Roof over the party walls
- Compartmentation
- External wall
Where a party wall meets a pitched roof, it is built up to the underside of the slates and fire-stopped there, and carried across the eaves, so fire cannot pass over the top of it through the roof space.
- The roof covering either side is chosen so fire does not spread across it from one house to the next.
- BS 9792 notes that in old blocks of flats the walls between flats may not go up through the roof void, and the government’s 2026 hazard rating guidance expects fire separation in the roof space between terraced houses too.
- So an assessor tries to look into the roof void, and records it when that is not practicable.
60 minutesAssumed: where the party wall is carried up to the roof it takes the 60 minutes of the party wall below, which LACORS’s 2008 guidance for existing housing lists for walls separating buildings; the roof’s own text says the wall is fire-stopped there and gives no period.
- LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
- GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
- GuidanceADB Vol 1, paras 7.15 and 7.16In a block of flats the junction of a compartment wall with the roof follows the provisions for houses (paras 5.11 and 5.12). In residential buildings no more than 15 m high, a combustible substrate and timber battens fully bedded in mortar over the width of the wall may extend over it.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary (opens in a new tab)Fire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.Why it applies here: The party walls run up through the pitched roof void.
- GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Reasonable fire separation is expected within any roof space, for example between terraced houses, and the lines of compartmentation between top-floor flats in buildings with a stay put policy should extend through the roof void in a continuous vertical plane to the underside of the roof.Why it applies here: The party walls run up through the pitched roof void.
INFIRISK guides
No INFIRISK guide on this yet.
What a fire risk assessor checks
The party wall through the roof void: continuous to the underside of the roof, fire-stopped, and the void reachable
Benchmark: For new work: the wall continued to the underside of the roof covering, fire-stopped, and across the eaves.
- GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentaryFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.
- GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Reasonable fire separation is expected within any roof space, for example between terraced houses, and the lines of compartmentation between top-floor flats in buildings with a stay put policy should extend through the roof void in a continuous vertical plane to the underside of the roof.
A defect the source namesFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire; access is recorded when it was not practicable.
- StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentaryFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.