cellar and the ground floor escape route they should give 60 minutes, which may be reduced to 30 minutes where the basement has automatic fire detection to the guidance’s standard.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D11, fire separation30 minutes of fire resistance between flats throughout is the ideal, but on risk assessment there may be no need for more fire-resisting separation between the flats, provided the walls and floors are of sound, traditional construction and additional compensatory detection is fitted.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.3Ceilings of 9 mm plasterboard or lath and plaster in sound condition give a lower standard of fire resistance: acceptable within the fire risk assessment in single households and shared houses of no more than three storeys, and in premises of higher risk only with compensating measures such as enhanced detection.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.4Ceilings not in sound condition, particularly lath and plaster ones, should be replaced or upgraded to give 30 minutes of fire resistance.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The floor over the lower ground flat, under the common hall and the raised ground floor flat

    Benchmark: LACORS (2008): 60 minutes between a basement or cellar and the ground floor escape route, which may be reduced to 30 minutes where the basement has an automatic fire detection and warning system to the standard the guidance recommends; 30 minutes between units of accommodation.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 20.1Floors and ceilings between units of accommodation should generally give 30 minutes of fire resistance. Between a basement or cellar and the ground floor escape route they should give 60 minutes, which may be reduced to 30 minutes where the basement has automatic fire detection to the guidance’s standard.
Show in the 3D model

The 11 m line, and a conversion done today

  • Firefighting
  • External wall
  • Means of escape
Show in the 3D model

Many provisions for blocks of flats in Approved Document B start once the top storey is more than 11 m above ground, measured to the floor of the top storey.

  • They are guidance on meeting the Building Regulations, which apply to building work and to a material change of use, such as turning a house into flats, when that work is carried out; they do not require a house converted long ago to be brought up to today’s standard, though any new building work to it would have to meet them.

For an existing building over 11 m the law adds two things here:

  • The responsible person must check the fire doors in the common parts at least every 3 months and use best endeavours to check the flat entrance doors at least every 12 months.
  • Because everyone leaves at once when the alarm sounds, the responsible person must also run residential evacuation plans: identify residents who could not get out without help, offer them a person-centred fire risk assessment, agree an emergency evacuation statement with each, and give the fire and rescue service a building emergency evacuation plan.

If it were converted today, Approved Document B would ask for:

  • sprinklers in every flat (para 7.4)
  • a protected lobby or corridor with a smoke vent between each flat and the single stair, and a vent at the head of the stair (paras 3.27 and 3.54 to 3.57)
  • no flat opening straight into the hall between the stair and the front door, which counts as part of the stair and needs the same lobby protection (para 3.84)
  • flights and landings of class A2-s3, d2 or better, so not the timber stair (para 3.85(a))
  • the full fire resistance of Appendix B in the floors, 60 minutes, as the house has four storeys above its lower ground floor (paras 6.5 to 6.7)
  • access for a pump to within 45 m of every point in each flat, measured along the route of the hose, or else fire mains (para 13.2): from where the model stops the pump, the hose would need 50.6 m to reach the farthest point of the top flat (about 46.4 m from a pump that could stop at the kerb by the gate, if the parked cars were not there), so a conversion done today would need a closer standing position, if the street allows one, or a fire main
  • inside the flats more than 4.5 m up, a protected entrance hall, a layout with no point in a habitable room more than 9 m from the flat’s door, or a second way out (para 3.18), and for the top flat, with no entrance of its own at ground level, one of the approaches in para 3.21, such as a protected stair inside the flat
  • floor and flat signs and a secure information box (paras 15.13 and 15.19)

LACORS’s 2008 guidance for existing housing, in its case study of a house of three or four storeys converted below the 1991 standard, asks for none of these. It does ask for 60 minutes in the floor between a basement and the ground floor escape route unless the basement has fire detection, and it asks councils and landlords to give serious consideration to water suppression systems, which it treats as one way to make up for weaker construction.

As the model draws it, this house is past it:

  • its top storey is taken as 11.5 m up, measured from the garden on the lowest side
  • the building is 12.4 m high from the mean ground level to the mean roof level, the height Table 10.1 uses
  • GuidanceADB Vol 1, para 7.4Blocks of flats with a top storey more than 11 m above ground should have a sprinkler system throughout the building, in accordance with Appendix E. The note to the paragraph excepts only common areas such as stairs, corridors and landings, and only when they are fire sterile.
  • GuidanceADB Vol 1, para 15.13To help the fire service identify each floor, a block of flats with a top storey more than 11 m above ground level should have floor identification signs and flat indicator signs.
  • GuidanceADB Vol 1, para 15.19Blocks of flats with a top storey more than 11 m above ground level should be provided with a secure information box.
  • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.
  • GuidanceADB Vol 1, para 10.7In buildings that include a residential purpose with a storey 11 m or more in height (Diagram D6), any insulation product or filler material used in the construction of an external wall should be class A2-s1, d0 or better. This does not apply to masonry cavity walls that comply with Diagram 8.2.
  • GuidanceADB Vol 1, para 10.10In buildings that include a residential purpose with a storey 11 m or more in height, balconies should meet one of two conditions; the first is that they contain only materials of class A1 or A2-s1, d0, apart from listed items such as cavity trays between two leaves of masonry, membranes, seals, fixings and electrical installations.
  • GuidanceADB Vol 1, para 3.32For some low rise buildings a single stair, protected as Diagram 3.9 shows, may be used where all of the following apply: the top storey is a maximum of 11 m above ground level; no more than three storeys are above the ground storey; the stair does not connect to a covered car park unless it is open sided; the stair does not serve offices, stores or other ancillary accommodation, unless they are separated from it by a protected lobby or protected corridor (minimum REI 30) with at least 0.4 m2 of permanent ventilation, or protected from smoke by a mechanical smoke control system; and a vent is provided for the fire and rescue service (para 3.32(e)).
  • GuidanceADB Vol 1, para 3.27(a)From the flat entrance door, a single escape route is acceptable on a storey served by a single common stair where every flat is separated from the stair by a protected lobby or common protected corridor (Diagram 3.7) and the travel distance in Table 3.1 for escape in one direction only is not exceeded.
  • GuidanceADB Vol 1, Table 3.1 note 2The maximum travel distance from a flat entrance door to the storey exit, where escape is in one direction only, is 7.5 m; in a small single stair building that follows Diagram 3.9 it is reduced to 4.5 m.
  • GuidanceADB Vol 1, para 3.54Except in buildings that comply with Diagram 3.9, the corridor or lobby directly in front of each storey exit should have a smoke vent, as high as practicable, with its top edge at least as high as the top of the door to the stair.
  • GuidanceADB Vol 1, Diagram 3.7 note 6A single common stair arrangement is only suitable for buildings with a top storey less than 18 m in height.
  • GuidanceADB Vol 1, Table 10.1For residential buildings (purpose groups 1 and 2) more than 11 m high, the outermost surface of an external wall should be class A2-s1, d0 or better wherever it is. At 11 m or less: class B-s3, d2 or better less than 1000 mm from the relevant boundary, and no provision 1000 mm or more from it. Timber cladding at least 9 mm thick is accepted only where the table asks for class C-s3, d2 (note 3).
  • GuidanceADB Vol 1, Appendix A and Diagrams D4 and D6The height of a building is measured as Diagram D4 shows, from the mean ground level to the mean roof level. The height of the top storey is measured as Diagram D6 shows, from ground level on the lowest side of the building to the upper surface of the top floor. They are different heights: a block whose top storey is under 11 m can be more than 11 m high.
  • GuidanceADB Vol 1, Appendix E, para E3Where sprinklers are needed they go throughout the building or separated part. Systems in residential buildings follow BS 9251. Systems in non-residential buildings, or in residential buildings outside the scope of BS 9251, follow BS EN 12845, with the extra measures for reliability in its Annex F.
  • GuidanceADB Vol 1, para 3.55(a)A smoke vent from a corridor or lobby may be located on an external wall, with a minimum free area of 1.5 m2.
  • GuidanceADB Vol 1, para 3.56A vent to the outside with a minimum free area of 1 m2 should be provided from the top storey of the stair.
  • GuidanceADB Vol 1, para 3.57In single stair buildings, the smoke vents on the storey where the fire starts, and the vent at the head of the stair, should be opened by smoke detectors in the common parts.
  • GuidanceADB Vol 1, para 3.84Every protected stairway should lead to a final exit, either directly or via a protected exit passageway. Any protected exit corridor or stair should have the same standard of fire resistance and lobby protection as the stair it serves.
  • GuidanceADB Vol 1, para 3.85(a)The flights and landings of escape stairs should be constructed of materials achieving class A2-s3, d2 or better if the escape stair is the only stair in a building with more than three storeys.
  • GuidanceADB Vol 1, paras 6.5 to 6.7Where an existing house is converted into flats, the existing construction should be reviewed: retained timber floors may make it difficult to meet the fire resistance asked for. In a converted building of no more than three storeys, REI 30 could be accepted for elements of structure if the means of escape follow Section 3; with four or more storeys, the full standard of Appendix B is necessary.
  • GuidanceADB Vol 1, Table B2 and its notesBlock of flats with sprinklers, top floor up to 18 m above ground: 60 minutes for the ground and upper storeys, and 60 minutes for a basement storey up to 10 m deep. The floor over a basement takes the higher of the two (note *). A floor inside a flat of more than one storey that does not support the building may be 30 minutes (note +). For flat conversions, paras 6.5 to 6.7 say when 30 minutes is acceptable (note §).
  • GuidanceADB Vol 1, para 13.2For flats, either provide access for a pumping appliance to within 45 m of all points inside each flat, measured along the route of the hose, or provide fire mains in accordance with paras 13.5 and 13.6.
  • GuidanceADB Vol 1, para 3.18(a)In flats with storeys more than 4.5 m above ground level, one approach is a protected entrance hall (minimum REI 30) serving all habitable rooms, meeting the conditions shown in Diagram 3.2.
  • GuidanceADB Vol 1, para 3.21A multi-storey flat with no external entrance of its own at ground level should follow one of four approaches, for example a protected stairway inside the flat together with sprinklers.
  • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 3, 5 to 10 and 13A building with two or more sets of domestic premises more than 11 m high to its top storey (Approved Document B Appendix D) with a simultaneous evacuation strategy is a specified residential building; its responsible person must identify residents whose ability to evacuate unaided is compromised, offer person-centred fire risk assessments, implement reasonable and proportionate mitigating measures, agree and record emergency evacuation statements, review them every 12 months, give the fire and rescue authority each such resident’s details with their explicit consent, and prepare, share and annually review a building emergency evacuation plan.
  • LawBuilding Regulations 2010, Regulations 3, 4, 5 and 6Building work, which includes the material alteration of a building, is to be carried out so that it complies with the applicable requirements of Schedule 1; a material change of use, such as a building coming to contain a flat where it did not before, brings the requirements regulation 6 lists. The requirements apply to the work and the change of use when they are done.
Show in the 3D model

Front lightwell

  • Means of escape
Show in the 3D model

The lightwell in front of a lower ground floor brings in daylight and, here, leads to a front door.

  • It only works as a way out if its steps reach the street and nothing locked stands in the way.
  • In LACORS’s 2008 guidance for existing housing, a basement well under a window is one of the things that rules the window out as an escape window.
  • GuidanceADB Vol 1, para 3.9Basement storeys containing habitable rooms should have either an emergency escape window or external door providing escape from the basement, or a protected stairway (minimum REI 30) leading from the basement to a final exit.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 14.2An escape window is accepted only where its room is no more than 4.5 m above ground and nothing such as a basement well lies under it; where it leads to a back garden with no exit, the garden should be at least as deep as the building is high.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The lightwell: steps up to the street, nothing locked or stored in the way, the lower ground doors

    Benchmark: For new building work, Approved Document B says a basement storey with habitable rooms should have an escape window or door of its own, or a protected stair to a final exit. LACORS (2008), for existing housing: a separate exit is the ideal, and a basement well under a window can stop it being an escape window.

    • GuidanceADB Vol 1, para 3.9Basement storeys containing habitable rooms should have either an emergency escape window or external door providing escape from the basement, or a protected stairway (minimum REI 30) leading from the basement to a final exit.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 14.2An escape window is accepted only where its room is no more than 4.5 m above ground and nothing such as a basement well lies under it; where it leads to a back garden with no exit, the garden should be at least as deep as the building is high.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.
Show in the 3D model

Bins and cycle stores

  • Means of escape
Show in the 3D model

With no way to the back gardens except through the houses, bins and cycles are kept at the front.

  • They are kept clear of the steps, the lightwell and its railings, so they never block a way out or feed a fire under a window.
  • Here e-bikes and e-scooters are not kept or charged in the common parts: a fire risk assessment notes any lithium-ion battery vehicles, assesses their risk and deals with them in its action plan.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary (opens in a new tab)Lithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.Why it applies here: Cycles are stored at the front of the houses, by the way out.
  • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.
  • Ongoing dutyThe Licensing and Management of Houses in Multiple Occupation (Additional Provisions) (England) Regulations 2007, Regulations 1(2), 4, 5, 7(3) and 8Regulations 2 to 11 apply to any HMO in England to which section 257 of the Housing Act 2004 applies. The manager displays their details in the common parts; keeps the means of escape free from obstruction and in good order and repair, the fire alarm and any equipment in good working order, and escape notices visible; has the fixed electrical installation tested at intervals of no more than five years; and keeps the common parts, including the entrance door and the flats’ doors, safe and in repair, so far as the manager can reasonably be expected to control them.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Bins and cycles at the front: clear of the steps, the lightwell and the windows; e-bikes not stored or charged in the common parts

    Benchmark: Escape routes kept clear: in the converted house a duty of the responsible person under the Fire Safety Order and of its manager under the 2007 regulations for section 257 HMOs; lithium-ion vehicles noted and dealt with in the action plan.

    • Ongoing dutyThe Licensing and Management of Houses in Multiple Occupation (Additional Provisions) (England) Regulations 2007, Regulations 1(2), 4, 5, 7(3) and 8Regulations 2 to 11 apply to any HMO in England to which section 257 of the Housing Act 2004 applies. The manager displays their details in the common parts; keeps the means of escape free from obstruction and in good order and repair, the fire alarm and any equipment in good working order, and escape notices visible; has the fixed electrical installation tested at intervals of no more than five years; and keeps the common parts, including the entrance door and the flats’ doors, safe and in repair, so far as the manager can reasonably be expected to control them.
    • Ongoing dutyFire Safety Order 2005, Article 14(1)Where necessary, the responsible person must keep routes to emergency exits, and the exits themselves, clear at all times.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentaryLithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.

    A defect the source namesLithium-ion vehicles can give very rapid fire development, toxic fumes and explosion if damaged or faulty.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentaryLithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.
Show in the 3D model

Enclosed back gardens

  • Means of escape
Show in the 3D model

The back gardens back onto other gardens, with no lane behind.

  • A garden reached only through the house is a safe place to escape to only if it is long enough to get away from the building.
  • For a new house: longer than the house is high to its mean roof level and longer than any rear extension is high.
  • In LACORS’s 2008 guidance for existing housing: at least as deep as the building is high.

The gardens here are 14.0 m long beyond the outriggers.

  • The houses are 13.2 m high from the garden to their mean roof level, the measure Approved Document B uses, and 15.0 m to the ridge.
  • LACORS does not say how it measures a building’s height.
  • GuidanceADB Vol 1, para 2.10(b) and Diagram 2.5Where escape from a house is into an enclosed space with an exit only through other buildings, such as a back garden, the length of the space should exceed the greater of the house’s height above ground to its mean roof level, and the height of any rear extension.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 14.2An escape window is accepted only where its room is no more than 4.5 m above ground and nothing such as a basement well lies under it; where it leads to a back garden with no exit, the garden should be at least as deep as the building is high.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Fire engine in the street

In a street of terraced houses the fire engine stops in the street, between the parked cars, and firefighters run hose from the pump up the steps, in at the front door and up the stair.

  • For flats built or converted now, Approved Document B says a pump should be able to get within 45 m of every point inside each flat, measured along the route of the hose, or the building should have fire mains.
  • That is guidance on meeting the Building Regulations, which apply to building work when it is carried out, so it does not require an existing house to be brought up to it.
  • Approved Document B’s typical specification asks for a road at least 3.7 m wide between kerbs for a pump.

Here the street is 7.0 m between kerbs, and the model takes cars to be parked on both sides, leaving about 3.0 m clear between them.

  • For new building work, Approved Document B’s typical specification for a pump’s access route gives a minimum of 3.7 m of road between kerbs (Table 13.1), and notes that appliances are not standardised.
  • Whether a pump could get through, stop and work here would need checking on a real street, with its width, parked cars, obstructions and turning.
  • From where the model stops it, a hose reaches the converted house’s front door in 12.2 m, and the farthest corner of the top flat’s loft in 50.6 m, up the common stair and the flat’s own stair.
  • The lower ground flat’s far corner, down the lightwell, is 38.6 m away.
  • GuidanceADB Vol 1, para 13.2For flats, either provide access for a pumping appliance to within 45 m of all points inside each flat, measured along the route of the hose, or provide fire mains in accordance with paras 13.5 and 13.6.
  • GuidanceADB Vol 1, Table 13.1A typical access route for a pump appliance: a road at least 3.7 m wide between kerbs, gateways at least 3.1 m wide, clearance at least 3.7 m high, and a carrying capacity of 12.5 tonnes.
  • LawBuilding Regulations 2010, Regulations 3, 4, 5 and 6Building work, which includes the material alteration of a building, is to be carried out so that it complies with the applicable requirements of Schedule 1; a material change of use, such as a building coming to contain a flat where it did not before, brings the requirements regulation 6 lists. The requirements apply to the work and the change of use when they are done.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Fire hydrant in the footway

The fire engine takes water from a public hydrant on the water main under the footway.

  • Its position is shown by a plate nearby, which the water undertaker must provide.
  • For a new block of flats or other building, Approved Document B asks for hydrants of its own only if it has a compartment of more than 280 m2 and stands more than 100 m from an existing hydrant (Vol 1 para 14.8, Vol 2 para 16.8); it has no such test for houses.

The converted house is not a new building, and it has no compartment over 280 m2, so it would not need a hydrant of its own.

  • LawThe Fire and Rescue Services Act 2004, Section 42A water undertaker must cause the location of every fire hydrant it provides to be clearly indicated by a notice or distinguishing mark, which it may place on a wall or fence adjoining a highway or public place.
  • GuidanceADB Vol 1, para 14.8A building needs additional fire hydrants only if it has a compartment of more than 280 m2 and is being erected more than 100 m from an existing fire hydrant.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

The lower ground floor

Lower ground floor flat

  • Means of escape
Show in the 3D model

The lower ground flat has its own front door from the lightwell, under the porch landing, and a door to the garden: it does not use the common hall or stair.

  • LACORS’s 2008 guidance for existing housing treats a lower ground floor below a raised entrance like a basement, and says that ideally it has its own exit to a place of safety.

It is a two-bedroom flat of 64.1 m2 measured inside its walls:

  • its living room is in the bay over the lightwell
  • its bedroom looks onto the side return
  • its kitchen opens at garden level onto the garden

Its front door is under the porch landing, reached down the lightwell steps.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model
  • This is guidance on what an assessor looks at, not an assessment of any real building.
  • LACORS is guidance for existing housing, not Building Regulations; its case studies are not off-the-peg solutions, and there is no obligation to adopt their exact solutions.
  • A fire risk assessment is made by a competent person (BS 9792:2025 clause 7).
  • LACORS dates from 2008. The government’s June 2026 hazard rating guidance says some of its content is out of date, particularly on domestic fire detection and firefighting equipment, but that it is likely to remain the most appropriate guidance for a range of existing homes, including shared houses and buildings converted into flats to a standard below the Building Regulations 1991.

Ongoing duties once people live here

Fire safety does not stop when the building is finished. These are the duties the law puts on whoever runs this building once people live and work in it: what must be done, by whom, when, and the law it comes from. Some apply only from a certain height; each says where it applies in this building.

  1. Fire risk assessment of the common parts

    Who
    The responsible person for the converted house: whoever controls its common parts in connection with a business, such as the freeholder or a management company, or else the owner. A managing agent shares the duties so far as it has control.
    What
    Make and keep under review a suitable and sufficient assessment of the fire risks to the people in and around the building, covering its structure, external walls and common parts and the doors between the flats and the common parts, and review it after a significant change such as a conversion.
    When
    Any building with two or more sets of domestic premises: the converted house.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety Order 2005, Articles 6(1A) and 9Where a building contains two or more sets of domestic premises, the Order applies to the building’s structure and external walls and any common parts, and to all doors between the domestic premises and the common parts. The responsible person must make a suitable and sufficient assessment of the risks, and review it regularly and after any significant change, including conversions.

    In the model: Common stair and landings, Common entrance hall and front door, Flat entrance doors

  2. Fire safety instructions for residents

    Who
    The responsible person for the converted house
    What
    Display fire safety instructions in a conspicuous part of the building: the evacuation strategy, how to report a fire, and what residents must do if a fire occurs. Give a copy to new residents and to every resident each year.
    When
    A building with two or more sets of domestic premises and common parts residents would escape through, at any height: the converted house.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 9The responsible person must display fire safety instructions in a conspicuous part of any building which contains two or more sets of domestic premises and common parts through which residents would need to evacuate, covering the evacuation strategy, how to report a fire and what residents must do, and give them to residents.

    In the model: Fire exit sign and fire action notice

  3. Fire door information for residents

    Who
    The responsible person for the converted house
    What
    Tell residents that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported at once: new residents when they move in, and all residents every 12 months.
    When
    A building with two or more sets of domestic premises and common parts residents would escape through: the converted house.
    In this building
    Applies here at every height.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(1) to (3)The responsible person must give residents information that fire doors should be kept shut when not in use, that self-closing devices should not be tampered with, and that faults or damage should be reported.

    In the model: Flat entrance doors

  4. Fire door checks above 11 m

    Who
    The responsible person for the converted house
    What
    Check the fire doors in the common parts, with their self-closers, at least every 3 months, and use best endeavours to check the flat entrance doors at least every 12 months, keeping a record of the steps taken.
    When
    A building with two or more sets of domestic premises above 11 m to its top storey: the converted house, whose loft, as the model takes it, is 11.5 m up. It applies to existing buildings, however long ago they were converted.
    In this building
    Applies here at: Over 11 m.
    • Ongoing dutyFire Safety (England) Regulations 2022, Regulation 10(4) to (8)Where a building with two or more sets of domestic premises is above 11 m to its top storey, the responsible person must use best endeavours to check the fire doors at the entrances of the flats at least every 12 months, keeping a record of the steps taken, and must check the fire doors in the communal areas at least every 3 months; the checks must include the self-closing devices.

    In the model: Flat entrance doors, Common stair and landings

  5. Residential evacuation plans above 11 m

    Who
    The responsible person for the converted house
    What
    Use reasonable endeavours to identify residents who could not evacuate without help because of a cognitive or physical impairment or condition; offer each a person-centred fire risk assessment and carry it out if they ask; put in place the reasonable and proportionate measures it shows; try to agree an emergency evacuation statement with them and give them a copy; review all of these at least every 12 months; with each resident’s explicit consent, give the fire and rescue authority their flat and floor number, the help they may need and whether they have a statement; and prepare a building emergency evacuation plan, give it to the fire and rescue authority and review it at least every 12 months.
    When
    A building with two or more sets of domestic premises more than 11 m high to its top storey, where the responsible person has decided everyone leaves at once: the converted house, whose loft, as the model takes it, is 11.5 m up. In force since 6 April 2026.
    In this building
    Applies here at: Over 11 m.
    • Ongoing dutyResidential Evacuation Plans Regulations 2025, Regulations 3, 5 to 10 and 13A building with two or more sets of domestic premises more than 11 m high to its top storey (Approved Document B Appendix D) with a simultaneous evacuation strategy is a specified residential building; its responsible person must identify residents whose ability to evacuate unaided is compromised, offer person-centred fire risk assessments, implement reasonable and proportionate mitigating measures, agree and record emergency evacuation statements, review them every 12 months, give the fire and rescue authority each such resident’s details with their explicit consent, and prepare, share and annually review a building emergency evacuation plan.

    In the model: The 11 m line, and a conversion done today, Fire exit sign and fire action notice

  6. Managing the converted house

    Who
    The manager of the converted house: the person managing it
    What
    Display the manager’s name, address and telephone number in the common parts; keep the means of escape free from obstruction and in good order and repair; keep the fire alarm and any fire fighting equipment in good working order; display notices showing the means of escape where every occupier can see them; have the fixed electrical installation inspected and tested at least every five years; and keep the common parts, including the front door and the flats’ entrance doors, safe, in repair and reasonably clear, so far as the manager can reasonably be expected to control them.
    When
    A converted block of flats to which section 257 applies: the converted house, on the model’s assumption about owner-occupation.
    In this building
    Applies here at every height.
    • Ongoing dutyThe Licensing and Management of Houses in Multiple Occupation (Additional Provisions) (England) Regulations 2007, Regulations 1(2), 4, 5, 7(3) and 8Regulations 2 to 11 apply to any HMO in England to which section 257 of the Housing Act 2004 applies. The manager displays their details in the common parts; keeps the means of escape free from obstruction and in good order and repair, the fire alarm and any equipment in good working order, and escape notices visible; has the fixed electrical installation tested at intervals of no more than five years; and keeps the common parts, including the entrance door and the flats’ doors, safe and in repair, so far as the manager can reasonably be expected to control them.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Sections 254(1)(e) and 257(1) to (5)A converted block of flats, a building converted into and consisting of self-contained flats, is a house in multiple occupation where the building work done for the conversion did not comply with the appropriate building standards and still does not, and less than two thirds of the flats are owner-occupied. For a conversion completed before 1 June 1992 the standards are those of the Building Regulations 1991; a flat is owner-occupied if lived in by someone with a lease of more than 21 years or the freehold, or their household.

    In the model: Common stair and landings, Fire alarm in the common parts, Flat entrance doors

  7. Smoke and carbon monoxide alarms in rented flats

    Who
    The immediate landlord of each rented flat
    What
    Make sure there is a smoke alarm on each storey of the flat with a room used as living accommodation, and a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker; check them on the day a new tenancy begins, and repair or replace them when a tenant reports a fault.
    When
    Each flat let on a tenancy the regulations cover. A licensable HMO is outside these regulations: its licence carries the same alarm conditions.
    In this building
    Applies here at every height.
    • Ongoing dutySmoke and Carbon Monoxide Alarm Regulations 2015, Regulations 2(1) and 4The regulations do not cover an HMO that must be licensed under Part 2 of the Housing Act 2004. For other specified tenancies the landlord ensures a smoke alarm on each storey with living accommodation and a carbon monoxide alarm in any room with a fixed combustion appliance other than a gas cooker, checked on the day a new tenancy begins.

    In the model: Alarms in the flats

  8. The council’s housing hazard rating

    Who
    The council, assessing the landlord’s homes
    What
    The council may inspect each flat and the converted house as a whole with its common parts, and rate their hazards; fire and explosions is one hazard. A hazard in the high band is a category 1 hazard, which the council must act on.
    When
    Any home, for inspections begun on or after 23 June 2026 under the amended rating system.
    In this building
    Applies here at every height.
    • LawThe Housing Health and Safety Rating System (England) Regulations 2005, Schedule 1, para 23A, and regulations 7 and 8; SI 2026/571 regulation 10, as amended by SI 2026/629The hazard of fire and explosions: exposure to uncontrolled fire and associated smoke and fumes, and an explosion. A hazard in the High band is a category 1 hazard. The amended rules apply to inspections begun on or after 23 June 2026.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Sections 1(4), 4 and 5(1)Residential premises include an HMO and any common parts of a building containing one or more flats. The council must arrange an inspection where it considers one appropriate or receives an official complaint, and must take enforcement action on a category 1 hazard.

    In the model: Common stair and landings

Guides behind this model

Read more on the topics this building shows.

What this model assumes

  • Seen from the street, the converted house is on the left. The house on the right is the same house let as a shared house, drawn closed: only its outside is shown.
  • A composite of the type, not any real address: a mid-terrace Victorian house, 5.8 m wide, with a lower ground floor, a raised ground floor, a first and a second floor, a loft and a rear outrigger.
  • Heights are scaled from evidence (printed ceiling heights in house listings plus 0.25 m floors). Ground is taken on the lowest side, the rear garden, which is also the front lightwell’s floor: the street is 1.67 m higher. On that reading the loft floor is 11.48 m up. For this illustration the top storey is taken as 11.48 m; a real building would need measuring before deciding which duties that depend on height apply.
  • The converted house was converted long ago, to a standard below the 1991 Building Regulations: one front door into a small common hall, the original timber stair from the hall to the second floor landing, and four flats. The lower ground flat has its own door from the lightwell; the top flat, on the second floor and in the loft, has its own stair behind its front door. No building work is being done, so the Building Regulations do not apply to it now: it is judged in use, under the Fire Safety Order in its structure, external walls, common parts and flat entrance doors, and under the Housing Act 2004, using LACORS’s 2008 guidance for existing housing.
  • The model takes fewer than two thirds of the converted house’s flats to be owner-occupied (lived in by someone holding a lease of more than 21 years or the freehold), which, with a conversion that did not and still does not meet the 1991 building standards, makes it a house in multiple occupation under section 257 of the Housing Act 2004.
  • Everyone leaves at once when the alarm sounds.
  • The converted house’s alarm follows LACORS’s 2008 guidance for existing housing, case study D11, in the common parts: a control panel inside the front door, manual call points by it and on each landing, smoke detection in the hall and on the landings, and a heat detector with a sounder just inside each flat’s door; each flat also has its own alarms, drawn to BS 5839-6 Table 1.
  • The fire engine stops in the street level with the house, between parked cars. Hose distances run along the middle of each stair flight on its slope, and across landings and rooms on plan.
  • The loft’s ceiling is taken 0.15 m inside the roof’s slope, for its rafters, insulation and boards: the model’s choice, which sets the top flat’s counted area.
  • Where neither a part’s own text nor the guidance it cites settles a fire resistance period, the model assumes one from LACORS’s 2008 guidance for existing housing, taking the more onerous value where the guidance leaves the choice to the fire risk assessment: 60 minutes in the floor over the lower ground flat and in the party wall where it meets the roof, and 30 minutes, with an FD30 door kept locked shut, round the meter cupboard. Each such value is marked as assumed where it is shown.

Approved Document B is the 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments, read for this building on 13 and 14 November 2026 and cited only for what new building work, such as a conversion done today, would need, and for the way it measures a building’s height, which the law borrows. LACORS is the 2008 guidance for existing housing, read with the government’s June 2026 hazard rating guidance on fire. BS 9792:2025 and BS 5839-6:2019+A1:2020 are paraphrased. Legislation is as revised on legislation.gov.uk.

Technical review by INFIRISK editorial: 15 November 2026 · Next review: 15 February 2027