INFIRISK 3D buildings · Existing shared house (HMO)

Shared house (HMO)

A Victorian house in a terrace, let as a shared house to six people and judged as it is lived in today. Step through every floor, from the front door along the protected route to the bedrooms, and see what a fire risk assessor checks.

See the same house converted into flats

This building is illustrative. It is drawn to show how the guidance fits together, and it is not a fire strategy or a design for any real building. For your own building, speak to a competent fire engineer or fire risk assessor.

Every part of the building

The roof

Roof over the party walls

  • Compartmentation
  • External wall
Show in the 3D model

Where a party wall meets a pitched roof, it is built up to the underside of the slates and fire-stopped there, and carried across the eaves, so fire cannot pass over the top of it through the roof space.

  • The roof covering either side is chosen so fire does not spread across it from one house to the next.
  • BS 9792 notes that in old blocks of flats the walls between flats may not go up through the roof void, and the government’s 2026 hazard rating guidance expects fire separation in the roof space between terraced houses too.
  • So an assessor tries to look into the roof void, and records it when that is not practicable.

60 minutesAssumed: where the party wall is carried up to the roof it takes the 60 minutes of the party wall below, which LACORS’s 2008 guidance for existing housing lists for walls separating buildings; the roof’s own text says the wall is fire-stopped there and gives no period.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
  • GuidanceADB Vol 1, paras 7.15 and 7.16In a block of flats the junction of a compartment wall with the roof follows the provisions for houses (paras 5.11 and 5.12). In residential buildings no more than 15 m high, a combustible substrate and timber battens fully bedded in mortar over the width of the wall may extend over it.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary (opens in a new tab)Fire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.Why it applies here: The party walls run up through the pitched roof void.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Reasonable fire separation is expected within any roof space, for example between terraced houses, and the lines of compartmentation between top-floor flats in buildings with a stay put policy should extend through the roof void in a continuous vertical plane to the underside of the roof.Why it applies here: The party walls run up through the pitched roof void.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The party wall through the roof void: continuous to the underside of the roof, fire-stopped, and the void reachable

    Benchmark: For new work: the wall continued to the underside of the roof covering, fire-stopped, and across the eaves.

    • GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentaryFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, p.36Reasonable fire separation is expected within any roof space, for example between terraced houses, and the lines of compartmentation between top-floor flats in buildings with a stay put policy should extend through the roof void in a continuous vertical plane to the underside of the roof.

    A defect the source namesFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire; access is recorded when it was not practicable.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentaryFire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.
Show in the 3D model

The first and second floors

Protected escape route (shared house)

  • Means of escape
  • Compartmentation
Show in the 3D model

For a shared house of three or four storeys, LACORS’s 2008 guidance for existing housing shows the hall, stairs and landings as one protected route to the front door, enclosed in 30-minute fire-resisting construction, with FD30 fire doors to the rooms that hold a fire risk.

  • It is existing housing guidance, applied by the council under the Housing Act, not Building Regulations.
  • In a low-risk three-storey shared house, sound existing walls of 20 minutes may be accepted.
  • The front door opens from inside without a key.

Here it is a three-storey shared house by LACORS’s count, from the front door up and leaving out the lower ground, so note 8 applies:

  • a 30-minute route is the ideal
  • if the house is judged low risk, sound existing walls of 20 minutes may be accepted

30 minutesGuidance allows 20 or 30 minutes.LACORS’s 2008 guidance shows the route enclosed in 30-minute fire-resisting construction; in a low-risk three-storey shared house, sound existing walls of 20 minutes may be accepted.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5, note 8In existing three-storey shared houses of low risk, existing walls and partitions may be accepted if 20 minutes of fire resistance can be achieved, which sound, conventional construction, including sound lath and plaster, is likely to give; doors onto the route may be accepted if they are sound, solid, close fitting and self-closing.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 16.1Final exit doors should open from inside without a removable key, which should always be so in an HMO, including a shared house; security locks should have an internal thumb-turn.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 3.2 and 33.2The case studies must not be used as off-the-peg solutions, and there is no obligation to adopt their exact solutions: each building is judged on its own risk assessment.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.
Show in the 3D model

Fire doors to the rooms (shared house)

  • Means of escape
  • Compartmentation
Show in the 3D model

The doors from the route into the rooms that hold the fire risk are FD30 fire doors.

  • LACORS’s 2008 guidance for existing housing, in its case study for a shared house of three or four storeys, leaves smoke seals off these doors, with alarms on the route and in the kitchen and lounge.
  • It explains that where detection is only on the route the alarm would only sound once a fire was well advanced, and that where there is smoke detection within the rooms (LD2 coverage) the alarm sounds early and seals help keep smoke off the route.
  • The alarms here cover the communal rooms as well as the route, so whether the doors to those rooms need smoke seals is for the fire risk assessment, and some councils now ask for them on the kitchen door; the government’s 2026 hazard rating guidance says LACORS is out of date on detection.
  • In a low-risk three-storey shared house, existing doors onto the route may be accepted if they are sound, solid, close fitting and self-closing; hollow infill (egg-box) doors are not.

FD30The doors from the route into the rooms that hold the fire risk are FD30 fire doors, without smoke seals in LACORS’s case study.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5, note 8In existing three-storey shared houses of low risk, existing walls and partitions may be accepted if 20 minutes of fire resistance can be achieved, which sound, conventional construction, including sound lath and plaster, is likely to give; doors onto the route may be accepted if they are sound, solid, close fitting and self-closing.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.3Smoke seals are usually fitted to fire doors, but not where detection is only in the escape route, as in many three-storey shared houses: there the smoke detectors would only operate when the fire is well advanced, so the seals’ benefit is outweighed. Where smoke detection is within the rooms (LD2 coverage), the alarm sounds early and smoke seals help keep smoke out of the escape route.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.6In lower risk premises, existing well fitted and well made solid doors may be acceptable; non-fire-resisting glazed doors, flimsy doors and hollow infill doors (known as egg-box doors) are not.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.

What a fire risk assessor checks

  1. Doors from the route into the rooms: rating, fit, closers, and locks that open from inside without a key

    Benchmark: LACORS (2008), for a shared house of three or four storeys: FD30 doors to the risk rooms without smoke seals (case study D5), with its alarms on the route and in the kitchen and lounge; where there is smoke detection within the rooms, which it calls LD2 coverage, it says seals help keep smoke off the route (para 21.3). Here the lounge and dining room have smoke alarms and the kitchen a heat alarm, so whether their doors need seals is for the fire risk assessment; some councils now ask for seals on the kitchen door.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.3Smoke seals are usually fitted to fire doors, but not where detection is only in the escape route, as in many three-storey shared houses: there the smoke detectors would only operate when the fire is well advanced, so the seals’ benefit is outweighed. Where smoke detection is within the rooms (LD2 coverage), the alarm sounds early and smoke seals help keep smoke out of the escape route.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.

    A defect the source namesNon-fire-resisting glazed doors, flimsy doors and hollow infill (egg-box) doors are not acceptable.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 21.6In lower risk premises, existing well fitted and well made solid doors may be acceptable; non-fire-resisting glazed doors, flimsy doors and hollow infill doors (known as egg-box doors) are not.
Show in the 3D model

Fire alarm (shared house)

  • Detection and alarm
Show in the 3D model

Interlinked mains-powered alarms with backup batteries: smoke alarms on the route at every level and in the communal rooms, and a heat alarm in the kitchen.

  • For an existing three-storey shared house BS 5839-6 recommends Grade D1, Category LD2, which leaves the bedrooms out, as LACORS’s 2008 guidance for existing housing does in a shared house of normal risk.
  • The government’s 2026 hazard rating guidance says LACORS is out of date on detection, and gives the same grade and category for a three-storey house.
  • Its licence must also require a carbon monoxide alarm in any room used as living accommodation (a hall, landing, bathroom or WC counts) that has a fixed combustion appliance other than a gas cooker.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 22.10For shared houses of normal risk, detection in bedrooms is not normally recommended, so a mixed system is not recommended.
  • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Schedule 4, para 1(4), (4A), (6) and (7), and para 1A(2) and (9)An HMO licence must include conditions requiring the licence holder to ensure that a smoke alarm is installed on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any room used wholly or partly as living accommodation (a hall, landing, bathroom or lavatory counts) that has a fixed combustion appliance other than a gas cooker; and that no room used as sleeping accommodation by one person over 10 is smaller than 6.51 m2, or 10.22 m2 for two people over 10, not counting floor where the ceiling is lower than 1.5 m.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.
  • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Appendix ABaseline indicators for rented single-family dwellings and shared houses with no floor greater than 200 m2: for existing premises, a three-storey house Grade D1, Category LD2, and a house of four or more storeys Grade D1, Category LD1.
  • StandardBS 5839-6, clause 9.2 a) Note 1, and Table 1 with its note B (opens in a new tab)For an existing shared house of up to three storeys let to no more than six people as one group, Table 1 recommends Grade D1, Category LD2; when Table 1 counts a house’s storeys, basement storeys can be ignored. Larger HMOs fall in other rows, with a communal system.Why it applies here: The shared house is let to six sharers and has three storeys above its lower ground floor.

What a fire risk assessor checks

  1. The shared house’s alarms: grade, category, where they are, interlinked, tested, and the carbon monoxide alarm

    Benchmark: Grade D1, Category LD2 for a shared house of up to six on up to three storeys; LACORS (2008) shows Grade D, LD3 with alarms in the kitchen, lounge and cellar, though the 2026 hazard rating guidance says it is out of date on detection; the licence asks a smoke alarm on each storey with living accommodation, and a carbon monoxide alarm in any room used as living accommodation with a fixed combustion appliance other than a gas cooker.

    • StandardBS 5839-6, clause 9.2 a) Note 1, and Table 1 with its note BFor an existing shared house of up to three storeys let to no more than six people as one group, Table 1 recommends Grade D1, Category LD2; when Table 1 counts a house’s storeys, basement storeys can be ignored. Larger HMOs fall in other rows, with a communal system.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 22.10For shared houses of normal risk, detection in bedrooms is not normally recommended, so a mixed system is not recommended.
    • GuidanceHousing Health and Safety Rating System (HHSRS): Operating guidance, Part 3: a supplementary guide to the hazard of fire and explosions, Part 3, Fire Safety Guidance, pp.51 to 52LACORS was published in 2008 and some of its content is out of date, particularly on domestic fire detection and firefighting equipment. It is likely to remain the most appropriate guidance for a range of existing residential premises, including single household properties, shared houses, bedsit HMOs and buildings converted into self-contained flats to a standard not in compliance with the Building Regulations 1991.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Schedule 4, para 1(4), (4A), (6) and (7), and para 1A(2) and (9)An HMO licence must include conditions requiring the licence holder to ensure that a smoke alarm is installed on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any room used wholly or partly as living accommodation (a hall, landing, bathroom or lavatory counts) that has a fixed combustion appliance other than a gas cooker; and that no room used as sleeping accommodation by one person over 10 is smaller than 6.51 m2, or 10.22 m2 for two people over 10, not counting floor where the ceiling is lower than 1.5 m.
Show in the 3D model

Bedrooms (shared house)

  • Means of escape
Show in the 3D model

A licensed HMO’s licence sets national minimum sizes for rooms used for sleeping:

  • 6.51 m2 for one person over 10 and 10.22 m2 for two, not counting floor where the ceiling is under 1.5 m.

Councils set their own amenity standards on top.

Here the six bedrooms are from 9.4 m2 to 21.4 m2, all above the 6.51 m2 minimum.

30 minutesAssumed: the bedrooms open off the protected route, so the walls between them and the route are its 30-minute construction, and their doors are the FD30 fire doors to the rooms, as LACORS’s 2008 case study for a shared house of three or four storeys gives them.

  • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Schedule 4, para 1(4), (4A), (6) and (7), and para 1A(2) and (9)An HMO licence must include conditions requiring the licence holder to ensure that a smoke alarm is installed on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any room used wholly or partly as living accommodation (a hall, landing, bathroom or lavatory counts) that has a fixed combustion appliance other than a gas cooker; and that no room used as sleeping accommodation by one person over 10 is smaller than 6.51 m2, or 10.22 m2 for two people over 10, not counting floor where the ceiling is lower than 1.5 m.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Laundry room, not a seventh bedroom

  • Means of escape
Show in the 3D model

This room at the end of the first floor outrigger is big enough to be a bedroom, and it is kept as a laundry and store.

  • The licence sets the most people the house may hold, here six.
  • A seventh sharer would also take it past the row of BS 5839-6 Table 1 for shared houses of up to six, into the larger HMO group with a communal system.

30 minutesAssumed: the model treats the laundry, with its machines, as a room that holds a fire risk, so, as LACORS’s 2008 case study for a shared house of three or four storeys gives every such room, it is enclosed from the route in 30-minute construction with an FD30 door.

  • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Schedule 4, para 1(4), (4A), (6) and (7), and para 1A(2) and (9)An HMO licence must include conditions requiring the licence holder to ensure that a smoke alarm is installed on each storey with a room used wholly or partly as living accommodation, and a carbon monoxide alarm in any room used wholly or partly as living accommodation (a hall, landing, bathroom or lavatory counts) that has a fixed combustion appliance other than a gas cooker; and that no room used as sleeping accommodation by one person over 10 is smaller than 6.51 m2, or 10.22 m2 for two people over 10, not counting floor where the ceiling is lower than 1.5 m.
  • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Section 61(2)An HMO licence authorises occupation by not more than a maximum number of households or persons specified in the licence.
  • StandardBS 5839-6, clause 9.2 a) Note 1, and Table 1 with its note B (opens in a new tab)For an existing shared house of up to three storeys let to no more than six people as one group, Table 1 recommends Grade D1, Category LD2; when Table 1 counts a house’s storeys, basement storeys can be ignored. Larger HMOs fall in other rows, with a communal system.Why it applies here: The shared house is let to six sharers and has three storeys above its lower ground floor.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Roof void and loft hatch

  • Compartmentation
Show in the 3D model

The roof void over a house that has no loft rooms is reached through a hatch from the top landing.

  • It is where the party wall and its fire stopping can be seen, so a fire risk assessment tries to look in, and records it when it cannot.

Here the shared house has no loft rooms, so its top storey is the second floor, 8.7 m above the garden.

The same house converted into flats has a loft conversion, which takes its top storey to 11.5 m.

  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 15.7, commentary (opens in a new tab)Fire spread through the roof void of a low-rise pitched-roof building has led to at least one fatal fire, so the assessor tries to include roof voids even in a Type 1 assessment, sampling them, and records it if access was not practicable. In old blocks of flats the compartment walls between flats might not extend through the roof void, as building regulations would now require.Why it applies here: The party walls run up through the pitched roof void.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Party walls

  • Compartmentation
Show in the 3D model

The wall between two houses in a terrace separates two buildings.

  • For new work it should resist fire for at least 60 minutes, run the full height of the building, and carry on up through the roof space to the underside of the roof.
  • LACORS’s 2008 guidance for existing housing also lists walls separating buildings for 60 minutes.

The model takes these party walls to be sound and continuous; in a real building that is not known until they are looked at, where services pass through them and where they meet the roof.

60 minutesA wall separating two buildings resists fire for at least 60 minutes in new work (ADB Table B2), and LACORS’s 2008 guidance lists such walls for 60 minutes too.

  • LawBuilding Regulations 2010, Schedule 1, B3Internal fire spread (structure).
  • GuidanceADB Vol 1, Table B2 note †For compartment walls that separate buildings, the period of fire resistance is increased to a minimum of 60 minutes.
  • GuidanceADB Vol 1, paras 5.10 to 5.13Walls common to two buildings run the full height in a continuous vertical plane and are continued through any roof space to the underside of the roof. They meet the underside of the roof covering or deck, fire-stopped, and are continued across any eaves. A 1500 mm wide zone of the roof either side of the wall should have a covering classified BROOF(t4) on a deck of class A2-s3, d2 or better; in buildings no more than 15 m high, a combustible deck and timber battens fully bedded in mortar over the wall may carry on across it.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 15.2Walls separating one building from another are listed among the elements needing 60 minutes of protection.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Outside walls

Brick and stucco on solid Victorian walls.

  • From the mean ground level to the mean roof level the building is 12.4 m high, more than 11 m, so any new outer surface on these walls is to be class A2-s1, d0 or better.
In existing buildings

Many existing blocks were built with combustible cladding or insulation, and a large programme of remediation is under way in England.

  • LawBuilding Regulations 2010, Schedule 1, B4External fire spread.
  • GuidanceADB Vol 1, Table 10.1For residential buildings (purpose groups 1 and 2) more than 11 m high, the outermost surface of an external wall should be class A2-s1, d0 or better wherever it is. At 11 m or less: class B-s3, d2 or better less than 1000 mm from the relevant boundary, and no provision 1000 mm or more from it. Timber cladding at least 9 mm thick is accepted only where the table asks for class C-s3, d2 (note 3).
  • GuidanceADB Vol 1, Appendix A and Diagrams D4 and D6The height of a building is measured as Diagram D4 shows, from the mean ground level to the mean roof level. The height of the top storey is measured as Diagram D6 shows, from ground level on the lowest side of the building to the upper surface of the top floor. They are different heights: a block whose top storey is under 11 m can be more than 11 m high.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

The street, the gardens and the raised ground floor

Shared kitchen

  • Means of escape
  • Detection and alarm
Show in the 3D model

The shared kitchen is a risk room, a room whose use presents a risk of a fire starting.

  • It has a fire door onto the route, a heat alarm linked to the smoke alarms, and a fire blanket.
  • The national amenity standards a council applies when deciding how many people a licensed HMO can hold include appropriate fire blankets and fire doors for a shared kitchen.

FD30The kitchen is a risk room, so its door onto the route is an FD30 fire door, as for every risk room.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
  • LawThe Licensing and Management of Houses in Multiple Occupation and Other Houses (Miscellaneous Provisions) (England) Regulations 2006, Schedule 3, paras 3 and 5A shared kitchen is equipped for the number sharing it, including appropriate extractor fans, fire blankets and fire doors; and appropriate fire precaution facilities and equipment are provided of the type, number and location considered necessary.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The shared kitchen: its fire door and closer, its heat alarm, the fire blanket, and the cooker away from the route

    Benchmark: LACORS (2008), for existing housing: an FD30 door, a heat alarm linked to the rest, and a fire blanket; the national amenity standards for licensed HMOs include appropriate fire blankets and fire doors in shared kitchens.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, Case study D5A shared house of three or four storeys: a 30-minute protected route with 30-minute fire-resisting construction and FD30 doors to all risk rooms, without smoke seals; a Grade D, LD3 system of interlinked mains smoke alarms in the escape route at each floor level, with a heat alarm in the kitchen, a smoke alarm in the lounge and smoke alarms in any cellar; a fire blanket in the kitchen; emergency lighting only if the route is long or complex or has no effective borrowed light.
    • LawThe Licensing and Management of Houses in Multiple Occupation and Other Houses (Miscellaneous Provisions) (England) Regulations 2006, Schedule 3, paras 3 and 5A shared kitchen is equipped for the number sharing it, including appropriate extractor fans, fire blankets and fire doors; and appropriate fire precaution facilities and equipment are provided of the type, number and location considered necessary.
Show in the 3D model

Front lightwell

  • Means of escape
Show in the 3D model

The lightwell in front of a lower ground floor brings in daylight.

  • It only works as a way out if its steps reach the street and nothing locked stands in the way.
  • In LACORS’s 2008 guidance for existing housing, a basement well under a window is one of the things that rules the window out as an escape window.
  • GuidanceADB Vol 1, para 3.9Basement storeys containing habitable rooms should have either an emergency escape window or external door providing escape from the basement, or a protected stairway (minimum REI 30) leading from the basement to a final exit.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 14.2An escape window is accepted only where its room is no more than 4.5 m above ground and nothing such as a basement well lies under it; where it leads to a back garden with no exit, the garden should be at least as deep as the building is high.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The lightwell: steps up to the street, and nothing locked or stored in the way

    Benchmark: For new building work, Approved Document B says a basement storey with habitable rooms should have an escape window or door of its own, or a protected stair to a final exit. LACORS (2008), for existing housing: a separate exit is the ideal, and a basement well under a window can stop it being an escape window.

    • GuidanceADB Vol 1, para 3.9Basement storeys containing habitable rooms should have either an emergency escape window or external door providing escape from the basement, or a protected stairway (minimum REI 30) leading from the basement to a final exit.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 14.2An escape window is accepted only where its room is no more than 4.5 m above ground and nothing such as a basement well lies under it; where it leads to a back garden with no exit, the garden should be at least as deep as the building is high.
    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.
Show in the 3D model

Bins and cycle stores

  • Means of escape
Show in the 3D model

With no way to the back gardens except through the houses, bins and cycles are kept at the front.

  • They are kept clear of the steps, the lightwell and its railings, so they never block a way out or feed a fire under a window.
  • Here e-bikes and e-scooters are not kept or charged in the common parts: a fire risk assessment notes any lithium-ion battery vehicles, assesses their risk and deals with them in its action plan.
  • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentary (opens in a new tab)Lithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.Why it applies here: Cycles are stored at the front of the houses, by the way out.
  • Ongoing dutyThe Management of Houses in Multiple Occupation (England) Regulations 2006, Regulation 4The manager of an HMO must keep every means of escape from fire free from obstruction and in good order and repair, keep fire fighting equipment and fire alarms in good working order, and display notices showing the means of escape (not needed with four or fewer occupiers).

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. Bins and cycles at the front: clear of the steps, the lightwell and the windows; e-bikes not stored or charged in the common parts

    Benchmark: Escape routes kept clear: in the shared house a duty of its manager under the 2006 HMO management regulations; lithium-ion vehicles noted and dealt with in the action plan.

    • Ongoing dutyThe Management of Houses in Multiple Occupation (England) Regulations 2006, Regulation 4The manager of an HMO must keep every means of escape from fire free from obstruction and in good order and repair, keep fire fighting equipment and fire alarms in good working order, and display notices showing the means of escape (not needed with four or fewer occupiers).
    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentaryLithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.

    A defect the source namesLithium-ion vehicles can give very rapid fire development, toxic fumes and explosion if damaged or faulty.

    • StandardBS 9792 Fire risk assessment. Housing. Code of practice, clause 13, commentaryLithium-ion battery vehicles such as e-bikes and e-scooters can give very rapid and extreme fire development, toxic fumes and explosion if damaged or faulty; the assessment notes them and deals with them in its action plan.
Show in the 3D model

Enclosed back gardens

  • Means of escape
Show in the 3D model

The back gardens back onto other gardens, with no lane behind.

  • A garden reached only through the house is a safe place to escape to only if it is long enough to get away from the building.
  • For a new house: longer than the house is high to its mean roof level and longer than any rear extension is high.
  • In LACORS’s 2008 guidance for existing housing: at least as deep as the building is high.

The gardens here are 14.0 m long beyond the outriggers.

  • The houses are 13.2 m high from the garden to their mean roof level, the measure Approved Document B uses, and 15.0 m to the ridge.
  • LACORS does not say how it measures a building’s height.
  • GuidanceADB Vol 1, para 2.10(b) and Diagram 2.5Where escape from a house is into an enclosed space with an exit only through other buildings, such as a back garden, the length of the space should exceed the greater of the house’s height above ground to its mean roof level, and the height of any rear extension.
  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 14.2An escape window is accepted only where its room is no more than 4.5 m above ground and nothing such as a basement well lies under it; where it leads to a back garden with no exit, the garden should be at least as deep as the building is high.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Fire engine in the street

In a street of terraced houses the fire engine stops in the street, between the parked cars, and firefighters run hose from the pump up the steps, in at the front door and up the stair.

  • For flats built or converted now, Approved Document B says a pump should be able to get within 45 m of every point inside each flat, measured along the route of the hose, or the building should have fire mains.
  • That is guidance on meeting the Building Regulations, which apply to building work when it is carried out, so it does not require an existing house to be brought up to it.
  • Approved Document B’s typical specification asks for a road at least 3.7 m wide between kerbs for a pump.

Here the street is 7.0 m between kerbs, and the model takes cars to be parked on both sides, leaving about 3.0 m clear between them.

  • For new building work, Approved Document B’s typical specification for a pump’s access route gives a minimum of 3.7 m of road between kerbs (Table 13.1), and notes that appliances are not standardised.
  • Whether a pump could get through, stop and work here would need checking on a real street, with its width, parked cars, obstructions and turning.
  • From where the model stops it, a hose reaches the shared house’s front door in 11.3 m, and the farthest corner of the room at the end of its second floor outrigger in 41.0 m, up its stair.
  • For a new house, Approved Document B says a pump should be able to get within 45 m of all points inside it (para 13.1), without saying how that is measured; it is for flats that it measures along the route of the hose.
  • GuidanceADB Vol 1, para 13.2For flats, either provide access for a pumping appliance to within 45 m of all points inside each flat, measured along the route of the hose, or provide fire mains in accordance with paras 13.5 and 13.6.
  • GuidanceADB Vol 1, Table 13.1A typical access route for a pump appliance: a road at least 3.7 m wide between kerbs, gateways at least 3.1 m wide, clearance at least 3.7 m high, and a carrying capacity of 12.5 tonnes.
  • LawBuilding Regulations 2010, Regulations 3, 4, 5 and 6Building work, which includes the material alteration of a building, is to be carried out so that it complies with the applicable requirements of Schedule 1; a material change of use, such as a building coming to contain a flat where it did not before, brings the requirements regulation 6 lists. The requirements apply to the work and the change of use when they are done.
  • GuidanceADB Vol 1, para 13.1For dwellinghouses, access for a pumping appliance should be provided to within 45 m of all points inside the dwellinghouse, with a door at least 750 mm wide on each elevation to which vehicle access is provided.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

Fire hydrant in the footway

The fire engine takes water from a public hydrant on the water main under the footway.

  • Its position is shown by a plate nearby, which the water undertaker must provide.
  • For a new block of flats or other building, Approved Document B asks for hydrants of its own only if it has a compartment of more than 280 m2 and stands more than 100 m from an existing hydrant (Vol 1 para 14.8, Vol 2 para 16.8); it has no such test for houses.

The shared house is not a new building, so it would not need a hydrant of its own.

  • Approved Document B gives no hydrant guidance for houses.
  • For a new block of flats or other building it asks for one only where a compartment is over 280 m2 and the building stands more than 100 m from an existing hydrant.
  • The shared house’s four storeys come to about 256 m2 in all.
  • LawThe Fire and Rescue Services Act 2004, Section 42A water undertaker must cause the location of every fire hydrant it provides to be clearly indicated by a notice or distinguishing mark, which it may place on a wall or fence adjoining a highway or public place.
  • GuidanceADB Vol 1, para 14.8A building needs additional fire hydrants only if it has a compartment of more than 280 m2 and is being erected more than 100 m from an existing fire hydrant.

INFIRISK guides

No INFIRISK guide on this yet.

Show in the 3D model

The lower ground floor

Lower ground floor (shared house)

  • Compartmentation
  • Means of escape
Show in the 3D model

The communal lower ground floor is separated from the route above by 30-minute construction, with a self-closing FD30S door at the head of its stair.

  • It has the same detection as the rest of the house, and its own door to the garden.

30 minutesThe lower ground floor is separated from the route above by 30-minute construction, with a self-closing FD30S door at the head of its stair.

  • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.

INFIRISK guides

No INFIRISK guide on this yet.

What a fire risk assessor checks

  1. The lower ground floor: the self-closing FD30S door at its stair head, the floor over it, its detection, and its garden door

    Benchmark: LACORS (2008), for existing housing: 30 minutes between the basement and the floor above, an FD30S self-closing door at the stair head in a larger shared house, the same detection as the rest of the house.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, paras 10.1 to 10.7A lower ground floor below a raised entrance is treated like a basement. Ideally the floor between it and the ground floor, including the stair’s soffit and spandrel, resists fire for 30 minutes, with a 30-minute door at the head of the basement stair; in larger shared houses a self-closing FD30S door is expected there. Ideally the basement has its own exit to a place of safety, and it has the same level of automatic detection as the rest of the house.

    A defect the source namesFlimsy constructions and hollow infill (egg-box) doors are not acceptable.

    • GuidanceHousing: fire safety. Guidance on fire safety provisions for certain types of existing housing, para 10.3Flimsy constructions and hollow infill-type doors, commonly known as egg-box doors, would not be accepted between a basement and the floor above.
Show in the 3D model
  • This is guidance on what an assessor looks at, not an assessment of any real building.
  • LACORS is guidance for existing housing, not Building Regulations; its case studies are not off-the-peg solutions, and there is no obligation to adopt their exact solutions.
  • A fire risk assessment is made by a competent person (BS 9792:2025 clause 7).
  • LACORS dates from 2008. The government’s June 2026 hazard rating guidance says some of its content is out of date, particularly on domestic fire detection and firefighting equipment, but that it is likely to remain the most appropriate guidance for a range of existing homes, including shared houses and buildings converted into flats to a standard below the Building Regulations 1991.

Ongoing duties once people live here

Fire safety does not stop when the building is finished. These are the duties the law puts on whoever runs this building once people live and work in it: what must be done, by whom, when, and the law it comes from. Some apply only from a certain height; each says where it applies in this building.

  1. HMO licence and its conditions

    Who
    The person having control of or managing the shared house, and its landlord; once it is licensed, the licence holder
    What
    Make sure the house is licensed by the council, do not knowingly let more people live there than the licence allows, and, as licence holder, keep its conditions: a smoke alarm on each storey with a room used as living accommodation, a carbon monoxide alarm in any such room with a fixed combustion appliance other than a gas cooker, a gas safety certificate for the council each year if there is gas, safe electrical installations and appliances, and the minimum sizes for rooms used for sleeping.
    When
    An HMO occupied by five or more people in two or more households: the shared house, let to six.
    In this building
    Applies here at every height.
    • LawThe Licensing of Houses in Multiple Occupation (Prescribed Description) (England) Order 2018, Article 4An HMO is of a prescribed description, and so must be licensed, if it is occupied by five or more persons living in two or more separate households and meets the standard test, the self-contained flat test (not a purpose-built flat in a block of three or more) or the converted building test.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Schedule 4, paras 1 and 1AAn HMO licence must include conditions on gas safety certificates, electrical installations and appliances, smoke alarms on each storey with a room used as living accommodation, carbon monoxide alarms in such rooms with a fixed combustion appliance other than a gas cooker, and the minimum sizes of rooms used for sleeping.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Section 61(2)An HMO licence authorises occupation by not more than a maximum number of households or persons specified in the licence.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Section 72It is an offence for a person having control of or managing an HMO that must be licensed, or its landlord, if it is not; for a person having control of or managing it to knowingly allow more occupiers than the licence authorises; and for the licence holder to break a licence condition.

    In the model: Fire alarm (shared house), Bedrooms (shared house)

  2. Managing the shared house

    Who
    The manager of the shared house
    What
    Display the manager’s name, address and telephone number; keep the means of escape free from obstruction and in good repair; keep fire fighting equipment and fire alarms in good working order; display notices showing the means of escape; keep the common parts safe, in repair and reasonably clear, and any basement area railings that belong to the house in good and safe repair; and provide enough bins for each household.
    When
    Any HMO other than a converted block of flats under section 257: the shared house.
    In this building
    Applies here at every height.
    • Ongoing dutyThe Management of Houses in Multiple Occupation (England) Regulations 2006, Regulations 3, 7 and 9The manager must make their name, address and telephone number available to each household and display them; keep the common parts in good repair, safe and reasonably clear, and boundary walls and basement area railings belonging to the HMO in good and safe repair; and provide bins adequate for each household.
    • Ongoing dutyThe Management of Houses in Multiple Occupation (England) Regulations 2006, Regulation 4The manager of an HMO must keep every means of escape from fire free from obstruction and in good order and repair, keep fire fighting equipment and fire alarms in good working order, and display notices showing the means of escape (not needed with four or fewer occupiers).

    In the model: Protected escape route (shared house), Front lightwell, Bins and cycle stores

  3. The council’s housing hazard rating

    Who
    The council, assessing the landlord’s homes
    What
    The council may inspect the shared house as a whole and rate its hazards; fire and explosions is one hazard. A hazard in the high band is a category 1 hazard, which the council must act on.
    When
    Any home, for inspections begun on or after 23 June 2026 under the amended rating system.
    In this building
    Applies here at every height.
    • LawThe Housing Health and Safety Rating System (England) Regulations 2005, Schedule 1, para 23A, and regulations 7 and 8; SI 2026/571 regulation 10, as amended by SI 2026/629The hazard of fire and explosions: exposure to uncontrolled fire and associated smoke and fumes, and an explosion. A hazard in the High band is a category 1 hazard. The amended rules apply to inspections begun on or after 23 June 2026.
    • LawThe Housing Act 2004: HMOs, licensing and the housing health and safety rating system, Sections 1(4), 4 and 5(1)Residential premises include an HMO and any common parts of a building containing one or more flats. The council must arrange an inspection where it considers one appropriate or receives an official complaint, and must take enforcement action on a category 1 hazard.

    In the model: Protected escape route (shared house)

Guides behind this model

Read more on the topics this building shows.

What this model assumes

  • Seen from the street, the shared house is on the right. The house on the left is the same house converted into flats, drawn closed: only its outside is shown.
  • A composite of the type, not any real address: a mid-terrace Victorian house, 5.8 m wide, with a lower ground floor, a raised ground floor, a first and a second floor, and a rear outrigger.
  • Heights are scaled from evidence (printed ceiling heights in house listings plus 0.25 m floors). Ground is taken on the lowest side, the rear garden, which is also the front lightwell’s floor: the street is 1.67 m higher. On that reading the second floor, the top storey, is 8.73 m up.
  • The shared house is an existing house let to six sharers as one group, with no building work and no change of use, so the Building Regulations do not apply to it. It is judged under the Housing Act 2004, through the council’s hazard rating, its HMO licence and the HMO management regulations, using LACORS’s 2008 guidance for existing housing, the council’s standards and BS 5839-6.
  • Everyone leaves at once when the alarm sounds.
  • The fire engine stops in the street level with the house, between parked cars. Hose distances run along the middle of each stair flight on its slope, and across landings and rooms on plan.
  • Where neither a part’s own text nor the guidance it cites settles a fire resistance period, the model assumes one from LACORS’s 2008 guidance for existing housing, taking the more onerous value where the guidance leaves the choice to the fire risk assessment: 60 minutes in the party wall where it meets the roof, and 30 minutes, with FD30 doors, between the route and the bedrooms and the laundry. Each such value is marked as assumed where it is shown.

Approved Document B is the 2019 edition incorporating the 2020, 2022, 2025 and 2026 amendments, read for this building on 13 and 14 November 2026 and cited only for what new building work would need, and for the way it measures a building’s height. LACORS is the 2008 guidance for existing housing, read with the government’s June 2026 hazard rating guidance on fire. BS 9792:2025 and BS 5839-6:2019+A1:2020 are paraphrased. Legislation is as revised on legislation.gov.uk.

Technical review by INFIRISK editorial: 15 November 2026 · Next review: 15 February 2027

Contains public sector information licensed under the Open Government Licence v3.0.